background image

12

FIGURE 11.

FILLING THE WATER HEATER

Never use this water heater unless it is completely full of water. 
To prevent damage to the tank, the tank must be fi lled with water. 
Water must fl ow from the hot water faucet before turning “ON” gas 
to the water heater.

To fi ll the water heater with water:

1.  Close the water heater drain valve by turning the handle to the 

right (clockwise). The drain valve is on the lower front of the water 
heater.

2. Open the cold water supply valve to the water heater.  

NOTE: The cold water supply valve must be left open when 
the water heater is in use.

3.  To insure complete fi lling of the tank, allow air to exit by opening the 

nearest hot water faucet.  Allow water to run until a constant fl ow is 
obtained.  This will let air out of the water heater and the piping.

4.  Check all water piping and connections for leaks.  Repair as needed.

VENTING

VENT DAMPERS - Any vent damper, whether it is operated thermally 
or otherwise must be removed if its use inhibits proper drafting of 
the water heater.

Thermally Operated Vent Dampers: Gas-fi red water heaters having 
thermal effi ciency in excess of 80% may produce a relatively low fl ue 
gas temperature.  Such temperatures may not be high enough to 
properly open thermally operated vent dampers.  This would cause 
spillage of the fl ue gases and may cause carbon monoxide poisoning.

Vent dampers must bear evidence of certifi cation as complying with 
the current edition of the American National Standard ANSI Z21.68 
(ANSI Z21.66 & 67, respectively, cover electrically and mechanically 
actuated vent dampers).  Before installation of any vent damper, 
consult the local gas utility for further information.

For replacement heater installations where using pre-existing venting, 
venting must be inspected for obstructions and if deterioration is 
present venting must be replaced.

To insure proper venting of this gas-fi red water heater, the correct 
vent pipe diameter must be utilized.  Any additions or deletions of 
other gas appliances on a common vent with this water heater may 
adversely affect the operation of the water heater.  Consult your gas 
supplier if any such changes are planned.

For proper venting in certain installations, a larger diameter vent pipe 
may be necessary.  Consult your gas supplier to aid you in determining 
the proper venting for your water heater from the vent tables in the 
current edition of the National Fuel Gas Code ANSI Z223.1/NFPA  54. 

Periodically check the venting system for signs of obstruction or 
deterioration and replace if needed.

The combustion and ventilation air fl ow must not be obstructed.

The water heater with draft hood installed must be connected to a 
chimney or listed vent pipe system, which terminates to the outdoors.  
Never operate the water heater unless it is vented to the outdoors 
and has adequate air supply to avoid risks of improper operation, 
explosion or asphyxiation.

For proper drafthood attachment, the drafthood legs may be angled 
slightly inward.

Obstructed or deteriorated vent systems may present serious health 
risk or asphyxiation.

The vent pipe from the water heater must be no less than the diameter 
of the draft hood outlet on the water heater and must slope upward 
at least 1/4 inch per linear foot (21 mm per meter), see Figure 12.

All vent gases must be completely vented to the outdoors of the 
structure (dwelling).  Install only the draft hood provided with the 
new water heater and no other draft hood.

Vent pipes must be secured at each joint with sheet metal screws.

FIGURE 12.  

Summary of Contents for COMMERCIAL GAS WATER HEATERS

Page 1: ...IL AT 2TECH LOCHINVAR COM COMMERCIAL GAS WATER HEATERS For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER C3 Technology Gas Water Heaters meet the new ANSI Z21 10 1 standard that...

Page 2: ...it relates to the installation of gas fired water heaters The qualified installer must also be familiar with the design features and use of flammable vapor ignition resistant water heaters and have a...

Page 3: ...3 GENERAL SAFETY...

Page 4: ...follow the safety rules the water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for the installation operation an...

Page 5: ...Y LOCAL CODES FIGURE 1 J Drip Leg Sediment Trap K Inner Door L Outer door M Union N Inlet Water Shut off Valve O Cold Water Inlet P Inlet Dip Tube Q Temperature Pressure Relief Valve R Rating Plate S...

Page 6: ...others These include the elderly children the infirm or physically mentally handicapped If anyone using hot water in your home fits into one of these groups or if there is a local code or state law re...

Page 7: ...larm or turn off the incoming water to the water heater when leakage is detected Sensors mounted in the drain pan that turn off the water supply to the entire home when water is detected in the drain...

Page 8: ...al injury or death Do not apply insulation to the top of the water heater as this will interfere with safe operation of the draft hood Do not cover the outer door thermostat or temperature pressure re...

Page 9: ...1 cm2 kW of total input rating of all equipment in the enclosure see Figure 9 Alternatively a single permanent opening may be used when communicating directly with the outdoors or with spaces that fre...

Page 10: ...uires water for space heating at temperatures higher than required for domestic water purposes a tempering valve must be installed Please refer to Figure 2 for suggested piping arrangement Water suppl...

Page 11: ...ctly into the fitting of the water heater designed for the relief valve Position the valve downward and provide tubing so that any discharge will exit only within 6 inches 153 mm above or at any dista...

Page 12: ...ion For replacement heater installations where using pre existing venting venting must be inspected for obstructions and if deterioration is present venting must be replaced To insure proper venting o...

Page 13: ...ing all gas appliances is used also turn off the gas at each appliance Leave all gas appliances shut off until the water heater installation is complete A gas line of sufficient size must be run to th...

Page 14: ...trol valve of the water heater can be accomplished by either of the two methods shown in Figures 13 and 14 A sediment trap shall be installed as close to the inlet of the water heater as practical at...

Page 15: ...burner It can be located by looking through the glass view port while pressing the piezo ignitor button several times Look for a spark at the pilot location see Figure D 9 Once the pilot has been foun...

Page 16: ...htubs showers sink etc HOTTER WATER CAN SCALD Water heaters are intended to produce hot water Water heated to a temperature which will satisfy space heating clothes washing dish washing and other sani...

Page 17: ...urner area during heating and cooling periods and should be considered normal See Condensation in this section OPERATIONAL CONDITIONS SMELLY WATER In each water heater there is installed at least one...

Page 18: ...able However over a period of time a flooded water heater will create dangerous conditions which can cause DEATH SERIOUS BODILY INJURY OR PROPERTY DAMAGE Contact a qualified installer or service agenc...

Page 19: ...s to completely reset and continues to release water immediately close the cold water inlet to the water heater follow the draining instructions and replace the temperature pressure relief valve with...

Page 20: ...d drip onto the burner or run on the floor This is common at the time of start up after installation and when incoming water is cold I Water in the water heater bottom or on the floor may be from cond...

Page 21: ...ional 26 Instruction Manual 27A Nipple with Heat Trap 27B Secondary Anode with Heat Trap Not Shown Now that you have purchased this water heater should a need ever exist for repair parts or service si...

Page 22: ...nctions Thermocouple TCO malfunction Replace pilot assembly High ambient room temperature Contact a service agency to determine cause BURNER WILL NOT Dirty or clogged air intake screen Clean and reins...

Page 23: ...23 NOTES...

Page 24: ...24 300 Maddox Simpson Parkway Lebanon TN 37090 Phone 615 889 8900 Fax 615 547 1000 Technical Services email 2tech lochinvar com www lochinvar com Copyright 2011 Lochinvar LLC All rights reserved...

Reviews: