PC Program Instructions

6

Parameters

SH off-on differential (SH off/on df)

The SH Off-on Differential sets how many degrees below the
turn-off temperature the outlet temperature has to go before
the boiler will turn on. This parameter can be changed  by
accessing parameter 

4AE

. The temperature range of this

parameter is 0°F to 86°F.  The default value is 20°F.

Drop of inlet temp before ending anti-cycling (Drop
in inlet)

The control will bypass the anti-cycling time if the inlet water
temperature drops too much.  The control will use the inlet
water temperature when it shuts off as the starting point.  If
the temperature drops this amount below the starting
temperature, the control will abort anti-cycling and allow the
boiler to fire.  This parameter can be changed by accessing
parameter 

4AF

.  The temperature range of this parameter is

0°F to 86°F.  The default value is 10°F. 

Offset HW setpoint to end HW demand

When heating an indirect hot water tank (heat maker), the
tank temperature (or inlet temperature if a tank sensor is not
used) must rise above the tank setpoint (parameter 

4AS

) by

this amount before the HW heat demand will end.  This
parameter can be changed by accessing parameter 

4AG.

The

temperature range of this parameter is 0° to 54°F (30°C).  The
default setting is 0°.

Outdoor air shutdown temp (Out SD Setp)

When the outdoor air temperature rises above this point, the
control will inhibit all SH demands (HW demands will still be
active). This parameter can be changed by accessing
parameter 

4AH

. The temperature range of this parameter is

0°F to 120°F (99°C).  The default value is 80°F (27°C).

OA shutdown differential (Out SD df)

This is the number of degrees below parameter 

4AH

the

outdoor air temperature must go before the boiler will again
respond to an SH demand. This parameter can be changed by
accessing parameter 

4AI

. The temperature range of this

parameter is 0°F to 90°F (50°C).  The default value is 10°F
(5°C).

Shift OA reset curve (Shift Air Reset)

The Shift Heat Curve shifts the actual setpoint above or below
the calculated setpoint by the number of degrees in this
parameter. This parameter can be changed by accessing
parameter 

4AJ

. The temperature range of this parameter is

-27°F (-15°C) to 27°F (15°C). The default value is 0°. This
feature will be active if this parameter is set to anything other
than 0°.

Night setback temperature (NSB Setp)

Once the internal clock has been set correctly, the night
setback feature can be used to program a lower water
temperature setpoint for space heating. This parameter can be
changed by accessing parameter 

4AK

. The temperature range

for this parameter is 32°F (0°C) to 140°F (60°C). With a
setting of 32°F (0°C) the feature is turned off.  The default
value will be 32°F (0°C).

SH turn-off differential cascade (Casc off df)

The SH turn-off differential cascade sets how many degrees
above the SH setpoint the system temperature has to go before
the boiler will shut off.  This parameter can be changed by
accessing parameter 

4AL.

The temperature range of this

parameter is 0°F to 72°F (40°C).   The default setting is 10°F
(5°C).

SH off-on differential cascade (Casc off/on df)

The SH off-on differential cascade sets how many degrees
below the turn-off temperature the system temperature has to
go before the boiler will turn back on.  This parameter can be
changed by accessing parameter 

4AM.

The temperature

range of this parameter is 0°F to 72°F (40°C).  The default
setting is 20°F (10°C).

SH anti-cycling time (Anti-C t)

Once a SH demand has been satisfied, a set amount of time
must elapse before the control will respond to a new SH
demand. This helps prevent short cycling of the boiler.  The
control will inhibit the new heat demand and “Anti-cycling”
will be shown on the display, until either this time has elapsed
or the water temperature drops below parameter 

4AF

. This

parameter can be changed by accessing parameter 

4AO

.  The

time range for this parameter is 0 minutes to 40 minutes.  The
default value is 1 minute. 

Max service time (Max Serv t)

The service mode allows the installer to set the unit to a fixed
firing rate for the purpose of combustion analysis. The delay
sets the length of time the boiler will stay in the service mode
if no keys have been pressed before going back to its original
state. This parameter can be changed by accessing parameter

4AP

. The time range of this parameter is 0 minutes to 40

minutes. The default value is 20 minutes.

