Operating information
Status Display Screens
Section
Display
Description
A
(Water heater
Status Bar)
STANDBY
The unit has not received a call for heat from a remote thermostat nor
has it received a call for heat from a DHW thermostat.
START
The unit has begun a burn cycle and is checking all safety circuits.
PREPURGE
The unit has initiated a prepurge period on a call for heat.
IGNITION
The unit has begun a spark period to ignite the main burner.
The unit has fired and is running at the displayed percentage.
POSTPURGE
The call for heat has been satisfied and the unit runs the fan for an
additional postpurge period to clear the combustion chamber and
vent system of residual flue products.
SHUTDOWN
The unit has been placed in the OFF position.
The controlled temperature has exceeded its set point and its offset.
BLOCKED
The unit has detected a condition that has temporarily interrupted
the current call for heat.
B
(Call for Heat
Indicators)
The tank thermostat or sensor has a call for heat.
The unit is being controlled by a 0 - 10V BMS signal.
The member unit is supplying heat while in Cascade Mode.
Figure 11-2 Status Display Screen
%