background image

Power Point 

 

User Manual 

 

Page 2 

 

1

 

Introduction 

1.1

 

Overview 

PowerPoint is a simple to use power distribution unit with a 3 phase mains input (single phase 
input available) and either 6 or 12 single phase outputs depending upon the model.  
 
Designed for applications wherever fixed or mobile power distribution is required, the PowerPoint 
distribution rack offers a 4-pole mains input isolator switch with Neutral Disconnect as standard 
and individual RCBO (RCD+MCB) per output channel. There are also 3 neon phase indicators to 
show power input to the rack. 
 
Output  circuit  rating  can  be  specified  as  either  10A,  16A  or  25  Amps  and  back  panel  options 
include either Australian GPO, Socapex, PowerCon or Hard Wired Terminals, depending upon 
the model. 

1.2

 

Features 

The PowerPoint Feature list includes: 

  A  front  panel  mounted  4-pole  mains  input  isolator  switch  with  neutral  disconnect  as 

standard provides easy access for quick isolation for the PowerPoint 

  Three neon indicators show state of input phase power. Easily visible from a distance 

  Twelve 10A, twelve 16A or six 25A output circuits 

  Residual Current circuit Breaker with Overcurrent protection (RCBO) devices for each 

output circuit are used to combine protection against current overload and short circuits 
and protection against earth leakage currents. Essentially, they protect connected loads 
and prevent users from receiving a life threatening shock. Standard on all LSC power 
products 

  The PowerPoint is at home as a 19" rackmount module in portable flight cases or touring 

frames or permanently installed in equipment racks. Versatility plus for any situation! 

  Three phase operation 

  Single phase operation possible 

  Utilising the same prov

en mechanical chassis as LSC’s premier products such as the 

APS power distribution unit, GEN VI and RED3 dimmers,  the PowerPoint is built to the 
same exacting standards ensuring great consistent performance when you need it, time 
after time. 

 

2

 

Front Panel 

 

 

 

12 channel PowerPoint  

 
 

 
See section 4 for rear panel options.

Output Load RCBO’s 

Main Input Isolator 

 

 

Input phase 

presence indicators 

 

Input phase labels 

Summary of Contents for Power Point

Page 1: ...Power Point Power Distribution System User Manual LSC Control Systems 61 3 9702 8000 info lsccontrol com au www lsccontrol com au Version 1 2 August 2021 ...

Page 2: ...nd in conjunction with this manual Servicing of this product is recommended to be carried out by LSC Control Systems Pty Ltd or its authorised service agents No liability will be accepted whatsoever for any loss or damage caused by service maintenance or repair by unauthorised personnel In addition servicing by unauthorised personnel may void your warranty LSC Control Systems products must only be...

Page 3: ...ting Up and Connecting 3 3 1 Safety 3 3 2 Unpacking 3 3 3 Mounting 3 3 4 Connections 3 3 4 1 Input Power Supply 3 3 4 2 Outputs and Phasing 3 4 Specifications and Output Options 3 4 1 Wieland Pinouts 5 4 2 Socapex Pinouts 6 5 Troubleshooting 3 5 1 Maintenance 3 5 2 Tripped Breakers 3 6 Compliance Statements 6 ...

Page 4: ... Three neon indicators show state of input phase power Easily visible from a distance Twelve 10A twelve 16A or six 25A output circuits Residual Current circuit Breaker with Overcurrent protection RCBO devices for each output circuit are used to combine protection against current overload and short circuits and protection against earth leakage currents Essentially they protect connected loads and p...

Page 5: ... OFF position before connecting or disconnecting any loads The individual outputs are fed from the following input power phases This input phase numbering is also shown on the front panel below each output circuit breaker Input Phase Output Input Phase Output 1 1 1 7 2 2 2 8 3 3 3 9 1 4 1 10 2 5 2 11 3 6 3 12 4 Troubleshooting Warning No user controls or user serviceable parts are located inside t...

Page 6: ... with rear panel mounted 5 cage clamp style terminals Supplied with 1 2m long H07 rubber 5 core x 6mm cable with 32A 5 pin 3 phase plug fitted export models supplied with no plug Supplied with 1 2m long H07 rubber 5 core x 10mm cable no connector supplied export models supplied with no plug PWP12 16 32A model supplied with 3 phase 1 2m H07 5 core x 6mm rubber cable fitted with 32A 3 phase plug PWP...

Page 7: ... 8 Active Pin 3 Chan 3 Active Pin 3 Chan 9 Active Pin 4 Chan 4 Active Pin 4 Chan 10 Active Pin 5 Chan 5 Active Pin 5 Chan 11 Active Pin 6 Chan 6 Active Pin 6 Chan 12 Active Pin 7 Not used Pin 7 Not used Pin 8 Not used Pin 8 Not used Pin 9 Chan 1 Neutral Pin 9 Chan 7 Neutral Pin 10 Chan 2 Neutral Pin 10 Chan 8 Neutral Pin 11 Chan 3 Neutral Pin 11 Chan 9 Neutral Pin 12 Chan 4 Neutral Pin 12 Chan 10 ...

Page 8: ...tral Pin 7 Chan 4 Active Pin 7 Chan 10 Active Pin 8 Chan 4 Neutral Pin 8 Chan 10 Neutral Pin 9 Chan 5 Active Pin 9 Chan 11 Active Pin 10 Chan 5 Neutral Pin 10 Chan 11 Neutral Pin 11 Chan 6 Active Pin 11 Chan 12 Active Pin 12 Chan 6 Neutral Pin 12 Chan 12 Neutral Pin 13 Earth Pin 13 Earth Pin 14 Earth Pin 14 Earth Pin 15 Earth Pin 15 Earth Pin 16 Earth Pin 16 Earth Pin 17 Earth Pin 17 Earth Pin 18 ...