Technical catalog for Susol & Metasol ACB
G
4. Draw-Out Operation
1. Please stop handle operation when draw in/out locking device protrudes.
2. Draw in or out by moving handle right or left side when draw in/out locking device can not be inserted.
Caution
1. Keep pushing the OFF button when the circuit breaker in a trip condition,
and insert a handle to the body of the circuit breaker.
2. Check the draw-out handle properly inserted and then push the lock plate
and turn the draw-out handle counterclockwise in order to insert the
breaker.
3. When the breaker reaches the TEST position, the lock plate automatically
projects and the draw-out handle is locked.
4. Push in the lock plate and turn the draw-out handle again counter-
clockwise until the lock plate projects, At this time, the draw-out operation
is finished with indicator which shows DISCONNECTED position.
5. The circuit breaker indicated with ‘DISCONNECTED’ can be separated safely from the cradle by removing a draw
in/out handle and releasing right and left locks.
6. Use a lifting hook to separate a circuit breaker from a cradle.
Draw-Out Operation Procedure
Summary of Contents for Metasol Series
Page 32: ...31 D Digital Trip Relay D 3 Internal Circuit Diagram Internal Circuit Diagram ...
Page 38: ...37 D Digital Trip Relay D Ground Fault Protection 4 Relay Function ...
Page 39: ...38 Technical catalog for Susol Metasol ACB Technical catalog for Susol Metasol ACB D D IDMTL ...
Page 40: ...39 D Digital Trip Relay D PT A Curve 4 Relay Function ...
Page 136: ...K 136 138 1 Control Circuit 2 External Dimension Control Circuit and Dimension 135 ...
Page 153: ...152 Technical catalog for Susol Metasol ACB Technical catalog for Susol Metasol ACB Memo ...
Page 154: ...153 Technical Materials Memo ...