20
8.8.5
TYPE C
53
When installing the heater as a Type C
53
appliance, it should be noted that the terminals must not be
installed on opposite sides of the building or closer than 500mm apart (centre to centre).
To install a Type C
53
terminal or air inlet, the procedure for either a Type C
13
(horizontal) or a Type C
33
(vertical)
terminal should be followed noting that the annular space of the terminal should be sealed off
8.9
FLUE TERMINAL GUARDING
If a horizontal flue terminal is to be fitted less than 2 metres from ground level or in a location where it can be
touched from a window, door or balcony, a terminal guard must be fitted. An approved terminal guard, Lochinvar
Part No. FTG0001 is available; please contact Lochinvar Limited for further information.
The terminal guard is constructed from plastic-coated mild steel and is suitable for use on condensing appliances
only. The guard should be installed centrally around the terminal ensuring a gap of at least 50mm between the
guard and terminal is maintained.
9.0
AIR SUPPLY
The following information is based on single water heater installations only. If more than one water heater is being
used,
BS6644
should be consulted to calculate the necessary requirements.
9.1
COMBUSTION VENTILATION
When used as a Type C appliance, provided sufficient clearance is provided, ventilation for combustion is not
necessary as the combustion air is ducted directly from outside.
When used as a Type B appliance, the combustion air requirements are as follows:
Model
Gross
Input
(kW)
Net
Input
(kW)
Ventilation
(Room)
(cm
2
)
Compartment
Compartment
(Direct to Outside)
(To Internal Space)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
SHW45-325CE
43.9
39.6
165
200
400
400
800
SHW60-325CE
58.6
52.8
230
265
530
530
1060
TABLE 9.1
COMBUSTION VENTILATION REQUIREMENTS SHW45-325CE – SHW60-325CE
Model
Gross
Input
(kW)
Net
Input
(kW)
Plant Room
Enclosure
Low
Summer Use
Medium
Summer Use
High
Summer Use
Low
Summer Use
Medium
Summer Use
High
Summer Use
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
High
(cm
2
)
Low
(cm
2
)
SHW85-435CE
83.5
75.3
152
304
228
380
304
456
380
760
456
836
532
912
SHW115-435CE
117.2 105.6
212
424
318
530
424
636
530
1060
636
1166
742
1272
SHW145-435CE
146.5 132.0
264
528
396
660
528
792
660
1320
792
1452
924
1584
TABLE 9.2
COMBUSTION VENTILATION REQUIREMENTS SHW85-435CE – SHW145-435CE