22
2. Configuring Inverters
C. Setting the Baud Rate
1. Back in the password-protected menu, scroll to “IFP” and press Enter.
2. Scroll to “19200” and press Enter.
3. Go to AC Sync mode by selecting “ESC” twice and pressing Menu twice.
D. Resetting the Inverter & Datalogger
1. Reset by the Fronius inverter by turning the DC disconnect off then the AC
disconnect off; then turn the AC disconnect on, followed by turning the DC
disconnect on.
2. Reboot the LGate using the reset button or by turning the LGate breaker off and on.
E. Verify that all settings in the above steps saved correctly.
3. Terminating the Daisy Chain
For the last or only inverter in the chain, install a Fronius-supplied termination plug in the
open Ethernet port.
For all other inverters, do not install any termination plugs.
Termination Plug in Last/Only Inverter
Termination
plug