background image

18

       

Installation & Operation Manual

Startup and maintenance

1.  Make sure the system is free of leaks and that air is 
 

purged from the system.

 

CAUTION

Fix any leaks found before proceeding 
further. Leakage from the heat source and 
solar piping can result in severe damage to 
the system.

2. Many soldering fluxes contain Zinc Chloride which 
 

can cause severe corrosion damage to stainless steel.  After 

  completing all domestic water connections, flush the 
 

Thermal-Stor tank thoroughly before leaving the installation. 

 

This is particularly important if the Thermal-Stor will be 

 

unused for an extended period of time after installation. 

 

Flush the storage tank by drawing at least three times its 

 

volume from the tank.

3.  Make sure that each zone valve or circulator operates 
 

when, and only when, its thermostat calls for heat.  Let each 

 

zone operate long enough to purge any remaining air from 

 the 

system.

 

Refer to the heat source and solar Installation and Operation 

 

Manuals for additional start-up information.

System startup

• 

Ensure that the boiler and solar water piping are free of 

 leaks.

• 

If there is an oil lubricated circulator in the system, make 

 

sure it is lubricated as called for by the circulator 

 manufacturer.

• 

Make sure that the heat source is maintained in accordance 

 

with the manufacturer’s instructions.

•  If antifreeze is required to keep the water chemistry 
 

within the parameters shown in Table 2A (see Section 

 

2 - Pre-Installation), make sure that this system is properly 

 maintained.

Annual service by a qualified service technician 
should include the following:

  Any procedure required by local codes.

  Verify system pressure. Air venting procedure may require 

 

adding water to bring boiler system up to pressure, typically 

 

12 psig minimum.

  Manually operate relief valve at least once a year. This will 

 

release some hot water. 

 WARNING

Before operating a relief valve, make sure no 
one is in front of or around the relief valve 
discharge piping. Hot discharge water can 
cause severe personal injury or substantial 
property damage.

 DANGER

Plugging the  relief valve or discharge piping 
can cause excessive pressure in the water 
heater, resulting in severe personal injury, 
death, or substantial property damage.

 

Move operating lever to open position for a few seconds 

 

and then move it back, allowing it to snap closed. After the 

 

relief valve is operated, if it continues to release water, close 

 

the cold water inlet to the water heater immediately. Follow 

 

the draining instructions, and replace the relief valve. If 

 

the relief valve weeps periodically, it may be due to thermal 

 

expansion. Do not plug the relief valve or discharge piping. 

 

In this case, ensure that the expansion tank is properly sized 

 

and charged to the appropriate pressure.

Maintenance Schedule

The Lochinvar Thermal-Stor solar tank is an extremely simple 
device and as such requires very little maintenance.  There are, 
however, several items which should be inspected on an annual 
or as needed basis to ensure a reliable supply of hot water:

  Verify that expansion tank pressure is equal to system 

 pressure.

Summary of Contents for TSU150

Page 1: ...ller service technician Read all instructions before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial property damage WARNING S...

Page 2: ...ty damage NOTICE indicates special instructions on installation operation or maintenance that are important but not related to personal injury or property damage HAZARD DEFINITIONS 2 PLEASE READ BEFOR...

Page 3: ...plate Consider piping and installation when determining appliance location Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee...

Page 4: ...nger equipment life for the solar thermal system and heat source If piped correctly the buffer tank can also function as a hydraulic separator effectively separating the flow in the boiler loop from t...

Page 5: ...TSU257 30 34 2 2 240 2875 TSU350 36 40 2 2 340 3775 TSU423 36 40 2 2 420 4650 TSU504 42 46 2 2 495 5475 TSU650 48 52 2 2 645 7050 TSU752 48 52 2 2 745 8100 TSU940 48 52 2 2 920 10000 AUXILIARY HEAT OU...

Page 6: ...g Measurements From Floor Model A in B in C in D in E in F in G in H in I in O in P in TSU150 2 1 4 10 3 4 21 1 4 28 3 4 33 50 1 4 55 1 4 71 75 3 4 3 1 2 3 1 2 TSU200 2 1 4 11 1 4 22 3 4 33 38 1 2 55...

Page 7: ...exchanger w tank Table 1E Tank with Spherical Measurements Model Spherical Model A in B in TSU150 SHX40000 44 1 2 28 TSU200 SHX40000 48 1 4 32 TSU257 SHX40001 50 1 4 34 TSU350 SHX40001 56 1 4 40 TSU4...

Page 8: ...sen for the tank is capable of supporting the weight This tank must be placed where leakage from the relief valve leakage from the related piping or leakage from the tank or connections will not resul...

Page 9: ...tor Take appropriate safety measures when carrying out any installation work on the roof and observe all relevant accident prevention regulations It is the installer s responsibility to comply with th...

Page 10: ...AR PUMP STATION CONTROLLER TEMPERATURE GAUGE TYPICAL SPHERICAL HEAT EXCHANGER SOLAR SENSOR FILL AND FLUSH VALVE PRESSURE RELIEF VALVE IMG00095 TEMPERATURE GAUGE EXPANSION TANK Figure 3 2 Solar System...

Page 11: ...the Thermal Stor buffer tank can be used to heat domestic water The hottest water is taken from the auxiliary heat supply and piped to the indirect heater where it is used to heat domestic potable wat...

Page 12: ...in Section VIII Division 1 paragraph UG 125 a All pressure vessels within the scope of this division irrespective of size or pressure shall be provided with pressure relief devices in accordance with...

Page 13: ...e tank so that water at a more constant temperature exits the mixing valve Always consult the mixing valve manufacturer s instructions and guidelines for correct piping and usage WARNING An anti scald...

Page 14: ...y local codes NOTICE BACKFLOW PREVENTER PRESSURE REDUCING VALVE PRESSURE GAUGE AIR SEPARATOR LOW TEMP ZONE ZONE 1 ZONE 2 HIGH LOW RETURN TEMPERATURE GAUGE EXPANSION TANK PRESSURE RELIEF VALVE IMG00123...

Page 15: ...RE GAUGE EXPANSION TANK MIXING VALVE PRESSURE RELIEF VALVE IMG00125 ZONE CIRCULATORS TYPICAL UNION Y STRAINER TYPICAL BOILER CIRCULATOR T P GAUGE DRAIN PRESSURE RELIEF VALVE CHECK VALVE SHOCK ARRESTOR...

Page 16: ...IN PRESSURE RELIEF VALVE SHOCK ARRESTOR CHECK VALVE DOMESTIC HOT WATER DOMESTIC COLD WATER MAKE UP WATER SPACE HEAT SUPPLY AUXILIARY HEAT SUPPLY Y STRAINER TYPICAL BRAISED PLATE HEAT EXCHANGER Please...

Page 17: ...meant to show system piping concept only the installer is responsible for all equipment and detailing required by local codes NOTICE Figure 4 5 DHW Priority Piping Multiple Temperature Space Heating...

Page 18: ...ion make sure that this system is properly maintained Annual service by a qualified service technician should include the following Any procedure required by local codes Verify system pressure Air ven...

Page 19: ...section If antifreeze is used in the heat source water check the concentration Heat source water including additives must be non toxic having a toxicity rating or class of 1 as listed in the Clinical...

Page 20: ...Revision Notes Revision A ECO C08886 initial release TSU I O Rev A 11 11 Printed in U S A...

Reviews: