Chapter 2 Specifications
2 - 2
2.2 Performance Specifications
Performance specifications of Pnet I/F module are as described below.
Item
Details
Module Type
Master
Network Type
Profibus-DP
Standard
EN50170/DIN19245
Interface
RS-485 (Electric)
Transmission Route
Bus type
Modulation Type
NRZ (Non Return to Zero)
MAC
Token Passing
Max. Distance &
Transmission Speed
Distance (m)
Transmission Speed (bps)
1,200
9.6k/19.2k/93.7k/187.5k
400
500k
200
1.5M
100
3M/6M/12M
Max. number of stations per
network
64
Max. number of stations per
segment
32 (including master & repeater)
Cable used
Electric-twist shielded pair cable
Max. input size per slave
244 bytes
Max. output size per slave
244 bytes
Max. input size of master
15,616 bytes (64 station * 244bytes/station)
Max. output size of master
15,616 bytes (64 station * 244bytes/station)
Communication Transmission
cycle
*1
10/20/50/100/200/500ms, 1/5/10s
Communication Reception
cycle
Main unit scan ×2 + Data reception time
*2
+ Communication module scan
Communication Parameters
to set
PROFICON (XBL-PMEC Dedicated Configuration Tool)
Internal-consumed current
(mA)
300
Weight (g)
86 (Including connector 122)
[Table 2.2.1] Performance Specifications
Summary of Contents for XBL-PMEC
Page 50: ...Chapter 5 PROFICON Setting 5 18 Figure 5 4 8 Network topology collected and composed...
Page 84: ...Chapter 7 Program Example 7 12 Figure 7 3 3 Screen of communication module setting...
Page 91: ...Chapter 8 Troubleshooting 8 3 8 5 Troubleshooting 8 5 1 Connection error on PROFICON XG5000...
Page 99: ...Appendix A 7 A 4 External Dimensions Unit mm XBL PMEC XBL PMEC...