46
Installation & Service Manual
STEP
9
NO
CHECK WIRING CONNECTIONS.
NO
YES
REPLACE IGNITER/SENSOR.
YES
STEP
10
NO
YES
GAS VALVE OPEN?
YES
STEP
11
IGNITER "LED" TURNS OFF
& VALVE "LED" STAYS ON?
STEP
12
YES
IGNITER / SENSOR WARMS UP
AND GLOWS RED.
120 VAC AT IGNITER/SENSOR?
NO
REPLACE MODULE.
IGNITION MODULE VALVE
"LED" LIGHTS UP?
"LED" BURNED OUT BUT CONTROL
FUNCTIONS. REPLACE AT A
CONVENIENT TIME.
NO
24 VAC TO GAS VALVE?
NO
CHECK WIRING CONNECTIONS.
NO
REPLACE GAS VALVE.
YES
NO
CHECK WIRING CONNECTIONS.
YES
NO
CHECK MOUNTING.
YES
NO
YES
MAIN BURNER RUNS UNTIL
CALL FOR HEAT ENDS AND
VALVE "LED" TURNS OFF?
YES
MANIFOLD PRESSURE CORRECT?
NO
SET MANIFOLD PRESSURE.
SEE INSTRUCTIONS.
YES
REPLACE IGNITER.
CONTINUITY OF CHASSIS
GROUND CONNECTIONS?
NO
TIGHTEN OR REPLACE GROUND.
YES
IGNITER/SENSOR MOUNTED PROPERLY?
NO
CORRECT MOUNTING.
YES
REPLACE IGNITER.
CHASSIS GROUND & WIRING CONNECTIONS TO IGNITER?
IGNITER/SENSOR MOUNT PROPERLY?
GAS SUPPLY PRESSURE TO GAS VALVE CORRECT?
SET THERMOSTAT ABOVE
WATER TEMPERATURE?
YES
STEP
13
THERMOSTAT OPENS?
YES
NO
REPLACE THERMOSTAT.
GAS VALVE CLOSES?
YES
NO
STEP
14
STEP
15
GAS VALVE CLOSES WHEN ONE LEAD IS REMOVED?
REPLACE GAS VALVE.
CAB STOPS AFTER 30 SEC. POST PURGE?
STEP
16
YES
SYSTEM OK?
STEP
17
NO
REPEAT PROCEDURE UNTIL
SYSTEM OPERATES NORMALLY.
SET GAS SUPPLY PRESSURE.
SEE INSTRUCTIONS.
NO
8
Troubleshooting
TROUBLESHOOTING CHART