background image

 

SOMMAIRE

 

E 4  

LOREME

 12, rue des Potiers d'Etain - 57071 Metz  

 03.87.76.32.51 - Fax 03.87.76.32.52 - Email: [email protected] - [email protected]

 

 
Configuration via the front face 

1) Thermal protection configuration

 

In this rubric, the user can set the different thermal protection parameters. 
 

1.1) Nominal Voltage (mV) 

The nominal voltage is the voltage trip point for the relay. It is used in the calculation of the trip time, and can be config-
ured from 0 mV to 200 mV. Usually this value should be set to the value of the measurement shunt caliber. For example 
50mV for a 50 mV / 500 A shunt. The scale of the input is equal to 10 times the nominal voltage. For example, for a 
nominal voltage = 50 mV, the input range will be 0/500 mV so the RPS23 will switch its input high caliber 0/2000 mV. 
 

1.2) Nominal current (A) 

This parameter is normally set to the current rating value of the measuring shunt. E.g. 500 A for a 50 mV / 500 A shunt. 
It may also be configured to the value of 

Unominal / Rshunt 

if the configured nominal voltage is not the nominal shunt 

voltage. It serves as a: 

 

switching threshold for relay 3 (over current detection). 

 

display scale for displaying the current measurement. 

 

measurement scale for the calculation of the analog output. 

 

1.3) Measure filter 

In some noisy environment, it is necessary to filter the input signal. This parameter is the coefficient of the digital filter 
included in the device. By increasing the value, the response time of the filter is increased and thus the response time of 
the device. If the value is zero, there is no filtering. The parameter can be configured from 0 to 50 in 0.1 steps. 
 

1.4) Thermal equations coefficients 

The coefficients K, R, a, b, c used in the calculation of the thermal image are entirely configurable to adapt the relay 
to quiet any protection curve. The relay uses the equation 1 for heating and the equation 2 for cooling: 
 
 

1) 

t = K x ( a / ((U / Unom)^b - 1) + c)

,   for 

(U/ Unom)^b > 1

.

 

 
 

2) 

t = K x R / ((U / Unom)^b - 1)

,   for 

(U/ Unom)^b < 1

 
1.4.1) K coefficient 

The K coefficient can be configured from 0 to 50 in 0.1 steps. 
 

1.4.2) R coefficient 

The R coefficient is used in the cooling equation. It can be configured from 0 to 100 in 0.01 steps. 
 

1.4.3) a coefficient 

The a coefficient can be configured from 0 to 100 in 0.001 steps. 
 

1.4.4) b coefficient 

The b coefficient is the power factor of thermal equations. It can be configured from 0 to 3 in 0.001 steps. 
 

1.4.5) c coefficient 

The c coefficient can be configured from 0 to 10 in 0.001 step. 
 
See table next page for some examples of coefficient values for different thermal protection. 
 

Remark: 

 

RPS23 Timing accuracy:   
Within ±5% or ±300ms whichever is greater. This is true when the “measure filter” is set to 0. 
Increasing the “measure filter” parameter will increase the tripping time of the relay. 

Summary of Contents for RPS23

Page 1: ...LOREME 12 rue des Potiers d Etain Actipole BORNY B P 35014 57071 METZ CEDEX 3 Phone 03 87 76 32 51 Telefax 03 87 76 32 52 Contact Commercial Loreme fr Technique Loreme fr Download manual at www loreme...

Page 2: ...E PRESENTATION p3 CONFIGURATION p3 1 Thermal protection configuration p4 2 Relays configuration p5 3 Analog outputs configuration p6 RS232 LINK SETTING p7 FIRMWARE UPDATE p8 EMC CONSIDERATION p9 1 Int...

Page 3: ...3 3 relays idem R2 nominal current overflow alarm RPS23 R4 4 relays idem R3 watchdog RPS23 S1 1 insulated analog output RPS23 S2 2 insulated analog outputs independently configurable The technical dat...

Page 4: ...ment it is necessary to filter the input signal This parameter is the coefficient of the digital filter included in the device By increasing the value the response time of the filter is increased and...

Page 5: ...and 2 and in of the nominal current for relay 3 The security parameter allows to choose between the activation or the de activation of the relay when alarm is activated in positive security relay is s...

Page 6: ...ime The security value allows to set the output to a known state when there is a sensor breaking or a measure range over flow This value will be transferred to output The limitation allows to bound th...

Page 7: ...another communication port number COMx and re quires the reconfiguration of the hyperterminal The terminal emulation software for PC HyperTerminal is resident in windows up to XP version For later ve...

Page 8: ...mode and is waiting for the firmware file This file is provide by LOREME and contain the firmware code in Intel HEX format Select the Transfer Send a text file in the HyperTerminal menu Select the dir...

Page 9: ...ty centimeters of a device with a transmitter walkie talkie of a power of 5 W be cause the latter can create a field with an intensity higher than 10 V M for a distance fewer than 50 cm 2 2 Power supp...

Page 10: ...rminal A terminal E external shunt Analog output 1 terminal K terminal L Terminals K shunt must be closed for voltage output Analog output 2 terminal P terminal N Terminals P shunt must be closed for...

Page 11: ...N CONFIG BP UP Up button Yes Down button No Yes Yes No No NOMINAL CURRENT XXXX value adjustment with UP DOWN buttons Yes No MEASURE FILTER XXXX value adjustment with UP DOWN buttons Yes No K COEFFICIE...

Page 12: ...03 87 76 32 52 Email Commercial Loreme fr Techni Next Page Up button Yes Down button No a COEFFICIENT XXXX value adjustment with UP DOWN buttons Yes No b COEFFICIENT XXXX value adjustment with UP DOWN...

Page 13: ...URITY NEGATIVE SECURITY ACTIVATION DELAY Value Setting Yes No DEACTIVATION DELAY Value Setting Yes No Yes OK Yes Yes Yes OUTPUT CONFIGURATION CURRENT VOLTAGE Low and high scale adjustment block OUTPUT...

Reviews: