Code Description Default Range
P-01
Password 0000 0000 - 9999
P-02
Programmable limit threshold enable OFF OFF - THR
P-03
Threshold measure kW 01=kW - 02=kvar - 03=V
04=A - 05=Hz - 06=kWh Part 07=h
Part – 08 kW demand
P-04
ON threshold 100.00 0.00 – 999.99
P-05
ON delay 5 s 0 – 9999 sec.
P-06
OFF threshold 50.00 0.00 – 999.99
P-07
OFF delay 5 s 0 – 9999 sec.
P-08
Hour counter enable OFF OFF-ON-THR
P-09
Enable demand measures OFF OFF-ON
P-20
Primary address 001 001-250
P-21
Secondary address HIGH Serial n. 0000-9999
P-22
Secondary address LOW Serial n. 0000-9999
P-23
Serial speed 2400 300
600
1200
2400
4800
9600
19200
38400
SETUP PARAMETER TABLE
P-01
– If set to 0000 (default) the password protection is disabled.
P-02
– Defines the function of the programmable limit threshold:
OFF
– Programmable threshold disabled.
THR
– The programmable threshold is activated by a maximum or minimum limit, depending on values programmed in P-04 and P-06.
If P-04 > P-06, then the limit threshold activates when the measure defined by P-03 is higher than P-04, end de-activates when its value
becomes less than P-06 (maximum limit with hysteresis).
If P-04 < P-06, then the limit threshold activates when the measure defined by P-03 is lower than P-04, end activates when its value
becomes higher than P-06 (minimum limit with hysteresis).
P-03
– Selection of measure to compare with thresholds.
P-04 and P-05
– Threshold and delay for output activation. Note: The measurements are updated every 1 second, that means that the
variability of this delay is in the range from 0 to + 1 second.
P-06 and P-07
– Threshold and delay for output de-activation.
P-08
– Defines the hor counter operation:
OFF
– hour counter disabled. It is not shown on the display.
ON
– The hour counter is incremented as long as the energy meter is supplied.
THR
– The hour counter is incremented as long as the threshold defined with previous parameter ( P-02, P-03, P-04 e P-05) is active.
P-09
– Enable of calculation and visualization of active energy demand and max demand.
P-20
– Primary address.
P-21
– Secondary address, first half (4 digits).
P-22
– Secondary address, second half (4 digits). The complete secondary address can be got by concatenating the content of
parameter P-21 with the one of parameter P-22. Example: secondary address 12345678, set P-21=1234 and P-22=5678.
P-23
– Baud rate.
Codice Descrizione Default Range
P-01
Password 0000 0000 - 9999
P-02
Abilitazione soglia limite programmabile OFF OFF - THR
P-03
Misura per soglia kW 01=kW - 02=kvar - 03=V
04=A - 05=Hz - 06=kWh Part 07=h
Part – 08 kW demand
P-04
Soglia ON 100,00 0,00 – 999,99
P-05
Ritardo soglia ON 5 sec. 0 – 9999 sec.
P-06
Soglia OFF 50,00 0,00 – 999,99
P-07
Ritardo soglia OFF 5 sec. 0 – 9999 sec.
P-08
Abilitazione contaore OFF OFF-ON-THR
P-09
Abilitazione misure demand OFF OFF-ON
P-20
Primary address 001 001-250
P-21
Secondary address HIGH Serial n. 0000-9999
P-22
Secondary address LOW Serial n. 0000-9999
P-23
Serial speed 2400 300
600
1200
2400
4800
9600
19200
38400
TABELLA PARAMETRI DI SETUP
P-01
– Se impostato a 0000 (default) la protezione da password è disabilitata.
P-02
– Definisce la funzione della soglia limite programmabile:
OFF
– Soglia programmabile disabilitata.
THR
– La soglia programmabile è attivata massima oppure di minima, a seconda dei valori impostati in P-04 e P-06.
Se P-04 > P-06, allora la soglia limite si attiva con la misura di P-03 > P-04, e si disattiva quando ritorna ad essere < P-06
(funzione di soglia massima con isteresi).
Se P-04 < P-06, allora la soglia limite si attiva con la misura di P-03 < P-04, e si disattiva quando ritorna ad essere > P-06
(funzione di soglia minima con isteresi).
P-03
– Selezione misura alla quale vengono applicate le soglie.
P-04 e P-05
– Soglia e relativo ritardo per attivazione uscita. Nota: le misure vengono aggiornate ed integrate 1 volta al
secondo, quindi questo ritardo ha una variabilità da 0 a + 1 secondo.
P-06 e P-07
– Come sopra, per disattivazione uscita.
P-08
– Definisce il funzionamento del contaore:
OFF
– Contaore disabilitato, non viene visualizzato.
ON
– Il contaore si incrementa fintanto che l’energy meter è alimentato.
THR
– Il contaore si incrementa fintanto che la soglia definita con i parametri precedenti ( P-02, P-03, P-04 e P-05) è
attivata.
P-09
– Abilitazione misura e visualizzazione potenza attiva integrata attuale e massima (max demand).
P-20
– Indirizzo primario.
P-21
– Indirizzo secondario, prime 4 cifre.
P-22
– Indirizzo secondario, ultime 4 cifre. L’indirizzo secondario completo si ottiene concatenando il contenuto del
parametro P-21 con quello del parametro P-22.
Esempio: indirizzo secondario 12345678, occorre impostare P-21=1234 e P-22=5678.
P-23
– Velocità.
MECHANICAL DIMENSIONS AND WIRING DIAGRAMS
90
44.7
35.8
43.7
63
5
92.5
M-BUS CONNECTION
DME D122 n°1
Max 1000m
Max 25Ohm - 180pF
DME D122 n°250 *
M1
M2
M2 M1
M-Bus
M-Bus Master
M2
M1
M-Bus
M1
M2
M2 M1
M-Bus
NOTE:
The number of connected devices depends on the Master unit load capacity
DIMENSIONI MECCANICHE E SCHEMI DI COLLEGAMENTO
CONNESSIONE M-BUS
L
L
M2
N
M1
DME D121
220...240V 50/60Hz
0.5-10 (63)A CI. 1
100...120V 50/60Hz
Energy meter
1000
Imp/kWh
LINE
LOAD
N
N
L
L