I273 GB I 04 14
31100126
G
B
18
M09 - ALARMS (ALAn, n=1..16)
Default
Range
P09.n.01 Alarm source
OFF
OFF-LIMx-INPx-BOOx
P09.n.02 Channel number (x)
1
1-16
P09.n.03 Latch
OFF
OFF-ON
P09.n.04 Priority
Low
Low-High
P09.n.05 Text
ALAn
(Text - 16 char)
M10 - COUNTERS CNTn (n=1..4)
Default
Range
P10.n.01 Count source
OFF
OFF-ON-INPx-LIMx-BOOx
P10.n.02 Channel number (x)
1
1-16
P10.n.03 Multiplier
1
1-1000
P10.n.04 Divider
1
1-1000
P10.n.05 Counter description
CNTn
(Text - 16 chars)
P10.n.06 Unit of measure
Umn
(Text - 6 chars)
P10.n.07 Reset source
OFF
OFF-ON-INPx-LIMx-BOOx
P10.n.08 Channel number (x)
1
1-16
M11 - PULSES PULn (n=1..5)
Default
Range
P11.n.01 Source measurement
kWh+
kWh+,kWh-,kvarh+,kvarh-,kVAh
P11.n.02 Count unit
100
10/100/1k/10k
P11.n.03 Pulse duration
0.1
0.01-1.00
Note:
this menu is divided into 16 sections, for alarms ALA1..16
P09.n.01
– Signal that generates the alarm. It can be the overcoming of a limit threshold (LIMx), the activation of an external alarm (INPx), one Boolean logic
condition (BOOx).
P09.n.02
– Channel number (x) referred to the previous parameter.
P09.n.03
– Defines if the alarm remains latched and has to be reset manually (ON) or if it automatically resets (OFF).
P09.n.04
– If the alarm has high priority, when it is activated the display page switches automatically on the alarm page, and the alarm is shown with the
Warning icon. If instead the priority level is set to Low, the page does not change and it is shown with the ‘information’ icon.
P09.n.05
– Free text of the alarm. Max 16 chars.
Note:
this menu is divided into 4 sections, for counters CNT1..4
P010.n.01
= Signal that causes the increment of the counter (on rising edge). It can be the power-on of the multimeter (ON), the overcoming of a limit threshold
(LIMx), the activation of an external input (INPx), one logic combination (BOOx).
P010.n.02
= Number of the channel (x) referred to previous parameter.
P010.n.03
= Multiplying factor. The pulse count is multiplied by this coefficient before being displayed.
P010.n.04
= Dividing factor. The pulse count is divided by this coefficient before being displayed. If different from 1, then the counter is displayed with 2
decimal digits.
P010.n.05
= Description of the counter. Free text 16 characters.
P010.n.06
= Unit of measure of the counter. Free text 6 characters.
P010.n.07
= Signal that causes the reset of the counter. As long as this signal is true, the counter remains to value 0.
P010.n.08
= Number of the channel (x) referred to previous parameter.
Note:
this menu is divided into 5 sections, for energy count pulses PUL1..5
P11.n.01
= Type of energy to which the pulse is linked to.
P11.n.02
= Quantity of energy for each pulse. (e.g. 10Wh, 100Wh, 1kWh etc.).
P11.n.03
= Pulse duration.
M12 - BOOLEAN LOGIC (BOOn, n=1..8)
Default
Range
P12.n.01 Operand 1
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.02 Channel number (x)
1
1 - 16
P12.n.03 Logic operator 1
- - -
- - - - AND - OR - EXOR - AND NOT -
OR NOT EXOR NOT
P12.n.04 Operand 2
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.05 Channel number (x)
1
1 - 16
P12.n.06 Logic operator 2
- - -
- - - - AND - OR - EXOR - AND NOT -
OR NOT EXOR NOT
P12.n.07 Operand 3
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.08 Channel number (x)
1
1 - 16
P12.n.09 Logic operator 3
- - -
- - - - AND - OR - EXOR - AND NOT -
OR NOT EXOR NOT
P12.n.10 Operand 4
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.11 Channel number (x)
1
1 - 16
Note:
this menu is divided into 8 sections, for Boolean variables BOO1..8
P12.n.01
= First operand of the Boolean logic.
P12.n.02
= Number of the channel (x) referred to previous parameter.
P12.n.03
= Logic operation between first and second operands.
P12.n.04
= Second operand.
From
P12.n.05 to P12.n.11
– (see above).