4 Installation, commissioning and replacement

 

 
Operating capacity and current error reporting should be checked 
during commissioning (validation) see section: "

commissioning and periodic proof

and at appropriate intervals recommended in paragraph: " 

proof interval

 " 

Any device that does not satisfy the commissioning control must be replaced. 
 

WARNING!

 

No user maintenance should be conducted, a defective device must be replaced by a new device of the same type. 
For a repair return or a recalibration, it is very important that all types of equipment failures are reported to allow  
the company to take corrective action to prevent systematic errors. 

 

4.1 Front panel description 

 

 
Convention: 
 

- The green LED indicate correct operation. 

 

- The red LED indicate a warning or a defect. 

4-20mA signal isolator, signal splitter with 2,3,4 outputs 
SIL2 / SIL3   

 

 

 

 CAL4/100ig     CAL4/100igM 

Green LED "Power" indicates that the device is cor-
rectly power on. 
Blink if power is on protected mode. 
(under voltage supply, overload or thermal protection 
mode) 

Green LED pass through by the output current 4  
indicates that the output loop current is closed.  
(current flow) 
light off when opening the output loop 
and when using test terminals located under the front  
panel  

Green LED pass through by the output current 3  
indicates that the output loop current is closed.  
(current flow) 
light off when opening the output loop 
and when using test terminals located under the front  
panel  

Green LED pass through by the output current 2  
indicates that the output loop current is closed.  
(current flow) 
light off when opening the output loop 
and when using test terminals located under the front  
panel  

Green LED pass through by the output current 1  
indicates that the output loop current is closed.  
(current flow) 
light off when opening the output loop 
and when using test terminals located under the front  
panel  

Summary of Contents for CAL4/100ig

Page 1: ...fety manual LOREME 12 rue des Potiers d Etain Actipole BORNY B P 35014 57071 METZ Phone 03 87 76 32 51 Fax 03 87 76 32 52 Contact Commercial Loreme fr Technique Loreme fr Download manual on www loreme...

Page 2: ...tate E4 2 1 Safety function E4 2 2 Safety fallback position E4 3 Safety Recommendation E4 3 1 Interfaces E4 3 2 Configuration Calibration E4 3 3 Useful lifetime E4 4 Installation commissioning and rep...

Page 3: ...urity features and damage to property environment or people 1 2 Functions and intended uses The transducer CAL4 100ig provides isolation and duplication of analog current loop 4 20mA an auxiliary powe...

Page 4: ...ssumed by the probabilistic estimation that it applies only to the useful lifetime of components Beyond this lifetime the probability of failure is increasing significantly with time The useful lifeti...

Page 5: ...uts SIL2 SIL3 CAL4 100ig CAL4 100igM Green LED Power indicates that the device is cor rectly power on Blink if power is on protected mode under voltage supply overload or thermal protection mode Green...

Page 6: ...ode the output load resistance must be between 0 ohms and 600 ohms Input wiring In 4 20mA passive current input between terminal in and GND for active transmitter In 4 20mA loop with transmitter suppl...

Page 7: ...efined under paragraph proof interval 5 1 control steps Periodic proof allows detection of possible product internal failure and loop calibration environmental conditions and a minimum heating time of...

Page 8: ...ls 4 20mA image of input Generally a transducer is taking place between a sensor and a protective equipment designated as Logic Safety Equipment Sensor transmitter CAL4 100ig PLC Logic Safety Equipmen...

Page 9: ...reby in the FMEA analysis this state is considered as a not dangerous state Study hypotheses The failure rate of component are considered as constant for the all system life time The evaluation of the...

Page 10: ...ion up to SIL3 according to standard IEC61508 2 2000 respecting the safety instructions specified in the safety manual The assessment of the safety critical and dangerous random failure give the follo...

Page 11: ...of a device with a walkie talkie 5 W output power because it creates a electromagnetic field with an intensity greater than 10 V M for a distance of less than 50 cm 2 2 Power supply Observe the charac...

Page 12: ...failure occurs if the measuring system doesn t switch into a define safe state or into an alarm signaling mode on process demand Appendix term and definitions SIL stands for Security Integrity Level w...

Reviews: