Connexions circuit de commande tarif

 

 

Tariff command circuit connections 

 

 
 
 
 

Isolation

 

 

Insulation 

 

Tension nominale d'isolation Ui 

250V~ 

 

Rated insulation voltage Ui 

250V~ 

Tension nominale de tenue aux impulsions 

Uimp 

6kV 

 

Rated impulse withstand voltage Uimp 

6kV 

Tension de tenue à la fréquence d'exercice 

4kV 

 

Power frequency withstand voltage 

4kV 

Connexions circuit d'alimentation/mesure

 

 

Supply / measurement circuit connections 

Type de bornes 

À vis (fixes) 

 

Type of terminals 

Screw (fixed) 

Nbr bornes 

7 pour l'alimentation / mesure 

 

Number of terminals 

7 for aux supply / measurement 

Section conducteurs (min…max) 

2,5…16 mm

2  

 (14…6 AWG)

 

 

Conductor cross section (min… max) 

2.5…16 mm

 (14…6 AWG)

 

Couple de serrage des bornes 

2 Nm (26,5 lbin) 

 

Tightening torque 

2 Nm (26.5 lbin) 

Type de bornes 

À vis (fixes) 

 

Terminal type 

Screw (fixed) 

Nbr bornes 

 

Number of terminals 

Section conducteurs (min…max) 

0,2…2,5 mm

   (24…12 AWG)

 

 

Cable cross section (min… max) 

0.2…2.5 mm

 (24…12 AWG)

 

Couple de serrage des bornes 

0,49 Nm (4,4lbin) 

 

Tightening torque 

0,49 Nm (4.4lbin) 

Connexion interface série

 

 

Serial interface connections 

Type de bornes 

À vis (fixes) 

 

Type of terminals 

Screw (fixed) 

Nbr de sorties 

 

Number of outputs 

Nbr bornes 

 

Number of terminals 

Section conducteurs (min…max) 

0,2…1,3 mm

2   

(24…16 AWG)

 

 

Conductor cross section (min… max) 

0.2…1.3 mm

2   

 (24…16 AWG)

 

Couple de serrage des bornes 

0,15 Nm (1,7lbin) 

 

Tightening torque 

0.15Nm (1.7lbin) 

Boîtier

 

 

Housing

 

Exécution 

4 modules (DIN 43880) 

 

Version 

4 module (DIN 43880) 

Montage 

 

Coulisse 35 mm (IEC/EN 60715) ou à 

vis au moyen de clips extractibles 

 

Mounting 

35mm DIN rail (IEC/EN 60715) 

or by screws using extractible clips 

Matériau 

Polyamide RAL 7035 

 

Material 

Polyamide RAL 7035 

Degré de protection 

IP40 sur façade (*) 

IP20 connexions 

 

Degree of protection 

IP40 on front (*) 

IP20 terminals 

Poids 

360 g 

 

Weight 

360 g 

Homologations et conformité

 

 

Certifications and compliance

 

Homologations 

EAC 

 

Certifications 

EAC 

Conformité aux normes 

EN 50470-1, EN 50470-3  

 

Reference standards 

EN 50470-1, EN 50470-3, TR50579 

*  Afin d'assurer la protection requise, l'appareil doit être installé dans un boîtier avec un degré 
de protection minimum IP51 (IEC/EN 60529). 

 

*   To comply with the protection requirements the meter must be mounted in a class IP 51 
  enclosure or better. (IEC/EN 60529). 

Summary of Contents for DMED301MID

Page 1: ...s Geräts befinden und vom Bediener leicht zugänglich sein Er muss als Trennvorrichtung für das Gerät gekennzeichnet sein IEC EN 61010 1 6 11 2 Das Gerät mit einem weichen Tuch reinigen keine Scheuermittel Flüssigreiniger oder Lösungsmittel verwenden ADVERTENCIA Leer atentamente el manual antes de instalar y utilizar el regulador Este dispositivo debe ser instalado por personal cualificado conforme...

Page 2: ... measurement accuracy is compliant with reference standard EN 50470 3 Class B while the reactive energy with IEC EN 62053 23 Class 2 In addition to energy metering it can measure further quantities which can be viewed on the backlight LCD display The DME D301MID has a standard 4U 72mm wide modular housing and is supplied with sealable terminal blocks Description Boîtier modulaire 4U 72 mm pour rai...

Page 3: ...L2 L3 Hz Fréquence 00 0 h Part Compteur horaire hhhhh mm 00000 00 L1 L2 L3 kW d Puissance active moyenne demande sur 15 min 00 00 kW d Max puissance active moyenne demande max 00 00 Selection of readings By pressing the keys it is possible to select the readings on the display following the sequence in the table reported below Each measurement unit is indicated by the correspondent icon in the low...

Page 4: ...ce of imported and exported energy The pulsing rate of the LED gives an immediate indication of the power flowing in every moment The pulse duration colour and intensity of the LED are compliant with the reference standards that define its utilisation in order to verify the accuracy of the energy meter Indication du débit d énergie Quand un appareil détecte un débit d énergie vers la charge l écra...

Page 5: ...if 1 Énergie Réactive Exp L3 2 kvarh 1000 1BFCh Tarif 2 Énergie Active Imp L3 2 kWh 1000 1C00h Tarif 2 Énergie Active Exp L3 2 kWh 1000 1C04h Tarif 2 Énergie Réactive Imp L3 2 kvarh 1000 1C08h Tarif 2 Énergie Réactive Exp L3 2 kvarh 1000 0002h Tension de Phase L1 2 V 100 0004h Tension de Phase L2 2 V 100 Modbus address table By modbus function 03 or 04 the following measures can be read from the d...

Page 6: ...e peut être utilisée pour la sélection entre deux tarifs T1 et T2 avec compteurs d énergie séparés la mise à zéro des compteurs partiels des compteurs horaires et de la demande max en activant l entrée l activation du compteur horaire 0006h L3 Phase Voltage 2 V 100 0008h L1 Current 2 A 10000 000Ah L2 Current 2 A 10000 000Ch L3 Current 2 A 10000 000Eh L1 L2 Voltage 2 V 100 0010h L2 L3 Voltage 2 V 1...

Page 7: ... clearing of partial energy meters CLEAR h simultaneous clearing of all 3 partial hour counters if enabled CLEAR d clearing of max demand values if enabled SET DEF set all parameters to default values SETUP programming of parameters set up INFO revision and checksum of internal software ESC return to normal operation 5 To select a function press while the required function is displayed For clearin...

Page 8: ...marque les mesures sont mises à jour et intégrées 1 fois par seconde Remarque Si P2 02 P2 03 le compteur horaire s active quand la mesure spécifiée par P2 01 devient supérieure à P2 02 et se désactive quand elle redevient inférieure à P2 03 fonction de seuil maximal avec hystérésis Si au contraire P2 02 P2 03 le compteur horaire s active quand la mesure spécifiée par P2 01 est inférieure à P2 02 e...

Page 9: ...l includes the harmonic contribution same vale as TOT case P08 01 Serial address node fot the communication protocol P08 02 Transmission speed of the communication port P08 03 Data format 7 bit settings possible only with ASCII protocol P08 04 Stop bit number P08 05 Communication protocol selection P7 02 Sélectionne la méthode de calcul pour la puissance réactive TOT la puissance réactive inclut é...

Page 10: ...tial exported reactive energy 47 kvarh L1 Part Énergie réactive L1 exportée partielle 47 kvarh L1 Part Partial exported L1 reactive energy 48 kvarh L2 Part Énergie réactive L2 exportée partielle 48 kvarh L2 Part Partial exported L2 reactive energy 49 kvarh L3 Part Énergie réactive L3 exportée partielle 49 kvarh L3 Part Partial exported L3 reactive energy 50 kW d Demande de puissance active 50 kW d...

Page 11: ...nt Iref Ib 15A Curant maximal Imax 80A Max current Imax 80A Courant de démarrage Ist 60 mA Start current Ist 60 mA Précision Accuracy Énergie active EN 50470 3 Classe B Active energy EN 50470 3 Class B Conditions de fonctionnement Ambient conditions Installation Uniquement pour usage interne Mounting Indoor use only Température d utilisation 25 55 C Operating temperature 25 55 C Température de sto...

Page 12: ...0 49 Nm 4 4lbin Connexion interface série Serial interface connections Type de bornes À vis fixes Type of terminals Screw fixed Nbr de sorties 2 Number of outputs 2 Nbr bornes 4 Number of terminals 4 Section conducteurs min max 0 2 1 3 mm2 24 16 AWG Conductor cross section min max 0 2 1 3 mm2 24 16 AWG Couple de serrage des bornes 0 15 Nm 1 7lbin Tightening torque 0 15Nm 1 7lbin Boîtier Housing Ex...

Reviews: