LSB ATC32U01A Installation Manual Download Page 7

7

AT C 3 2 U 0 1 A   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

C r e a t e d :   1   O c t . ,   2 0 1 2

THERMOSTAT

CONFIGURATION

PROGRAMMABLE

NON PROGRAMMABLE

NIGHT SETBACK

SELECT OPTION   

 PREVIOUS                                          SAVE 

INSTALLER SETTINGS

THERMOSTAT CONFIG

SYSTEM CONFIG

ACCESSORY CONFIG

INPUT DEALER INFO

HUMIDITY CONFIG

TEMPERATURE ALGORITHM

DEMAND REDUCTION CNFG

SERVICE MODE

RESTORY DEFAULTS

ATC32U01

SELECT OPTION   

 PREVIOUS

AIRFLOW SELECTION

                                                                      CFM

HEAT STAGE 1                                              600

HEAT STAGE 2                                              750 

AUXILIARY HEAT                                          850

EMERGENCY HEAT                                      850

COOL STAGE 1                                             525

COOL STAGE 2                                             700

COOL DEHUMID 1                                        425

COOL DEHUMID 2                                        550

CONTINUOUS FAN                                       350

HEAT OFF DELAY                                           60

COOL OFF DELAY                                          30

 PREVIOUS                                             NEXT 

NOTE:

  “Motorized Valve” used here refers to a two-position 

motorized water valve, not to be confused with the modulating 
motorized water valve found in the LOOP CONFIG.

2.2.3 PROGRAMMING

Adjust the Programming options using the up/down arrow 
buttons.  Press the center button to save changes.
 

• Programmable 

(default)

 – enables 7-day    

  

programming

 

• Non-Programmable

 – disables 7-day programming

 

• Night 

Setback

 – enables night setback 

  

programming

NOTE

:  When the thermostat is confi gured for non-

programmable mode, the Display Date and Time setting 
defaults to NO.

3.0  System Confi guration

Use the System Confi guration option on the start-up screen 
to adjust critical equipment settings.

The System Confi guration information will be automatically 
obtained from each communicating control in the system.

Note 1:

 The Airfl ow Selection menu (section 3.1) will not be 

present if the connected communicating control is confi gured 
for No Blower.

Note 2: 

The Pump Confi guration menu (section 3.4) will 

not be present if the connected communicating control is 
confi gured for No Loop Confi guration (OTHER).

Note 3: 

The Valve Confi guration menu (section 3.5) will 

not be present if the connected communicating control is 
confi gured for No Loop Confi guration (OTHER). 

3.1 AIRFLOW 

SELECTION

Adjust the airfl ow settings for each system operating mode 
using the up/down arrow buttons.  Press the center button to 
select each item.
 • 

Airfl ow Settings (defaults stored in control) - 

 

 

valid range:  obtained from control (in 25 CFM   

  

increments)

 

•  Blower Off Delay (default 60 seconds) – valid 

 

 

range:  0 to 255 seconds (in 5 second increments)

NOTE 1:

  The Airfl ow Settings will only be present if the 

connected communicating control is confi gured for ECM 
blower.

NOTE 2: 

 If multiple units are connected to one thermostat, 

refer to section 3.6 for unit selection.

3.2 OPTION 

SELECTION

This option allows the confi guration of heat pump options to 
be modifi ed.

Adjust the Option settings using the up/down arrow buttons.  
Press the center button to select each item.
 

•  Motorized Valve (defaults stored in control) – 

 

 

 

valid range:  Off, On

“On” delays compressor start until the valve is fully open. 

 

 

SYSTEM CONFIGURATION

AIRFLOW SELECTION

OPTION SELECTION

UNIT CONFIG                                           YF024

PUMP CONFIGURATION

SELECT OPTION   

 PREVIOUS                                          SAVE 

Summary of Contents for ATC32U01A

Page 1: ...10 4 3 UV Lamp 10 Caution These instructions are intended to be used by the installer or service personnel End users are NOT advised to change or modify any of these settings Doing so may cause the e...

Page 2: ...This page was intentionally left blank...

Page 3: ...In areas with poor air circulation such as behind a door or in an alcove II THERMOSTAT INSTALLATION 1 Turn off all power to unit 2 If an existing thermostat is being replaced A Remove existing thermo...

Page 4: ...thermostat will not call for heating until the temperature is 69 F Adjust the Differential setting using the up down arrow buttons Navigate between Differentials using the left right arrow buttons Pr...

Page 5: ...nformation then press and hold the right arrow for 5 seconds 1 4 2 DEMO MODE OPERATION Control Demo Mode operation parameters from the Demo Operation screen shown below DEMO OPERATION OUTDOOR FAN AUTO...

Page 6: ...compressor applications 2 0 Installer Menu Settings 2 1 INSTALLER MENU SETTINGS ACCESS The Installer Settings can be accessed at any time from the Main Operating screen by holding the up down arrows...

Page 7: ...on will be automatically obtained from each communicating control in the system Note 1 The Airflow Selection menu section 3 1 will not be present if the connected communicating control is configured f...

Page 8: ...d from System Configuration screen Select VS PUMP PARALLEL when applying multiple internal flow controller units to a single loop in parallel NOTE Refer to section 3 6 3 for multi unit configuration i...

Page 9: ...ted to one another in series as shown by the figure below MODULATING VALVE CONFIGURATION DEG HEATING DELTA T 8 COOLING DELTA T 15 PREVIOUS NEXT 3 5 VALVE CONFIGURATION Configure temperature differenti...

Page 10: ...he UV lamps after the selected time has passed Adjust the UV Lamp Reminder settings using the up down arrow buttons Press the center button to save changes Cumulative Run Time default Off valid range...

Page 11: ...stages energized until the demand is fully satisfied see NOTE 1 Differential This logic will only use temperature differential to determine the appropriate heating or cooling stages for operation Thi...

Page 12: ...UT OFF O PHYSICAL INPUT ON G PHYSICAL INPUT ON H PHYSICAL INPUT OFF EMERG SHUTDOWN OFF NIGHT SETBACK OFF OVR INPUT OFF PREVIOUS NEXT 9 0 Service Mode 9 1 MANUAL OPERATION Manual Operation mode allows...

Page 13: ...TEST OFF 3 OFF HWG SP 125 4 OFF HWG DISABLED JW3 LT1 SETTING WELL PREVIOUS 9 4 FAULT HISTORY Fault History mode displays the five most recent stored fault codes for the connected communicating contro...

Page 14: ...Or 9 4 2 Flow Conditions Displays detailed blower and pump speed valve position readings that were recorded at the time the fault occurred NOTE If multiple units are connected to one thermostat refer...

Page 15: ...INFO When multiple units are connected to one thermostat UNLIKE Mult Unit Diagnostics the service personnel views each units fault information by selecting the next option 10 0 Restore Defaults The th...

Page 16: ...ce and may not be as described herein Please contact the Manufacturer s Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and o...

Reviews: