L-Proxy User Manual
47
LOYTEC
Version 3.1
LOYTEC electronics GmbH
Figure 40: Data point details page.
Clicking on the
Set
button writes the new value to the device’s data server. When setting a
value, the Web page displays the status of the action:
•
Successfully set value
: The new value has been successfully set in the data point and
the update has been sent on the network, if it is a network data point.
•
Could not send value update
: The new value has been set but it has not been sent out
on the network. The reason can be that the peer node is currently offline or there is a
configuration error. The data point status reflects this error.
•
Could not set value (error code
): The new value has not been set because of an
internal error. Please contact LOYTEC with the error code.
5.3 Device Statistics
The device statistics pages provide advanced statistics information about the CEA-709
device, the CEA-852 device, the System Log, and the Ethernet interface.
5.3.1 IP Statistics
Figure 41 shows the IP statistics page. It allows finding possible problems related to the IP
communication. Specifically, any detected IP address conflicts are displayed (if the L-
Proxy’s IP address conflicts with a different host on the network).