Tank setpoint temp

This setting is applied to the tank sensor (when connected).  It
is used to start and stop the HW call for heat.  This setting can
be changed by accessing parameter 

4AS

.  The temperature

range is 60°F (15.5°C) to 190°F (87.5°C).  The default setting
is 120°F (49°C).

Summary of Contents for SMART TOUCH

Page 1: ...SYNC Installation and Operation Manual and the SYNC Service Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial pro...

Page 2: ...3 PC to Unit Connection 3 Starting the Program 4 6 2 Status Screen 5 6 3 Graphics Screen 7 4 Fault History Screen 8 5 Cascade Screen 9 6 PARAMETERS Parameter Information Screens 10 Changeable Paramet...

Page 3: ...r assigned to the USB cable above The programs display temperatures in F If you wish to display temperatures in C click on the Settings tab along the top of the Main Screen window and move the cursor...

Page 4: ...the upper left hand corner of the window A window opens in which you can type in the password see FIG 1 3 Note that the password is case sensitive and is in all CAPS Click on the Ok button or press th...

Page 5: ...o run at low fire Finally the 0 10Vdc input Voltage and Flame Current are shown To the right of the sensor temperature readings are the various setpoints The SH setpoint is the setpoint the SMART TOUC...

Page 6: ...active limits if any the last active limit the burner status the last fault and the date and time as stored in the SMART TOUCH PC Program Instructions While in the SMART TOUCH Status Screen you can g...

Page 7: ...he desired scale The top number represents F and the bottom number represents C Press the Ok button to close the Options window The background color of the Graphics Screen can be changed by pressing t...

Page 8: ...is shown as well as the number of successful and failed ignition attempts Finally a count of internal checks is shown The total number of occurrences of certain faults are also stored in the control a...

Page 9: ...t is a check box indicating if the temperature regulation is being held constant and if the Ramp Delay feature is active The Freeze P1 regulation box is checked when the next controller can be started...

Page 10: ...an adjustment to a parameter select the parameter to be changed from the appropriate set Click on the box next to the parameter and type in the value for the parameter Once an adjustment has been mad...

Page 11: ...stable The time range for each ramp delay is adjustable from 1 minute to 40 minutes with the total of all 6 ramp delays not to exceed 109 minutes The default delay time for Periods 1 2 and 3 is 2 minu...

Page 12: ...switching boiler on Parameter 2DJ is the minimum time delay between starting one burner and starting the next burner in the Cascade The range for this parameter is 0 seconds to 255 seconds The default...

Page 13: ...mperature setpoint for fixed operation or the maximum temperature setpoint when the outdoor air sensor is used This parameter can be changed by accessing parameter 4AA The temperature range of this pa...

Page 14: ...alue is 0 This feature will be active if this parameter is set to anything other than 0 Night setback temperature NSB Setp Once the internal clock has been set correctly the night setback feature can...

Page 15: ...has occurred or the maximum user setpoint has been reached Once the SH demand has been satisfied the setpoint will revert back to its calculated setting The boost temperature can be changed by accessi...

Page 16: ...ndow click on the tab labeled 4D Pump Delay to set the delay time for the boiler system and HW pumps see FIG 6 8 below Figure 6 8 Parameter Set 4D SH pump delay after SH demand Boiler Pump D This feat...

Page 17: ...re rises to or above this point the water temperature will be at its minimum setpoint This parameter can be changed by accessing parameter 4FD The temperature range of this parameter is 30 F 34 C to 9...

Page 18: ...eter 4GD The voltage range for this parameter is 0Vdc to 4GC The default value is 10Vdc Min BMS voltage to start demand BMS V Heat If parameter 4GK is set to 1 then the heat demand will be generated b...

Page 19: ...pear confirming that the file was saved Note that the new file name appears in the lower right hand corner of the SMART TOUCH PC program window BMS Voltage at min power BMS V min mod If parameter 4CB...

Page 20: ...Revision Notes Revision A initial release SYNC PCP Rev A Printed in the USA 4 10...

Reviews: