Grou
p
Code
Name
Setting
Setting Range Unit
adjustment gain
53
Torque limit setting
0
Keypad-1
0
–12
-
54
Forward direction
retrograde torque limit
180.0
0.0
–200.0
%
55
Forward direction
regenerative torque
limit
180.0
0.0
–200.0
%
56
Reverse direction
regenerative torque
limit
180.0
0.0
–200.0
%
57
Reverse direction
retrograde torque limit
180.0
0.0
–200.0
%
For high-performance operation, the parameters of the motor connected to the inverter
output must be measured. Use auto tuning (bA.20 Auto Tuning) to measure the
parameters before you run sensorless vector operation. To run high-performance
sensorless vector control, the inverter and the motor must have the same capacity. If the
motor capacity is smaller than the inverter capacity by more than two levels, control may
be inaccurate. In that case, change the control mode to V/F control. When operating with
sensorless vector control, do not connect multiple motors to the inverter output.
5.10.1 Sensorless Vector Control Operation Setting for
Induction Motors
To run sensorless vector control operation, set dr.09 (Control Mode) to 4 (IM
sensorless), select the capacity of the motor you will use at dr.14 (Motor Capacity),
and select the appropriate codes to enter the rating plate information of the motor.
Code
Input (Motor Rating Plate Information)
dr.18 Base Freq
Base frequency
bA.11 Pole Number Number of motor poles
bA.12 Rated Slip
Rated slip
bA.13 Rated Curr
Rated current
bA.15 Rated Volt
Rated voltage
bA.16 Efficiency
Efficiency
(when no information is on the rating plate, default values are
used.)
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...