Chapter 7 Program
7-4
(b) It transmits data at the rising edge of M0000
(c) HSC module is equipped at slot 0 of extension base stage 1. While M00001 is on, it transmits data D00001 ~ D00006 to
internal memory address 10 ~ 15.
XGK CPU module
HSC module
Data
D area
Internal memory
Data1 D00001
10
Data2 D00002
11
Data3 D00003
12
Data4 D00004
13
Data5 D00005
14
Data6 D00006
15
7.1.2 Function Block of XGI/XGR
1. GET function block
Function Block to read data of Global constant area at XGI/XGR CPU module. That data can be saved at variable area of
XGI/XGR CPU module (Except flag area).
(1) GET function block configuration
Function block
Classification
Variable
Description
REQ Request
execution
BASE
Base where HSC module is equipped
SLOT
Slot where HSC module is equipped
Input
MADDR Global
constant
area
DONE
Function Block execution status
STAT Error
information
Output
DATA Output
data
Remark
(1) ‘###’ means that WORD, DWORD, INT, UINT, DINT, UDINT type is available.
(2) For ‘REQ’, edge signal or level signal is available.
(3) For ‘MADDR’, Global constant or integer is available.
(4) ‘Output data’ is data read from Global constant.
(5) In case of XGR, HSC module should be equipped at extension base.
Function block is classified as follows according to output variable type.
Function Block
Output variable type
Operation description
GET_WORD
WORD
Reads WORD data from Global constant area (MADDR).
GET_DWORD DWORD
Reads
DWORD
data
from Global constant area (MADDR).
GET_INT
INT
Reads INT data from Global constant area (MADDR).
GET_UINT
UINT
Reads UINT data from Global constant area (MADDR).
GET_DINT
DINT
Reads DINT data from Global constant area (MADDR).
GET_UDINT
UDINT
Reads UDINT data from Global constant area (MADDR).