Appendix 3 GM Function Block Conversion Program
App3-3
(b) Pulse input type setting
Function Block Type
Classifica
tion
Variable
name
Type
Contents
REQ BOOL
FB execution
Executed when changing “0->1” ( : Rising edge)
BASE USINT
Base Number
Base number where HSC module is equipped
SLOT USINT
Slot Number
Slot number where HSC module is equipped
Ch0
_Fxy_CH0_PLS_MODE 01
MADDR UINT
Channe
l
Ch1
_Fxy_CH1_PLS_MODE 26
0
2phase 1multiplication
1
2phase 2multiplication
2
2phase 4multiplication
3
CW/CCW
4
1phase 1input 1multiplication(Program up/down input)
5
1phase 1input 2multiplication(Program up/down input)
6
1phase 2input 1multiplication(B phase up/down input)
Input
DATA DWORD
Pulse
input
mode
setting
7
1phase 2input 2multiplication (B phase up/down input)
DONE BOOL
Execution
status
If it completes, it outputs 1 and holds. If error occurs, it
outputs 0
Output
STAT USINT
Error status
In case of error, outputs error code
(c) Ring count lower limit setting
Function Block type
Classific
ation
Variable
name
Type
Contents
REQ BOOL
FB execution
Executed when changing “0->1” ( : Rising edge)
BASE USINT
Base Number
Base number where HSC module is equipped
SLOT USINT
Slot Number
Slot number where HSC module is equipped
Ch0
_Fxy_CH0_RING_MIN 04
MADDR UINT
Channel
Ch1
_Fxy_CH1_RING_MIN 29
Input
DATA DWORD
Ring Count lower
limit
-2,147,483,648 ~ 2,147,483,647
DONE BOOL
Execution status
If it completes, it outputs 1 and holds. If error occurs, it
outputs 0
Output
STAT USINT
Error status
In case of error, outputs error code
Summary of Contents for XGF-HD2A