background image

1 8

TNR-I&S-02

FLUSHING WATER HEATER

1.

Turn OFF the water heater electrical disconnect switch.

2.

Open the drain valve and allow water to flow until it runs clean.

3.

Close the drain valve when finished flushing.

4.

Turn ON the water heater electrical disconnect switch.

DRAINING WATER HEATER

The water heater must be drained if it is to be shut down and exposed to
freezing temperatures. Maintenance and service procedures may also
require draining the water heater.
1.

Turn off the water heater electrical disconnect switch.

2.

Connect a hose to the drain valve.

3.

Locate hose’s discharge in an area where hot water will not cause
any damage or injury.

4.

Close the cold water inlet valve to water heater.

5.

Open a nearby hot water faucet to vent the system.

6.

Open the heater drain valve.

7.

If the water heater is being drained for an extended shutdown, it
is suggested the drain valve be left open during this period.

FILLING WATER HEATER

1.

Close the water heater drain valve by turning the knob or valve
stem clockwise.  If alternative water connections are provided but
not used, make certain they are plugged (i.e. rear connections).

2.

Open the cold water supply shut-off valve.

3.

Open several hot water faucets to allow air to escape from the
system.

4.

When a steady stream of water flows from the faucets, the water
heater is filled.  Close the faucets and check for water leaks at the
water heater drain valve, combination temperature and pressure
relief valve and the hot and cold water connections.

SEDIMENT  AND LIME SCALE REMOVAL

Waterborne impurities consist of the particles of soil and sand which settle
out and form a layer of sediment on the bottom of the tank.

The amount of calcium carbonate (lime) released from water is in direct
proportion to water temperature and usage. The higher the water
temperature or water usage, the more lime deposits are dropped out of

COMPONENT

Tank
Anode Rods
Relief Valve
Blower
Vent & Air Intake System
Ignition System
Vent Terminal
Combustion System
Condensate Line

OPERATION

Sediment Removal
Inspect
Check Operation
Clean Inlet Screen
Inspect
Inspect
Free of Shrubs & Debris
Inspect
Inspect

INTERVAL

Monthly
Semi-Annually
Semi-Annually
As Required
Every 3  Months
Annually
Monthly
Monthly
Monthly

REQUIRED

Flushing
Replace as Required
Proper Operation
Soft Brush
Joints should be sealed
Clean of dust and dirt
Remove object that caused restriction
Confirm S-OP
Remove restriction

Table 4

Suggested Maintenance Schedule

the water. This is the lime scale which forms in pipes, water heaters and on
cooking utensils.

Lime accumulation not only reduces the life of the equipment but also
reduces efficiency of the water heater and increases fuel consumption.

The usage of water softening equipment greatly reduces the hardness of
the water.  However, this equipment does not always remove all of the
hardness (lime).  For this reason it is recommended that a regular schedule
of deliming be maintained.

The depth of the buildup should be measured periodically.  Water heaters
will have about 3 inches of lime buildup when the level of lime has reached
the bottom of the cleanout opening or about 1 inch of lime buildup if it has
reached the drain valve opening.  A schedule for deliming should be set
up, based on the amount of time it would take for a ½ inch buildup of lime.

Example1:

Initial inspection shows ½ an inch of lime accumulation. Therefore, the
water heater can be delimed once a year.

To remove sediment and lime scale:

1. Drain the heater.  Refer to DRAINING THE WATER instructions in this

section.

2. Remove outer cover plate from lower side of water heater jacket.
3. Remove cover and gasket from cleanout opening.
4. Remove lime, scale or sediment using care not to damage the

glass-lining.

5. Inspect cleanout plate gasket:  Replace gasket if necessary (Contact

local distributor for correct part number).

6. Install gasket and cleanout plate.  Be sure to draw plate up tight by

tightening screws securely.

7. Close the drain valve.  Open a hot water fixture to allow air to

escape.  Open the cold water supply to water heater and allow the
tank to fill.  Follow the lighting instructions.

8. Check for water leakage.
9. Install outer jacket cover plate.

Summary of Contents for TNR-I&S-02

Page 1: ...perature and pressure relief valve complies with local codes If the combination temperature and pressure relief valve does not comply with local codes replace it with one that does Install a discharge...

Page 2: ...ions will be short and direct 2 THIS WATER HEATER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR DO NOT install this water heater on carpeting 3 FOR BASEMENT INSTALLATION provide a solid level elev...

Page 3: ...pening is to be located within twelve 12 inches of the enclosure top and the bottom opening within twelve 12 inches of the enclosure bottom Each opening shall have a free area of at least one square i...

Page 4: ...the time it is open Keep clear of the combination temperature and pressure relief valve discharge line outlet The discharge may be hot enough to cause scald injury The water is under pressure and may...

Page 5: ...injuy and may be used as a guide in determining the safest water temperature for your applications ALTERNATE SPACE HEATING WATER CONNECTIONS Connect the system supply and return piping to the water he...

Page 6: ...on instructions Water heater must be protected from freezing downdrafts during shutdown periods Provide protection of the building materials from degradation by flue gases from the exhaust vent termin...

Page 7: ...IONS FOR INSTALLATIONS The vent terminal must not terminate 1 Directly above a paved sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings 2 Less th...

Page 8: ...de wall if vented on the same wall 2 Use the proper PVC cement to secure the 90 exhaust vent and air intake terminals provided with the water heater to the plastic pipes The distance between the back...

Page 9: ...0 elbow referred to as the exhaust vent terminal and the air intake terminal Power Vent Terminal Location Refer to the Direct Vent Terminal Location see page 7 section previously mentioned to determin...

Page 10: ...tical run and every 3 feet of horizontal run of vent pipe length Stress levels in the pipe and fittings can be significantly increased by improper installation If rigid pipe clamps are used to hold th...

Page 11: ...other appliance Using this kit on other appliances and or water heaters can result in property damage personal injury or death DO NOT operate this water heater until the installation and assembly of t...

Page 12: ...pipe See Figure 19 5 Install concentric Y fitting and pipe assembly through the structure s hole and field supplied roof boot flashing Do not allow insulation or other materials to accumulate inside p...

Page 13: ...7 Take the time and effort to do a professional job Shortcuts will only cause you problems and delays in start up The majority of failures in these systems are the result of shortcuts and or improper...

Page 14: ...any damage or injury caused as a result of a cracked gas inlet as a result of excessive torque This water heater and its gas connection must be leak tested before placing the water heater in operatio...

Page 15: ...at satisfied 4 Blower pre purge 9 Main burner OFF 5 Igniter warm up 10 Blower post purge WARNING Water heaters are heat producing appliances To avoid damage or injury there must be no materials stored...

Page 16: ...1 6 TNR I S 02 LIGHTING INSTRUCTIONS Figure 24 Lighting Instruction Label...

Page 17: ...mperature during standby periods Lower water temperatures also extend tank life Remember no water heating system will provide exact temperatures at all times Allow a few days of operation at this sett...

Page 18: ...em Condensate Line OPERATION Sediment Removal Inspect Check Operation Clean Inlet Screen Inspect Inspect Free of Shrubs Debris Inspect Inspect INTERVAL Monthly Semi Annually Semi Annually As Required...

Page 19: ...sion Replace with a new valve of the recommended size as necessary A thorough inspection of the valve should be performed at least every three years by removing the temperature and relief valve from t...

Page 20: ...illed with condensate then replace pressure switch If filled empty hose Is the Collector Limit Switch N C If no then reset switch If this switch trips more than 3 times call service If all items above...

Reviews: