Device Presentation 

The purpose of the RPS23 is to protect a load against DC over-current heating by the utilization of an inverse time cur-
rent characteristic. The device has a mV DC voltage input, ranging from 0 to 2000 mV over 2 calibers (0/250 mV & 
0/2000 mV), automatically selected according to the configuration of the nominal voltage. To measure a current, an ex-
ternal shunt has to be used. The current measured and displayed is signed but the protection function is carried out on 
the absolute value of the measurement. 
The relay is entirely configurable via the front face keys and display. It can be equipped with 1 to 4 relays and 1 to 2 
analog outputs. Relays 1 and 2 are affected to the thermal protection, relay 3 to nominal current overflow detection and 
relay 4 is the watchdog relay. The watchdog relay is normally closed and LED R4 is off. When a default is detected 
(internal measure error), the watchdog relay is open and LED R4 is ON.  
In normal operation, the RPS23 displays the value of the measured current (see configuration). When a default is de-
tected, the device display the following messages: 
- "

Err

" for sensor break or internal measure failure. 

 
It is necessary to notice the differences between all the models: 

RPS23

1 relay (thermal protection). 

RPS23/R2

:  2 relays (thermal protection). 

RPS23/R3

:  3 relays (idem R2 + nominal current overflow alarm). 

RPS23/R4

:  4 relays (idem R3 + watchdog). 

RPS23/S1

:  1 insulated analog output 

RPS23/S2

:  2 insulated analog outputs, independently configurable. 

 
 
The technical data sheet is downloadable here: 

http://www.loreme.fr/fichtech/RPS23_eng.pdf

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

CONFIGURATION 

Pressing the upper key permit to access the configuration.  
 
For each rubric, a message is streaming on the display and the <YES> key permits to access the rubric and the <NO> 
key to skip it. For a choice selection, the <YES> key validate the choice and the <NO> key invalidate it or pass to the 
next choice. 
 
During an adjustment procedure, the upper key increment the value and the lower key decrement the value and the re-
lay 1 LED is flashing. All the parameters are limited excepted the nominal current (LOW or HIGH is displayed on over-
flow). The adjustment procedure is terminated automatically after 4 seconds if no key is pressed. 
 
The message "

OK !

" is displayed at the end of the configuration after all the parameters have been memorized. 

If the configuration is stopped before the message "

OK !

" appears, the newly configured parameters are not saved. 

Connector for relays 1 & 2,  
outputs and power supply. 
 
 
Power present LED. 
 
 4 digits display (current value) 
 
Relay 1 alarm LED (thermal protection).  
Relay 2 alarm LED (thermal protection).  
 
Relay 3 alarm LED (nominal current).   
 

 

 

        

Relay 4 alarm LED (watchdog). 
 
Cover 
 
Connector for voltage input & 
relays 3, 4. 

Configuration access 

or 

YES key 

or 

increment key (+) 

NO key 

or 

decrement key (-) 

RPS23 

Stereo Jack for the RS232 
link 

Summary of Contents for RPS23

Page 1: ...LOREME 12 rue des Potiers d Etain Actipole BORNY B P 35014 57071 METZ CEDEX 3 Phone 03 87 76 32 51 Telefax 03 87 76 32 52 Contact Commercial Loreme fr Technique Loreme fr Download manual at www loreme...

Page 2: ...E PRESENTATION p3 CONFIGURATION p3 1 Thermal protection configuration p4 2 Relays configuration p5 3 Analog outputs configuration p6 RS232 LINK SETTING p7 FIRMWARE UPDATE p8 EMC CONSIDERATION p9 1 Int...

Page 3: ...3 3 relays idem R2 nominal current overflow alarm RPS23 R4 4 relays idem R3 watchdog RPS23 S1 1 insulated analog output RPS23 S2 2 insulated analog outputs independently configurable The technical dat...

Page 4: ...ment it is necessary to filter the input signal This parameter is the coefficient of the digital filter included in the device By increasing the value the response time of the filter is increased and...

Page 5: ...and 2 and in of the nominal current for relay 3 The security parameter allows to choose between the activation or the de activation of the relay when alarm is activated in positive security relay is s...

Page 6: ...ime The security value allows to set the output to a known state when there is a sensor breaking or a measure range over flow This value will be transferred to output The limitation allows to bound th...

Page 7: ...another communication port number COMx and re quires the reconfiguration of the hyperterminal The terminal emulation software for PC HyperTerminal is resident in windows up to XP version For later ve...

Page 8: ...mode and is waiting for the firmware file This file is provide by LOREME and contain the firmware code in Intel HEX format Select the Transfer Send a text file in the HyperTerminal menu Select the dir...

Page 9: ...ty centimeters of a device with a transmitter walkie talkie of a power of 5 W be cause the latter can create a field with an intensity higher than 10 V M for a distance fewer than 50 cm 2 2 Power supp...

Page 10: ...rminal A terminal E external shunt Analog output 1 terminal K terminal L Terminals K shunt must be closed for voltage output Analog output 2 terminal P terminal N Terminals P shunt must be closed for...

Page 11: ...N CONFIG BP UP Up button Yes Down button No Yes Yes No No NOMINAL CURRENT XXXX value adjustment with UP DOWN buttons Yes No MEASURE FILTER XXXX value adjustment with UP DOWN buttons Yes No K COEFFICIE...

Page 12: ...03 87 76 32 52 Email Commercial Loreme fr Techni Next Page Up button Yes Down button No a COEFFICIENT XXXX value adjustment with UP DOWN buttons Yes No b COEFFICIENT XXXX value adjustment with UP DOWN...

Page 13: ...URITY NEGATIVE SECURITY ACTIVATION DELAY Value Setting Yes No DEACTIVATION DELAY Value Setting Yes No Yes OK Yes Yes Yes OUTPUT CONFIGURATION CURRENT VOLTAGE Low and high scale adjustment block OUTPUT...

Reviews: