background image

3

TNR-I&S-02

AIR REQUIREMENTS

1. Do not obstruct the flow of combustion and ventilating air.

2. For safe operation, adequate air is needed for combustion and

ventilation. Sooting may result in serious damage to the water heater
and risk of fire or explosion. It can also create a risk of asphyxiation.
Such a condition often will result in a yellow, luminous burner flame,
causing carboning or sooting of the combustion chamber, burner and
flue tubes.

MECHANICAL EXHAUSTING OF ROOM AIR

1. Where an exhaust fan is installed in the same room with this water

heater and combustion air is drawn from inside the room, sufficient
openings for air must be provided in the walls.UNDERSIZED
OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM THROUGH
THE WATER HEATER’S VENTING SYSTEM, CAUSING POOR COMBUSTION
THAT MAY BE HAZARDOUS TO LIFE. SOOTING MAY RESULT IN SERIOUS
DAMAGE TO THE WATER HEATER AND RISK OF FIRE OR EXPLOSION
WHICH CAN ALSO CREATE A RISK OF ASPHYXIATION. Refer to local
codes and /or National Fuel Gas Code for proper air opening sizing.

UNCONFINED SPACE

1. In buildings of conventional frame, brick or stone construction,

unconfined spaces may provide adequate air for combustion and
ventilation.

2. If the unconfined space is within a building of tight construction

(buildings using the following construction: weather stripping, heavy
insulation, caulking, vapor barrier, etc.), air for combustion and
ventilation must be obtained from outdoors. This may be
accomplished by piping air directly to the water heater from outside
or providing opening or ducts in the wall.  The installation instructions
for confined spaces in tightly constructed buildings must be followed
to ensure adequate air supply.

CONFINED SPACE

1. When drawing combustion air from inside a conventionally

constructed building to a confined space, such a space shall be
provided with two permanent openings.

The top opening is to be located within twelve (12) inches of the
enclosure top and the bottom opening within twelve (12) inches
of the enclosure bottom.

Each opening shall have a free area of at least one square inch
per 1000 Btu/hr of the total input of all appliances in the enclosure,
but not less than 100 square inches.

2. If the confined space is within a building of tight construction, air for

combustion and ventilation must be obtained from outdoors. This
may be accomplished by piping air directly to the water heater from
outside or providing opening or ducts in the wall.  When directly
communicating with the outdoors through vertical ducts, two
permanent openings, located in the above manner, shall be provided.

Each opening shall have a free area of not less than one square
inch per 4000 Btu/hr of the total input of all appliances in the
enclosure.

If horizontal ducts are used, each opening shall have a free area
of not less than one square inch per 2000 Btu/hr of the total input
of all appliances in the enclosure.

3. If the water heater is installed as a direct vent (outside air piped

directly to the water heater), then additional opening, other than
the opening for the air intake, are not required.  However, adequate
ventilation air must be provided in all cases to prevent increased
room temperature.

CHEMICAL VAPOR CORROSION

Corrosion of the flue ways and vent system will occur if air for combustion
contains certain chemical vapors. Such corrosion may result in poor
combustion and create a risk of asphyxiation. Spray can propellants,
cleaning solvents, refrigerator and air conditioning refrigerants, swimming
pool chemicals, calcium and sodium chloride, waxes and process chemicals
are corrosive. Products of this sort should not be stored near the water
heater or outside by the air intake (if applicable).

TYPICAL INSTALLATION ILLUSTRATION

 CAUTION

If building cold water supply has a back-flow preventer, check valve
or water meter with check valve provisions for thermal expansion of
water in the hot water system must be provided.

 

Figure 2

Typical Front Inlet Connection

Summary of Contents for TNR-I&S-02

Page 1: ...perature and pressure relief valve complies with local codes If the combination temperature and pressure relief valve does not comply with local codes replace it with one that does Install a discharge...

Page 2: ...ions will be short and direct 2 THIS WATER HEATER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR DO NOT install this water heater on carpeting 3 FOR BASEMENT INSTALLATION provide a solid level elev...

Page 3: ...pening is to be located within twelve 12 inches of the enclosure top and the bottom opening within twelve 12 inches of the enclosure bottom Each opening shall have a free area of at least one square i...

Page 4: ...the time it is open Keep clear of the combination temperature and pressure relief valve discharge line outlet The discharge may be hot enough to cause scald injury The water is under pressure and may...

Page 5: ...injuy and may be used as a guide in determining the safest water temperature for your applications ALTERNATE SPACE HEATING WATER CONNECTIONS Connect the system supply and return piping to the water he...

Page 6: ...on instructions Water heater must be protected from freezing downdrafts during shutdown periods Provide protection of the building materials from degradation by flue gases from the exhaust vent termin...

Page 7: ...IONS FOR INSTALLATIONS The vent terminal must not terminate 1 Directly above a paved sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings 2 Less th...

Page 8: ...de wall if vented on the same wall 2 Use the proper PVC cement to secure the 90 exhaust vent and air intake terminals provided with the water heater to the plastic pipes The distance between the back...

Page 9: ...0 elbow referred to as the exhaust vent terminal and the air intake terminal Power Vent Terminal Location Refer to the Direct Vent Terminal Location see page 7 section previously mentioned to determin...

Page 10: ...tical run and every 3 feet of horizontal run of vent pipe length Stress levels in the pipe and fittings can be significantly increased by improper installation If rigid pipe clamps are used to hold th...

Page 11: ...other appliance Using this kit on other appliances and or water heaters can result in property damage personal injury or death DO NOT operate this water heater until the installation and assembly of t...

Page 12: ...pipe See Figure 19 5 Install concentric Y fitting and pipe assembly through the structure s hole and field supplied roof boot flashing Do not allow insulation or other materials to accumulate inside p...

Page 13: ...7 Take the time and effort to do a professional job Shortcuts will only cause you problems and delays in start up The majority of failures in these systems are the result of shortcuts and or improper...

Page 14: ...any damage or injury caused as a result of a cracked gas inlet as a result of excessive torque This water heater and its gas connection must be leak tested before placing the water heater in operatio...

Page 15: ...at satisfied 4 Blower pre purge 9 Main burner OFF 5 Igniter warm up 10 Blower post purge WARNING Water heaters are heat producing appliances To avoid damage or injury there must be no materials stored...

Page 16: ...1 6 TNR I S 02 LIGHTING INSTRUCTIONS Figure 24 Lighting Instruction Label...

Page 17: ...mperature during standby periods Lower water temperatures also extend tank life Remember no water heating system will provide exact temperatures at all times Allow a few days of operation at this sett...

Page 18: ...em Condensate Line OPERATION Sediment Removal Inspect Check Operation Clean Inlet Screen Inspect Inspect Free of Shrubs Debris Inspect Inspect INTERVAL Monthly Semi Annually Semi Annually As Required...

Page 19: ...sion Replace with a new valve of the recommended size as necessary A thorough inspection of the valve should be performed at least every three years by removing the temperature and relief valve from t...

Page 20: ...illed with condensate then replace pressure switch If filled empty hose Is the Collector Limit Switch N C If no then reset switch If this switch trips more than 3 times call service If all items above...

Reviews: