1
Service
Service Manual
14
Parameter table
Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to
access them
Menu Sub
Item
Parameter Name
(as shown on the LCD screen)
See
Page
Min
Max
Default
User
Installer
Value
Value
Value Access
Access
C
7
Boost Time
20
0
250
20
No
Yes
8
Boost Temperature
20
0
25
0
No
Yes
9
Shift OA Reset Curve
20
-27
27
0
No
Yes
D
1
Ramp Delay Mode
20
N/A
N/A
N/A
No
Yes
2
Ramp Delay Time #1
20
1
40
2
No
Yes
3
Ramp Delay Time #2
20
1
40
2
No
Yes
4
Ramp Delay Time #3
20
1
40
2
No
Yes
5
Ramp Delay Time #4
20
1
40
1
No
Yes
6
Ramp Delay Time #5
20
1
40
1
No
Yes
7
Ramp Delay Time #6
20
1
40
1
No
Yes
8
Ramp Delay Limit #1
20
10
100
20
No
Yes
9
Ramp Delay Limit #2
20
10
100
30
No
Yes
10
Ramp Delay Limit #3
20
10
100
40
No
Yes
11
Ramp Delay Limit #4
20
10
100
55
No
Yes
12
Ramp Delay Limit #5
20
10
100
75
No
Yes
13
Ramp Delay Limit #6
20
10
100
100
No
Yes
E
1
BMS Active/Inactive
21
ACTIVE INACTIVE INACTIVE
No
Yes
2
BMS Mode
21
POWER SETPOINT
POWER
No
Yes
3
BMS Volts at Min Rate
21
0
10
2
No
Yes
4
BMS Volts at Max Rate
21
0
10
10
No
Yes
5
BMS Rate at Min Volts
21
4
100
4
No
Yes
6
BMS Rate at Max Volts
21
0
100
100
No
Yes
7
BMS Volts at Min Setpoint
21
0
10
2
No
Yes
8
BMS Volts at Max Setpoint
21
0
10
10
No
Yes
9
BMS Setpoint at Min Volts
21
32
185
68.9
No
Yes
10
BMS Setpoint at Max Volts
21
32
185
178.7
No
Yes
11
BMS Volts to Enable
21
0
10
2
No
Yes
12
Differential to Stop BMS Demand
21
0
10
0.5
No
Yes
13
BMS Enable Mode
21
ENABLE VOLTAGE VOLTAGE
No
Yes
OUTDOOR
RESET
RAMP DELA
Y
BMS
Summary of Contents for Crest 1.5
Page 54: ...3 Troubleshooting 54 NOTES ...