LOYTEC CEA-709 User Manual Download Page 31

L-Switch User Manual 

31 

LOYTEC  

Version 6.0 

 

LOYTEC electronics GmbH   

shapes  or  by  placing  phantom  routers  in  e.g.  NL-220.  Please  contact  LOYTEC  support  if 
you think you need this feature! 

If the mode is changed via the console menu, it cannot changed via the corresponding DIP 
switch  anymore  (see  Section  2.4).  Choose  “[4]  Set router configuration according to DIP 
switch”, to return control to the DIP switch. 

3 - Group learning 

This  menu  option  allows  enabling  or  disabling  learning  of  group  addresses  (see  Section 
4.1.1.3). 

5 – Block unknown domains 

The  L-Switch  XP  will  learn  up  to  four  domains.  If  your  network  contains  more  than  four 
domains please contact LOYTEC support for advice! 

6 – Factory reset w. status button 

In case the L-Switch XP is in the mode repeater or smart switch, pressing the status button 
longer  than  20  seconds  resets  the  switching  tables  (see  Section  5.1).  This  function  can  be 
disabled using this menu option. 

5.3.6  Reset configuration (load factory defaults) 

This menu item allows resetting the device into its factory default state. The following menu 
appears.  

Reset Configuration Menu 
======================== 
 
[1]  Reset everything to factory defaults 
[2]  Reset switch configuration to factory defaults 
[3]  Reset all passwords 
 
[q]  Quit 
 
Please choose: 

Figure 23 Reset to factory defaults menu. 

1 – Reset everything to factory defaults 

Pressing “1” resets the complete device to factory defaults (including error log etc.). 

2 – Reset switch configuration to factory defaults 

Pressing “2” performs a reset identical to pressing the status button longer than 20 seconds 
(see Section 5.5). Use this menu item if you are moving CEA-709 network nodes between 
different CEA-709 channels. 

5.4  Network Diagnostics 

The L-Switch XP provides simple network diagnostics via its port LEDs: 

If the port LED does not light up at all this port is not connected to any network segment or 
the connected network segment currently shows no traffic. 

If the port LED is flashing green the state of the network segment connected to this port is 
ok. 

Summary of Contents for CEA-709

Page 1: ...L Switch XP CEA 709 Router User Manual LOYTEC electronics GmbH...

Page 2: ...R ANY OTHER APPLICATION IN WHICH IN THE FAILURE OF SUCH PRODUCT COULD CREATE A SITUATION IN WHICH PERSONAL INJURY OR DEATH MAY OCCUR LOYTEC MAKES NO REPRESENTATION AND OFFERS NO WARRANTY OF ANY KIND R...

Page 3: ...rt 14 2 6 3 LS 11CB 2 Port 14 2 6 4 LS 13300CB 3 Port 15 2 6 5 LS 33300CB 3 Port 15 2 6 6 LS 13333CB 5 Port 16 2 6 7 LS 11333CB 5 Port 17 2 7 Wiring 17 3 Network Media 19 3 1 TP 1250 19 3 2 FT 10 20 3...

Page 4: ...les 32 6 The L Switch XP in a Network 33 6 1 L Switch XP as Smart Switch 33 6 2 L Switch XP as Configured CEA 709 Router 34 6 3 Wink action 34 7 Updating the L Switch XP Firmware 35 7 1 Firmware Updat...

Page 5: ...Time IP Internet Protocol IP 852 logical IP channel that tunnels CEA 709 packets according CEA 852 LSD Tool LOYTEC System Diagnostics Tool MAC Media Access Control MD5 Message Digest 5 a secure hash f...

Page 6: ......

Page 7: ...the L Switch XP can be configured via the network In addition to the Plug Play switch mode the L Switch XP can be operated as a standard configured CEA 709 router In this operating mode the L Switch...

Page 8: ...types e g power line and FT Network monitoring and network management 1 2 Scope This document covers L Switch XP devices with firmware version 6 0 See Section 10 for differences between the different...

Page 9: ...closure is 9 TE 1 TE 17 5 mm wide for DIN rail mounting following DIN 43 880 see Figure 1 Status Button DIP Switch Console Connector Status LED Port LEDs Figure 1 L Switch XP multi port enclosure dime...

Page 10: ...e ID of each port NIDx Unless stated otherwise all bar codes are encoded using Code 128 An additional label is also supplied with the L Switch XP for documentation purposes Internally the 3 Port LS xx...

Page 11: ...n 6 0 LOYTEC electronics GmbH Figure 3 Internal assignment of NIDs on LS xxx00CB Figure 4 Example of internal NID order on LS xxx00CB Figure 5 Internal assignment of NIDs on LS xxxxxCB Figure 6 Exampl...

Page 12: ...e DIP switch assignment is shown in Table 1 For details see Chapter 4 DIP Switch Function Factory Default 1 2 ON ON L Switch XP switch mode ON OFF L Switch XP repeater mode OFF ON L Switch XP subnet l...

Page 13: ...mends using its LPOW 2415B power supply with the L Switch XP 2 6 Connecting Diagrams The L Switch XP provides screw terminals to connect to the network as well as to the power supply The screw termina...

Page 14: ...0 Channel Port 1 15 Earth Ground 16 17 Power Supply do not connect terminal 17 to earth ground Table 5 L Switch XP Terminals LS 13CB 2 6 3 LS 11CB 2 Port Terminal Function 1 Earth Ground 2 3 CEA 709 A...

Page 15: ...Channel Port 1 24 Earth Ground 25 26 Power Supply do not connect terminal 26 to earth ground Table 7 L Switch XP Terminals LS 13300CB 2 6 5 LS 33300CB 3 Port Terminal Function 1 6 NC 7 Earth Ground 8...

Page 16: ...l Port 5 4 Earth Ground 5 6 CEA 709 A B of FT 10 Channel Port 4 7 Earth Ground 8 9 CEA 709 A B of FT 10 Channel Port 3 10 Earth Ground 11 12 CEA 709 A B of FT 10 Channel Port 2 13 Earth Ground 14 15 C...

Page 17: ...Terminals LS 11333CB 2 7 Wiring Every network segment connected to the L Switch XP needs to be terminated according to the rules found in the specification of the transceiver see Chapter 3 Important...

Page 18: ...Switch User Manual 18 LOYTEC Version 6 0 LOYTEC electronics GmbH 100 Port not in use Power Supply Figure 7 Connecting the L Switch XP LS 13333CB Figure 7 shows an L Switch XP where Port 5 is not used...

Page 19: ...k termination LT 13 Figure 8 shows an example Figure 8 TP 1250 and FT 10 Network Termination If the collision less backbone mode recommended default behavior is disabled the L Switch XP TP 1250 ports...

Page 20: ...nd of the bus LOYTEC recommends using its L TERM network terminators LT 13 LT 33 or LT 03 for network termination see Figure 9 Figure 9 FT 10 Network Termination 3 3 RS 485 The L Switch XP RS 485 port...

Page 21: ...rs for the LONMARK TP RS485 39 channel 39 kbps are used RS 485 can only be used in a bus configuration and must be terminated on both ends The maximum stub length between the main bus and a single nod...

Page 22: ...on address of a message to which port s the message has to be forwarded or whether it has to be forwarded at all Thus it isolates local network traffic e g in case of heavy loaded networks This is the...

Page 23: ...lt all subnet or domain wide broadcasts are forwarded to all ports1 4 1 1 5 Unique Node ID Address Learning The L Switch XP has no learning strategy for unique node ID addresses Node ID addressed mess...

Page 24: ...mode of the standard CEA 709 router differs from the L Switch XP repeater mode see Section 4 1 2 While the L Switch XP repeater mode is transparent and does not require any additional configuration th...

Page 25: ...conds the next available port will be selected When the status button is released the Service Pin Message is sent out on the currently selected port If the L Switch XP is operated in smart switch mode...

Page 26: ...repeater mode Table 11 Port LED patterns 5 3 Console The L Switch XP is equipped with a serial interface to display the results of the self test allow advanced configuration via a console menu upgrade...

Page 27: ...CEA 709 port 5 FT Passed Starting CEA 709 networking Passed L Switch XP c LOYTEC electronics GmbH Mon Sep 10 08 11 41 2012 V6 0 0 Figure 15 Console messages during the boot phase The duration of a su...

Page 28: ...interface console See Section 7 2 for detailed instructions Note If you select this option accidentally you can return to the main menu by sending a break signal In case your terminal program does no...

Page 29: ...nfiguring the CEA 709 router mode CEA 709 Configuration Menu 1 Port 1 XF TP 1250 1250 kBit Port 2 FT Port 3 FT Port 4 FT Port 5 FT r Router configuration Configured Router DIP q Quit without saving x...

Page 30: ...this menu Set router mode 1 Enable Configured Router Mode 2 Enable Smart Switch Mode 3 Set router configuration according to DIP switch Please choose Figure 21 Router mode configuration menu 2 Subnet...

Page 31: ...ed using this menu option 5 3 6 Reset configuration load factory defaults This menu item allows resetting the device into its factory default state The following menu appears Reset Configuration Menu...

Page 32: ...earing the L Switch XP status and statistic data Resetting the L Switch XP back to unconfigured state All this is done when the button is released Afterwards a reset is performed to let the changes ta...

Page 33: ...ng the network cables the L Switch XP can be powered up and it will start its switching application When using a standard binding tool e g LonMaker bindings between nodes connected to different ports...

Page 34: ...ter FT 10 Router FT 10 Router FT 10 Router FT 10 Router TP 1250 Figure 24 Internal structure of a 5 Port L Switch XP in configured CEA 709 router mode Each router must be commissioned separately The p...

Page 35: ...any messages 7 1 Firmware Update via the Network Basically firmware downloads can be performed on every L Switch XP port However since the L Switch XP is not based on a Neuron Chip a new firmware imag...

Page 36: ...that Figure 25 and Figure 26 do not necessarily show the proper product Press Download to start the download A progress bar as shown in Figure 26 can be seen Figure 26 Progress bar during firmware dow...

Page 37: ...0 channel is used in standard backbone mode make sure that all L Switch XP devices have the collision less backbone mode disabled 8 2 One or more port LEDs are flashing red Problem One or more port LE...

Page 38: ...o firmware update was attempted please contact LOYTEC support see Section 8 6 8 4 LonMaker cannot commission node Problem When adding a new node to a LonMaker project LonMaker receives the service pin...

Page 39: ...lves your specific problem please contact us at the following address LOYTEC electronics GmbH Blumengasse 35 A 1170 Vienna Austria Europe email support loytec com web http www loytec com tel 43 1 4020...

Page 40: ...use the enhanced statistic features of the L Switch XP with the LOYTEC system diagnostics tool LSD tool AN006E L Switch XP and LNS How to use the L Switch XP with LonMaker and other network management...

Page 41: ...on the firmware version The L Switch XP can be used with firmware versions 3 0 and up Firmware Version Features 1 0 1 2 Final 1 2 0 3 0 3 1 4 2 6 0 Console Menu configuration firmware update Aging mec...

Page 42: ...1100 mA 24 VAC Operating Temperature ambient 0 C to 50 C Storage Temperature 10 C to 85 C Humidity non condensing operating 10 to 90 RH 50 C Humidity non condensing storage 90 RH 50 C Enclosure Instal...

Page 43: ...on LSD Tool Added application note on L Switch XP LonMaker shapes Updated application note on L Switch XP backbone mode Added application note on using L Switch XP devices with CEA 709 IP Routers Add...

Reviews: