2.3 Mounting
The device comes prepared for mounting on DIN rails following DIN EN 50 022.The
device can be mounted in any position. However, an installation place with proper airflow
must be selected to ensure that the L-Switch XP temperature does not exceed the specified
range (see Section 11).
2.4 DIP Switch Setting
The L-Switch XP uses 7 switches to select the mode of operation. The DIP switch
assignment is shown in Table 1. For details see Chapter 4.
DIP Switch #
Function
Factory Default
1, 2
ON, ON: L-Switch XP switch mode
ON, OFF: L-Switch XP repeater mode
OFF, ON: L-Switch XP subnet learning
OFF, OFF: Configured CEA-709 router
ON, ON
3
Bit-rate auto detection On/Off
(RS-485 version only)
ON
4
Must be OFF
OFF
5
Must be OFF
OFF
6
Must be OFF
OFF
7
Must be OFF
OFF
Table 1: DIP switch settings for L-Switch XP
2.5 Power Supply
The L-Switch XP can either be DC or AC powered (Table 2 to Table 3).
Terminal
Function
Note
24
Earth Ground
25, 26
Power Inputs
12-35 VDC or
12-24 VAC
± 10%
Table 2: Power Terminals for L-Switch XP multi-port LS-xxxxxCB