background image

1  

Prevent combustion air contamination

4

If the boiler combustion air inlet is  located 
in a laundry room or pool facility, for 
example, these areas will always contain 
hazardous contaminants.

To prevent the potential of severe 
personal injury or death, check for areas 
and products listed in Table 1A before 
installing the boiler or air inlet piping.

If contaminants are found, you MUST:

  • Remove contaminants permanently.  
   

          —OR—

  • Relocate air inlet and vent  

 

    terminations to other areas.

 WARNING

 WARNING

Products to avoid:

Spray cans containing chloro/fluorocarbons

Permanent wave solutions

Chlorinated waxes/cleaners

Chlorine-based swimming pool chemicals

Calcium chloride used for thawing

Sodium chloride used for water softening

Refrigerant leaks

Paint or varnish removers

Hydrochloric acid/muriatic acid

Cements and glues

Antistatic fabric softeners used in clothes dryers

Chlorine-type bleaches, detergents, and cleaning solvents 
found in household laundry rooms
Adhesives used to fasten building products and other similar 
products

Areas likely to have contaminants

Dry cleaning/laundry areas and establishments

Swimming pools

Metal fabrication plants

Beauty shops

Refrigeration repair shops

Photo processing plants

Auto body shops

Plastic manufacturing plants

Furniture refinishing areas and establishments

New building construction

Remodeling areas

Garages with workshops

Table 1A Corrosive Contaminants and Sources

 WARNING

If the boiler combustion air inlet is located 
in any area likely to cause contamination, 
or if products which would contaminate 
the air cannot be removed, you must have 
the combustion air and vent re-piped 
and terminated to another location. 

 

Contaminated combustion air will damage 
the boiler, resulting in possible severe 
personal injury, death, or substantial 
property damage.

Pool and laundry products and common household 
and hobby products often contain fluorine or chlorine 
compounds.  When these chemicals pass through the boiler, 
they can form strong acids.  The acid can eat through the 
boiler wall, causing serious damage and presenting a possible 
threat of flue gas spillage or boiler water leakage into the 
building.

Please read the information listed in Table 1A.  If 
contaminating chemicals will be present near the location of 
the boiler combustion air inlet, have your installer pipe the 
boiler combustion air and vent to another location, per the    
Copper-fin II Installation and Operation Manual.

                                  

User’s Information Manual

Summary of Contents for Copper-fin II 2072

Page 1: ...e present WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a near by phone F...

Page 2: ...avoided may result in property damage NOTICE indicates special instructions on installation operation or maintenance that are important but not related to personal injury or property damage Contents...

Page 3: ...nts in the Copper fin II Installation and Operation Manual Checking equipment Upon receiving equipment check for signs of shipping damage Pay particular attention to parts accompanying the appliance w...

Page 4: ...tal fabrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishments New building construc...

Page 5: ...stiff bristle brush Remove and clean burners using water Dry before re assembling Clean the blower wheel with a brush and vacuum Do not let dirt from cleaning get pulled into the blower Owner mainten...

Page 6: ...iquids near the appliance Remove immediately if found 2 Air contaminants Products containing chlorine or fluorine if allowed to contaminate the appliance intake air will cause acidic condensate in the...

Page 7: ...to a safe place of disposal This discharge line must be installed by a qualified heating installer or service technician in accordance with the instructions in the Copper fin II Installation and Opera...

Page 8: ...nformation above on this label 2 Turn off all electric power to the appliance 3 Open control access panel 4 This appliance is equipped with an ignition device which automatically lights the burner Do...

Page 9: ...nk water temperature set point during normal operation Press to change displayed data values in Menu Mode Press to navigate through menu listing in Menu Mode Press to toggle display during normal oper...

Page 10: ...the code parameter A1 must be accessed The default code is 0704 The code can be changed one digit at a time by using the arrow keys on the display A2 Date and time The control uses an internal clock...

Page 11: ...The maximum allowable tank set point can be adjusted using parameter E4 The temperature range of this parameter is 60 F 16 C to the value of parameter E3 to 190 F 88 C The default temperature is 190 F...

Page 12: ...in II Service Manual This feature can be turned on or off depending on the installation This parameter can be changed by the installer by accessing parameter G3 The control range of this parameter is...

Page 13: ...r ignition Display will show IGNITOR A or IGNITOR B depending on which stage has priority HTR RUN STG Or HTR DHW STG The unit has fired and is running at the displayed number of stages 1 2 3 4 HTR POS...

Page 14: ...parenthesis SYSSUP F If the system supply sensor has not been selected as the control sensor only the system supply temperature will be displayed SYSSUP OPEN The control does not detect the system su...

Page 15: ...Press the Next arrow key on the SMART SYSTEM display to access Screen 8 Screen 8 Line 1 SYS PUMP The control will display either ON or OFF based upon system pump requirements upon demand for space hea...

Page 16: ...release Revision B ECO C11124 reflects the update of ignition timing information on page 13 Revision C PCP 3000021634 CN 500011858 reflects an update to the maintenance information on page 5 CFX CHX...

Reviews: