background image

19

PC Program Instructions

6

Parameters 

(continued)

Figure 6-13

Save Parameter File Window

Storing parameters on your PC

Once you have customized the parameters for a particular
heater, you can store the new settings on your PC.  This will
allow you to restore these settings should you have to replace
the SMART TOUCH control, or allow you to load these
settings into another heater at a later date.

The settings are stored as a data file.  To save a file, click on

Parameters

at the top of the screen, then on 

Save data file to

disk

on the bottom of the pull-down menu (see FIG. 6-1 on

page 10).  A new window will appear (FIG. 6-13).  On the top
left side it shows the drive on which it will save the file.  Below
that is the directory it will use.  These may be changed to any
drive and folder you wish (for instance, a USB flash drive).  At
the right side is a list of the default data files.  At the bottom
is a field for entering the file name you wish to use.  Note that
the extension for this file is 

.pil

.  Make sure that you DO NOT

overwrite the extension when entering the file name.  

You

MUST NOT use any of the default file names shown in the
field on the right side of the window.  This could overwrite
that default file!

If you are updating a file, and want to

overwrite the old one, you may scroll down to that file name
and click on it, instead of having to type it into the field at the
bottom of the window.  Click on the 

OK

button to save the

file.  A message will appear confirming that the file was saved.
Note that the new file name appears in the lower right-hand
corner of the SMART TOUCH PC program window.

BMS Voltage at min power (BMS V @min mod)

If parameter 

4CB

is set to 0, the control must know what

voltage corresponds to the minimum power.  This can be
changed by accessing parameter 

4GI.

The range for this

parameter is 0Vdc to 4GJ  The default value is 2Vdc.

BMS Voltage at max power (BMS V @max mod)

If parameter 

4CB

is set to 0, the control must know what

voltage corresponds to the maximum power.  This can be
changed by accessing parameter 

4GJ.

The range for this

parameter is 4GI to 10Vdc.  The default value is 10Vdc.

BMS Demand Enable (1) Voltage (0)

If parameter 

4CG

is set to YES (BMS control of cascade), the

heat demand can be activated either by the voltage on the
0-10Vdc input, or by closing the enable contacts.  To choose
the voltage input, set parameter 

4GK

to  0.    To  choose  the

enable input, set parameter 

4GK

to 1.  The default value is 0.

Loading stored parameters from the PC

To retrieve a set of parameters that had been stored previously,
click on 

Parameters

at the top of the screen, then on 

Get data

file from disk

(see FIG. 6-1 on page 10).  A new window will

appear (FIG. 6-14).  On the left top corner, select the drive on
which the data file is stored, followed by the correct folder.  The
list of data files in that folder will be shown on the right.  Click
on the data file you wish to obtain.  That file name will appear in
the field at the bottom of the window.  Click on the 

OK 

button.

Note that this file name appears in the lower right-hand corner
of the SMART TOUCH PC window.

Figure 6-14

Get Parameter File Window

Summary of Contents for SMART TOUCH

Page 1: ...SYNC Installation and Operation Manual and the SYNC Service Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial pro...

Page 2: ...3 PC to Unit Connection 3 Starting the Program 4 6 2 Status Screen 5 6 3 Graphics Screen 7 4 Fault History Screen 8 5 Cascade Screen 9 6 PARAMETERS Parameter Information Screens 10 Changeable Paramet...

Page 3: ...r assigned to the USB cable above The programs display temperatures in F If you wish to display temperatures in C click on the Settings tab along the top of the Main Screen window and move the cursor...

Page 4: ...the upper left hand corner of the window A window opens in which you can type in the password see FIG 1 3 Note that the password is case sensitive and is in all CAPS Click on the Ok button or press th...

Page 5: ...o run at low fire Finally the 0 10Vdc input Voltage and Flame Current are shown To the right of the sensor temperature readings are the various setpoints The SH setpoint is the setpoint the SMART TOUC...

Page 6: ...active limits if any the last active limit the burner status the last fault and the date and time as stored in the SMART TOUCH PC Program Instructions While in the SMART TOUCH Status Screen you can g...

Page 7: ...he desired scale The top number represents F and the bottom number represents C Press the Ok button to close the Options window The background color of the Graphics Screen can be changed by pressing t...

Page 8: ...is shown as well as the number of successful and failed ignition attempts Finally a count of internal checks is shown The total number of occurrences of certain faults are also stored in the control a...

Page 9: ...t is a check box indicating if the temperature regulation is being held constant and if the Ramp Delay feature is active The Freeze P1 regulation box is checked when the next controller can be started...

Page 10: ...an adjustment to a parameter select the parameter to be changed from the appropriate set Click on the box next to the parameter and type in the value for the parameter Once an adjustment has been mad...

Page 11: ...stable The time range for each ramp delay is adjustable from 1 minute to 40 minutes with the total of all 6 ramp delays not to exceed 109 minutes The default delay time for Periods 1 2 and 3 is 2 minu...

Page 12: ...switching boiler on Parameter 2DJ is the minimum time delay between starting one burner and starting the next burner in the Cascade The range for this parameter is 0 seconds to 255 seconds The default...

Page 13: ...mperature setpoint for fixed operation or the maximum temperature setpoint when the outdoor air sensor is used This parameter can be changed by accessing parameter 4AA The temperature range of this pa...

Page 14: ...alue is 0 This feature will be active if this parameter is set to anything other than 0 Night setback temperature NSB Setp Once the internal clock has been set correctly the night setback feature can...

Page 15: ...has occurred or the maximum user setpoint has been reached Once the SH demand has been satisfied the setpoint will revert back to its calculated setting The boost temperature can be changed by accessi...

Page 16: ...ndow click on the tab labeled 4D Pump Delay to set the delay time for the boiler system and HW pumps see FIG 6 8 below Figure 6 8 Parameter Set 4D SH pump delay after SH demand Boiler Pump D This feat...

Page 17: ...re rises to or above this point the water temperature will be at its minimum setpoint This parameter can be changed by accessing parameter 4FD The temperature range of this parameter is 30 F 34 C to 9...

Page 18: ...eter 4GD The voltage range for this parameter is 0Vdc to 4GC The default value is 10Vdc Min BMS voltage to start demand BMS V Heat If parameter 4GK is set to 1 then the heat demand will be generated b...

Page 19: ...pear confirming that the file was saved Note that the new file name appears in the lower right hand corner of the SMART TOUCH PC program window BMS Voltage at min power BMS V min mod If parameter 4CB...

Page 20: ...Revision Notes Revision A initial release SYNC PCP Rev A Printed in the USA 4 10...

Reviews: