LSB ATC32U01A Installation Manual Download Page 14

AT C 3 2 U 0 1 A   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

C r e a t e d :   1   O c t . ,   2 0 1 2

14

9.5 

CLEAR FAULT HISTORY

Clear Fault History will clear all fault codes stored in the 
thermostat as well as the fault history in any connected 
communicating controls (DXM2/AXM).

9.6 MULT-UNIT 

DIAGNOSTICS

If multiple units are connected to one thermostat when 
Manual Operation, Control Diagnostics, or Dipstick 
Confi guration is selected, the service personnel will see a 
screen to select a specifi c unit by the last 4 digits of its serial 
number.

NOTE:

 Multiple units may be connected directly to the ATC 

thermostat or connected to one another in series, as shown by 
the fi gure below.

9.4.5 Possible 

Causes

 

Possible causes as to why the fault occurred

NOTE

: If multiple units are connected to one thermostat, refer 

to section 9.7.

POSSIBLE FAULT CAUSES

LOW  WATER  COIL  TEMP

LOW  WATER  TEMP - HTG

LOW  WATER  FLOW - HTG

LOW  REFRIG  CHARGE - HTG

INCORRECT  LT1  SETTING

BAD  LT1  THERMISTOR

 PREVIOUS                                        

Two 
connections 
on DXM2 
board to allow 
for multi-unit 
installation

Or

9.4.2 Flow 

Conditions

Displays detailed blower and pump speed / valve 
position readings that were recorded at the time the 
fault occurred.

NOTE

: If multiple units are connected to one thermostat, refer 

to section 9.7.

9.4.3 Input/Output 

Conditions

Displays the status of all physical and communicated 
inputs, switches, and control outputs that were 
recorded at the time the fault occurred.

NOTE

: If multiple units are connected to one thermostat, refer 

to section 9.7.

9.4.4 Confi guration Conditions

Displays the status of all dipswitch settings that were 
recorded at the time the fault occurred.

NOTE

: If multiple units are connected to one thermostat, refer 

to section 9.7.

FAULT FLOW CONDITIONS

LT1    LOW   WATER   TEMP

HEAT   1     11:11 AM   11/14

ECM   TARGET   CFM                                     800

ECM   BLOWER   RPM                                   550

FLOW   RATE   GPM                                       6.5

PUMP   SPEED                                              60%

VALVE POSITION                                            0%

 PREVIOUS                                        

FAULT I / O CONDITIONS

LT1    LOW   WATER   TEMP

HEAT   1     11:11 AM   11/14

       TSTAT           SAFETY           OUTPT

CONV COMM

HPS

Y1

Y1

LOC

CC

Y2

Y2

CO

RV

W

W

ACC1

O

O

OUTPT

ACC2

G

G

FAN

AL1

H

H

HWG

EH1

OVR

DH

PUMP

EH2

 PREVIOUS                                        

FAULT   CONFG   CONDITIONS

LT1    LOW   WATER   TEMP

HEAT   1     11:11 AM   11/14

        S1           S2              S3

1      ON      1    ON       1    ON

2      ON      2    ON       2    OFF

3      ON      3    ON       3    OFF

4      ON      4    ON       4    OFF

5      ON      5    ON

6      ON      6    ON       LT1    WELL

7      ON      7    ON       LT2    WELL

8      ON      8    ON

 PREVIOUS                                        

Summary of Contents for ATC32U01A

Page 1: ...10 4 3 UV Lamp 10 Caution These instructions are intended to be used by the installer or service personnel End users are NOT advised to change or modify any of these settings Doing so may cause the e...

Page 2: ...This page was intentionally left blank...

Page 3: ...In areas with poor air circulation such as behind a door or in an alcove II THERMOSTAT INSTALLATION 1 Turn off all power to unit 2 If an existing thermostat is being replaced A Remove existing thermo...

Page 4: ...thermostat will not call for heating until the temperature is 69 F Adjust the Differential setting using the up down arrow buttons Navigate between Differentials using the left right arrow buttons Pr...

Page 5: ...nformation then press and hold the right arrow for 5 seconds 1 4 2 DEMO MODE OPERATION Control Demo Mode operation parameters from the Demo Operation screen shown below DEMO OPERATION OUTDOOR FAN AUTO...

Page 6: ...compressor applications 2 0 Installer Menu Settings 2 1 INSTALLER MENU SETTINGS ACCESS The Installer Settings can be accessed at any time from the Main Operating screen by holding the up down arrows...

Page 7: ...on will be automatically obtained from each communicating control in the system Note 1 The Airflow Selection menu section 3 1 will not be present if the connected communicating control is configured f...

Page 8: ...d from System Configuration screen Select VS PUMP PARALLEL when applying multiple internal flow controller units to a single loop in parallel NOTE Refer to section 3 6 3 for multi unit configuration i...

Page 9: ...ted to one another in series as shown by the figure below MODULATING VALVE CONFIGURATION DEG HEATING DELTA T 8 COOLING DELTA T 15 PREVIOUS NEXT 3 5 VALVE CONFIGURATION Configure temperature differenti...

Page 10: ...he UV lamps after the selected time has passed Adjust the UV Lamp Reminder settings using the up down arrow buttons Press the center button to save changes Cumulative Run Time default Off valid range...

Page 11: ...stages energized until the demand is fully satisfied see NOTE 1 Differential This logic will only use temperature differential to determine the appropriate heating or cooling stages for operation Thi...

Page 12: ...UT OFF O PHYSICAL INPUT ON G PHYSICAL INPUT ON H PHYSICAL INPUT OFF EMERG SHUTDOWN OFF NIGHT SETBACK OFF OVR INPUT OFF PREVIOUS NEXT 9 0 Service Mode 9 1 MANUAL OPERATION Manual Operation mode allows...

Page 13: ...TEST OFF 3 OFF HWG SP 125 4 OFF HWG DISABLED JW3 LT1 SETTING WELL PREVIOUS 9 4 FAULT HISTORY Fault History mode displays the five most recent stored fault codes for the connected communicating contro...

Page 14: ...Or 9 4 2 Flow Conditions Displays detailed blower and pump speed valve position readings that were recorded at the time the fault occurred NOTE If multiple units are connected to one thermostat refer...

Page 15: ...INFO When multiple units are connected to one thermostat UNLIKE Mult Unit Diagnostics the service personnel views each units fault information by selecting the next option 10 0 Restore Defaults The th...

Page 16: ...ce and may not be as described herein Please contact the Manufacturer s Customer Service Department at 1 405 745 6000 for specific information on the current design and specifications Statements and o...

Reviews: