Impulsion LED 

 

LED pulse 

Nombre d'impulsions 

1000imp / kWh   

 

Number of pulses 

1000 pulses / kWh   

Durée impulsion 

30ms 

 

Pulse length 

30ms 

Circuit d'entrée tarif

 

 

Tariff command input circuit 

Tension nominale Uc  

100 - 240V~ 

 

Rated voltage Uc 

100 - 240V~ 

Limites de fonctionnement 

85 - 264V~ 

 

Operating voltage range 

85 - 264V~ 

Fréquence nominale 

50/60 Hz

 

 

Rated frequency 

50/60Hz

 

Limites de fonctionnement 

45 - 66Hz 

 

Operating frequency range 

45 - 66Hz 

Puissance absorbée/dissipée  

0,9VA / 0,6W 

 

Power consumption/dissipation 

0.9VA / 0.6W 

Interface série RS485 

 

RS485 serial interface

 

Vitesse 

Programmable 1 200-38 400 bps 

 

Speed 

Programmable 1200-38400bps 

 

Caractéristiques techniques 

    Technical characteristics

 

Tension  

 

Voltage 

Tension nominale Us   

400V 3N~ 

 

Rated voltage Us 

400V 3N~ 

Limites de fonctionnement 

323-456V 3N~ 

 

Operating voltage range 

323-456V 3N~ 

Fréquence nominale 

50Hz

 

 

Rated frequency 

50Hz

 

Limites de fonctionnement 

45-66Hz 

 

Operating frequency range 

45 - 66Hz 

Puissance absorbée/dissipée  

2,5VA  /  1W 

 

Power consumption/dissipation 

2.5VA /  1W 

Courant 

 

Current 

Courant minimum (Imin) 

0,75A 

 

Minimum current (Imin) 

0,75A 

Courant de transition (Itr)  

1,5A 

 

Transition current (Itr) 

1,5A 

Courant de référence (Iref - Ib)  

15A 

 

Reference current (Iref - Ib)  

15A 

Curant maximal (Imax) 

 80A 

 

Max current (Imax) 

 80A 

Courant de démarrage (Ist)  

60 mA 

 

Start current (Ist)  

60 mA 

Précision 

 

Accuracy

 

Énergie active (EN 50470-3) 

Classe B 

 

Active energy (EN 50470-3) 

Class B 

Conditions de fonctionnement 

 

Ambient conditions 

Installation 

Uniquement pour usage interne 

 

Mounting 

Indoor use only 

Température d'utilisation 

-25 - +55°C 

 

Operating temperature 

-25…+55°C 

Température de stockage 

-25 - +70°C 

 

Storage temperature 

-25…+70°C 

Humidité relative 

80 % non condensante 

(IEC/EN 60068-2-78) 

 

Relative humidity 

80% non-condensing 

(IEC/EN 60068-2-78) 

Degré de pollution maximale du milieu 

2  

 

Maximum pollution degree 

2  

Catégorie de surtension 

 

Overvoltage category 

Altitude 

≤2000m 

 

Altitude 

≤2000m 

Séquence climatique 

Z/ABDM (IEC/EN 60068-2-61) 

 

Climatic sequence 

Z/ABDM (IEC/EN 60068-2-61) 

Résistance aux chocs 

10g (IEC/EN 60068-2-27) 

 

Shock resistance  

10g (IEC/EN 60068-2-27) 

Résistance aux vibrations 

0.7g (IEC/EN 60068-2-6) 

 

Vibration resistance 

0.7g (IEC/EN 60068-2-6) 

Environnement mécanique 

Classe M1 

 

Mechanical environment 

Class M1 

Environnement électromagnétique 

Classe E1 

 

Electromagnetic environment 

Class E1 

DME 301 n°1

DME 301 n°31

TR

SG

A

B

RS485

PX1

SG

B

TR A

PC

TR

SG

A

B

RS485

DME D301

PX1

B

TR A

SG

B

TR A

SG

SG

TR A

B

PX1

PC

Device addresses n° 1-30

TR

PX1

TR

SG

A

B

SG

A

B

DME D301

Device addresses n° 31-60

up to 255 devices

Repeat this wiring diagram

Set as repeater

Set as repeater

TR

SG

A

B

RS485

TR

SG

A

B

RS485

Summary of Contents for DMED301MID

Page 1: ...s Geräts befinden und vom Bediener leicht zugänglich sein Er muss als Trennvorrichtung für das Gerät gekennzeichnet sein IEC EN 61010 1 6 11 2 Das Gerät mit einem weichen Tuch reinigen keine Scheuermittel Flüssigreiniger oder Lösungsmittel verwenden ADVERTENCIA Leer atentamente el manual antes de instalar y utilizar el regulador Este dispositivo debe ser instalado por personal cualificado conforme...

Page 2: ... measurement accuracy is compliant with reference standard EN 50470 3 Class B while the reactive energy with IEC EN 62053 23 Class 2 In addition to energy metering it can measure further quantities which can be viewed on the backlight LCD display The DME D301MID has a standard 4U 72mm wide modular housing and is supplied with sealable terminal blocks Description Boîtier modulaire 4U 72 mm pour rai...

Page 3: ...L2 L3 Hz Fréquence 00 0 h Part Compteur horaire hhhhh mm 00000 00 L1 L2 L3 kW d Puissance active moyenne demande sur 15 min 00 00 kW d Max puissance active moyenne demande max 00 00 Selection of readings By pressing the keys it is possible to select the readings on the display following the sequence in the table reported below Each measurement unit is indicated by the correspondent icon in the low...

Page 4: ...ce of imported and exported energy The pulsing rate of the LED gives an immediate indication of the power flowing in every moment The pulse duration colour and intensity of the LED are compliant with the reference standards that define its utilisation in order to verify the accuracy of the energy meter Indication du débit d énergie Quand un appareil détecte un débit d énergie vers la charge l écra...

Page 5: ...if 1 Énergie Réactive Exp L3 2 kvarh 1000 1BFCh Tarif 2 Énergie Active Imp L3 2 kWh 1000 1C00h Tarif 2 Énergie Active Exp L3 2 kWh 1000 1C04h Tarif 2 Énergie Réactive Imp L3 2 kvarh 1000 1C08h Tarif 2 Énergie Réactive Exp L3 2 kvarh 1000 0002h Tension de Phase L1 2 V 100 0004h Tension de Phase L2 2 V 100 Modbus address table By modbus function 03 or 04 the following measures can be read from the d...

Page 6: ...e peut être utilisée pour la sélection entre deux tarifs T1 et T2 avec compteurs d énergie séparés la mise à zéro des compteurs partiels des compteurs horaires et de la demande max en activant l entrée l activation du compteur horaire 0006h L3 Phase Voltage 2 V 100 0008h L1 Current 2 A 10000 000Ah L2 Current 2 A 10000 000Ch L3 Current 2 A 10000 000Eh L1 L2 Voltage 2 V 100 0010h L2 L3 Voltage 2 V 1...

Page 7: ... clearing of partial energy meters CLEAR h simultaneous clearing of all 3 partial hour counters if enabled CLEAR d clearing of max demand values if enabled SET DEF set all parameters to default values SETUP programming of parameters set up INFO revision and checksum of internal software ESC return to normal operation 5 To select a function press while the required function is displayed For clearin...

Page 8: ...marque les mesures sont mises à jour et intégrées 1 fois par seconde Remarque Si P2 02 P2 03 le compteur horaire s active quand la mesure spécifiée par P2 01 devient supérieure à P2 02 et se désactive quand elle redevient inférieure à P2 03 fonction de seuil maximal avec hystérésis Si au contraire P2 02 P2 03 le compteur horaire s active quand la mesure spécifiée par P2 01 est inférieure à P2 02 e...

Page 9: ...l includes the harmonic contribution same vale as TOT case P08 01 Serial address node fot the communication protocol P08 02 Transmission speed of the communication port P08 03 Data format 7 bit settings possible only with ASCII protocol P08 04 Stop bit number P08 05 Communication protocol selection P7 02 Sélectionne la méthode de calcul pour la puissance réactive TOT la puissance réactive inclut é...

Page 10: ...tial exported reactive energy 47 kvarh L1 Part Énergie réactive L1 exportée partielle 47 kvarh L1 Part Partial exported L1 reactive energy 48 kvarh L2 Part Énergie réactive L2 exportée partielle 48 kvarh L2 Part Partial exported L2 reactive energy 49 kvarh L3 Part Énergie réactive L3 exportée partielle 49 kvarh L3 Part Partial exported L3 reactive energy 50 kW d Demande de puissance active 50 kW d...

Page 11: ...nt Iref Ib 15A Curant maximal Imax 80A Max current Imax 80A Courant de démarrage Ist 60 mA Start current Ist 60 mA Précision Accuracy Énergie active EN 50470 3 Classe B Active energy EN 50470 3 Class B Conditions de fonctionnement Ambient conditions Installation Uniquement pour usage interne Mounting Indoor use only Température d utilisation 25 55 C Operating temperature 25 55 C Température de sto...

Page 12: ...0 49 Nm 4 4lbin Connexion interface série Serial interface connections Type de bornes À vis fixes Type of terminals Screw fixed Nbr de sorties 2 Number of outputs 2 Nbr bornes 4 Number of terminals 4 Section conducteurs min max 0 2 1 3 mm2 24 16 AWG Conductor cross section min max 0 2 1 3 mm2 24 16 AWG Couple de serrage des bornes 0 15 Nm 1 7lbin Tightening torque 0 15Nm 1 7lbin Boîtier Housing Ex...

Reviews: