3 4 Wiring

Figure 3: Wiring diagram

Socket

Terminal

Connection

DC input

P

connected to positive terminal of PV module

N

connected to negative terminal of PV module

AC output

M-1

connected to protective ground wire

M-2

connected to U phase of the motor

M-3

connected to V phase of the motor

M-4

connected to W phase of the motor

water level sensor input

S-1

ground

S-8

float switch 1, controlled by PR 15

S-7

float switch 2, controlled by PR 16

S-6

well probe sensor 1, controlled by PR 17

S-5

well probe sensor 2, controlled by PR 18

grounding

G

connect to proper ground

CAUTION: Ensure the exact locations of 
the DC input “P” and “N” sockets 

CAUTION: Ensure the wiring of AC 
output is based on the marks of the 
sockets 

CAUTION: To ensure proper operation 
of the system, select the wire size 
according to the following recom-
mended principle 

Prompt: Float switch 1 controlled by PR 15 and 
float switch 2 controlled by PR 16 can be combined 
to a dual float switch 

Prompt: Well probe sensor 1 controlled by PR 17 
and well probe sensor 2 controlled by PR 18 can be 
combined to a dual switch well probe 

Prompt: Please refer to chapter 4 3 Parameter for 
further information on parameter settings 

3 5 DC Disconnect switch

The pump system must be equipped with proper sized DC 
disconnect switch. The switch must be installed between 
solar generator and controller. It must meet the following 
requirements:

 

ƒ

minimum 800V DC

 

ƒ

continuous current rating according to maximum cur-
rent of pump controller or higher

 

ƒ

the switch must be rated for DC current, NOT AC

A PV disconnect switch, matching all requirements above, 
can be purchased from LORENTZ.

The use of a properly sized disconnect switch is an 
important safety measure and obligatory for a professional 
installation of a solar pumping system.

WARNING – No disconnect switches 

must be installed in power wires 
between motor and pump controller  
Connecting the motor wire to the 
switched-on controller might 
irreparably damage it  Such damages 
are excluded from the warranty 

Summary of Contents for PS15k

Page 1: ...x 29 www lorentz de All specifications and information are given with good intent errors are possible and products may be subject to change without notice Pictures may differ from actual products depe...

Page 2: ...4 1 4 Connection 4 1 5 Operation 4 1 6 Others 4 2 Introduction 5 2 1 Solar Pumping System Components 5 2 2 Product Features 5 2 3 Technical Data 5 3 Installation and Wiring 6 3 1 Purchase Inspection...

Page 3: ...rdous material danger of damage to equipment and buildings Safety oriented Operation The safety directions contained in the manual existing national regulations for the prevention of accidents as well...

Page 4: ...ouble check that input power has been disconnected before connecting the device otherwise electrocution or fire can be caused WARNING The earth terminal must be reliably grounded otherwise touching th...

Page 5: ...PV modules connected in series and in parallel absorbs solar irradiation and converts it into electrical energy providing power for the whole system The pump controller controls and adjusts the system...

Page 6: ...of the PV modules 2 pcs 4 Plug for the negative terminal of the PV modules 2 pcs 5 Motor plug 1 pc 6 sensor plug 1 pc Inspection item Inspection method Consistency with ordered product Inspect the ide...

Page 7: ...s CAUTION To ensure proper operation of the system select the wire size according to the following recom mended principle Prompt Float switch 1 controlled by PR15 and float switch 2 controlled by PR16...

Page 8: ...ug four wires yellow green wire M 1 connected to protective ground wire red wire M 2 connected to U phase of the motor yellow wire M 3 connected to V phase of the motor blue wire M 4 connected to W ph...

Page 9: ...ked with two cable ties For a pump that is to be installed in a vertical position clamp it to the pipe just above the pump outlet as shown in the photo Splice the two probe wires using the splice kit...

Page 10: ...ed electrical potentials during operation of the pump system 3 9 2 How to ground The grounding cable must be a copper cable with a cross section of at least 16mm2 For connection with the con troller u...

Page 11: ...tor light RED ON float switch or well probe status is abnormal RUN run key starting control for the controller STOP stop key shutdown control for the controller DATA data inquiry key enter or quit fro...

Page 12: ...er of controller 1 50kW MODE output current of controller 6 0A MODE time 12 30h MODE syncronous rotation speed 500 min 1 MODE controller temperature 37 C MODE water level sensor status normal water le...

Page 13: ...odified day month year selected digit flickers modify the date to be inquired 12th February ENTER confirm date to be inquired year 2008 MODE historical data accumulated generated energy of the day 9 9...

Page 14: ...displayed Display e g initial status non control parameter display PROG enter the parameter modification interface display parameter PR0 PR 0 select the parameter to be viewed and edited display para...

Page 15: ...age from PR3 according to pump model PR5 start up delay 1 to 150 start up delay time after power up or shut down in seconds 30s PR6 year 2 000 to 2 999 year must be set to actual date PR7 month 1 to 1...

Page 16: ...9 0 no well probe sensor deactivated 0 6 well probe normally closed 7 well probe normally open 8 well probe normally open for dual switch mode with well probe 1 9 well probe normally closed for dual...

Page 17: ...your LORENTZ COMPASS sizing for proper data and compare to the factory values given in the parameter setup table Another way to determine correct values is to measure the real open circuit voltage Vo...

Page 18: ...be clearly visible without measuring Set parameter PR11 to value 0 Set parameter PR12 to value 30 00 Press the RUN key to start the pump and observe the water yield from the outlet Press the STOP key...

Page 19: ...sible frequency accord ing to the available power from the PV generator MPP tracking PR11 2 Same behaviour like for PR11 1 but the pump is not starting automatically it has to be started manually by p...

Page 20: ...rt At this time the fault number will appear in the first and second digit of the numeric display The last several digits will display the countdown of the restart when the count down is 0 fault displ...

Page 21: ...as normal again This time depends on the well probe startup latency PR 27 plus the general pump start delay PR 5 abnormal coordination of float switch 1 and 2 The pump will be restarted after the con...

Page 22: ...se use the controller under environment recommended by this manual Inspect and maintain as per the following table Inspect frequency regular Inspection item Inspection content Judgment standard runnin...

Reviews: