1
Service
(continued)
Service Manual
15
Parameter table
Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to
access them
Menu Sub
Item
Parameter Name
(as shown on the LCD screen)
See
Page
Min
Max
Default
User
Installer
Value
Value
Value Access
Access
F
1
Temperature Units
21
°F
°C
°F
Yes
Yes
2
LCD Backlight Time
21
0
255
240
Yes
Yes
3
Freeze Protection; Pump On
21
-22
45
44.6
No
Yes
4
Freeze Protection; Burner On
22
-22
45
37.4
No
Yes
5
Freeze Protection; Burner Diff
22
0
20
5
No
Yes
6
HWG to SH Switching Time
22
0
240
30
No
Yes
7
SH to HWG Switching Time
22
0
240
30
No
Yes
8
Anti-Cycling Time
22
0
40
10
No
Yes
9
Anti-Cycling Differential
22
0
40
1
No
Yes
10
HWG Rate Limiting
22
10
100
100
No
Yes
11
Service Mode Timeout
22
0
40
40
No
Yes
12
Controlling Sensor
22
0
4
2
No
Yes
13
Inlet Control Time Delay
22
0
40
3
No
Yes
G
1
SH Night Setback Offset Temp
22
0
90
0
No
Yes
2
SH Night Setback Mon End
22
N/A
N/A
N/A
No
Yes
3
SH Night Setback Mon Begin
22
N/A
N/A
N/A
No
Yes
4
SH Night Setback Tue End
22
N/A
N/A
N/A
No
Yes
5
SH Night Setback Tue Begin
22
N/A
N/A
N/A
No
Yes
6
SH Night Setback Wed End
22
N/A
N/A
N/A
No
Yes
7
SH Night Setback Wed Begin
22
N/A
N/A
N/A
No
Yes
8
SH Night Setback Thur End
22
N/A
N/A
N/A
No
Yes
9
SH Night Setback Thur Begin
22
N/A
N/A
N/A
No
Yes
10
SH Night Setback Fri End
22
N/A
N/A
N/A
No
Yes
11
SH Night Setback Fri Begiin
22
N/A
N/A
N/A
No
Yes
12
SH Night Setback Sat End
22
N/A
N/A
N/A
No
Yes
13
SH Night Setback Sat Begin
22
N/A
N/A
N/A
No
Yes
14
SH Night Setback Sun End
22
N/A
N/A
N/A
No
Yes
15
SH Night Setback Sun Begin
22
N/A
N/A
N/A
No
Yes
AD
V
ANCED SETUP
SH NIGHT SETB
A
C
K
Summary of Contents for Crest 1.5