79
G
1.
수동조작
4. Keep pushing the OFF button when the circuit breaker in a trip condition, and insert a handle to the body of the
circuit breaker.
5. Check the draw-out handle properly inserted and then push the lock plate and turn the draw-out handle clockwise
in order to insert the breaker.
6. When the breaker reaches the TEST position, the lock plate automatically projects and the draw-out handle is locked.
7. Push in the lock plate and turn the draw-out handle again clockwise until the lock plate projects, the inserting
operation is finished. At this time, the draw-out position indicator shows CONNECTED position.
1. Operating handle of cradle only can be inserted when
pushing OFF button.
2. If locking device for draw in/out protrudes, stop handle
operation and move to next procedure as it indicates
the complete operation of ongoing process.
Caution
3. Draw-in Operation
Disconnected
Position
Tested
Position
Connected
Position
Operation