Zero Clearance Box
Flush Wood Medium & Flush Wood Large Hybrid-Fyre™
Zero Clearance Box Assembly Details
Step 7
Screw 250mm collar in place
NOTE 1:
There is a different starter section provided for
the Medium Flush Wood and Large Hybrid-Fyre™
models. Please use the correct starter for the
model being installed.
The Flush Wood Large Hybrid-Fyre™ Starter
must be secured to the top of the firebox and
sealed around using a fireplace cement as per
installation manual.
NOTE 2:
Use plastic insulating cover where the fan power cable passes through
the inner and outer panels
NOTE 3:
A t
riple skin flue must be installed from zero clearance box as per Australian Standards.
A 25mm clearance from the outer 10” casing to any combustible material must be
maintained.
Please see heater owners manual for other clearances and more information.
* Images for illustration purposes only, some details may change
4
The Flush Wood Medium Starter needs to be
secured to the flue collar, however, it is not
required to be sealed.
It has been designed with a check out for the
bypassrod at the front and to rest on the tab
inside the flue spiggot on the left.
Medium Starter
Large Hybrid-Fyre Starter