19
2
General venting
(continued)
Installation & Service Manual
DANGER
Failure to properly seal all vent joints
and seams may result in flue gas spillage
and carbon monoxide causing severe
personal injury or death.
The connection from the vent to the vent termination
outside the building
MUST
be made with one of the
specified vent materials and must be direct as possible
with no reduction in diameter. The vent accessories not
otherwise provided, such as firestop spacers, thimbles, caps,
etc.,
MUST
be from the same vent material manufacturer
and installed in accordance with the manufacturers listing.
The vent connection through the sidewall must provide
correct spacing to combustible surfaces. The vent pipe
connection to the sidewall vent cap
MUST
have a gas-tight
seal to prevent the leakage of flue products.
VENT HOOD MUST BE
MOUNTED 4’ MIN. AWAY
HORIZONTALLY FROM
DOORS AND WINDOWS
VENT HOOD MUST
BE MOUNTED 1’ MIN.
ABOVE DOORS
AND WINDOWS
VENT HOOD
VENT HOOD
1’ ABOVE GRADE
DIRECT VENT AIR INLET
3’ ABOVE ANY OUTSIDE
AIR INTAKE WITH 10’
VENT HOOD MUST BE MOUNTED
4’ MINIMUM BELOW WINDOWS
VENT HOOD MUST BE
MOUNTED AT LEAST
10’ FROM INSIDE CORNER
4’ MIN
1’ MIN
1’ MIN
4’ MIN
3’ MIN
Figure 2-13 Sidewall Vent Locations
Venting of Flue Products
Locate appliances as close as possible to the sidewall where
the vent for flue products will be installed.
Horizontal runs must slope upwards not less than 1/4 inch
per foot (21 mm per meter) from the appliance to the vent
terminal. Follow manufacturers instructions.
The vent cap shall terminate at least 3 feet (91 cm) above
any forced air inlet within 10 feet (3.05 m).
The vent shall terminate at least 4 feet (1.22 m) below, 4
feet (1.22 m) horizontally from or 1 foot (30 cm) above any
door, window or gravity air inlet to the building.
The vent system shall terminate at least 1 foot (30 cm) above
grade and above normal snow levels.
The vent for a direct vent system shall
NOT
terminate
above public walkways.
The vent shall not be installed closer than 10 feet (3.05 m)
from an inside corner of an L-shaped structure.
Do not terminate the vent in a window well, stairwell,
alcove, courtyard, or other recessed area. The vent can not
terminate below grade.
Flue gas condensate can freeze on exterior walls or on the
vent cap. Frozen condensate on the vent cap can result in
a blocked flue condition. Some discoloration to exterior
building surfaces can be expected. Adjacent brick or
masonry surfaces should be protected with a rust resistant
sheet metal plate.
The vent cap should have a minimum clearance of 4 feet
(1.22 m) horizontally from and in no case above or below,
unless a 4 foot (1.22 m) horizontal distance is maintained
from electric meters, gas meters, regulators and relief
equipment.
Combustion Air Inlet
Combustion air supply pipes can
NOT
be combined into a
single pipe for multiple appliance installations.
Combustion air supplied from outdoors must be free of
contaminants (See
Combustion and Ventilation Air
). To
prevent recirculation of flue products into the combustion
air inlet, follow all instructions in this section.
To help prevent recirculation of flue products:
The combustion air inlet cap
MUST NOT
be installed
above the flue outlet cap.
The combustion air inlet cap must be installed horizontally
or below the flue outlet and
MUST
maintain a minimum 3
foot (91 cm) radius clearance from the flue outlet cap.
The combustion air inlet cap and vent cap for flue outlet
MUST
be located on the same sidewall and in the same
pressure zone.
The combustion air inlet cap must not be installed closer
than 10 feet (3.05 m) from an inside corner of a L-shaped
structure.
The combustion air inlet cap must be installed at least 1
foot (30 cm) above ground level and above normal snow
levels
Summary of Contents for Efficiency-Pac EW 150 -- 300
Page 47: ...47 Notes ...