Inspect ignition and flame sense 

electrodes

1.  Remove the ignition and flame sense electrodes from the 

water heater heat exchanger access cover.

2.  Remove any deposits accumulated on the ignition/flame 

sense electrode using sandpaper.  If the electrodes cannot 
be cleaned satisfactorily, replace with new ones.

3.  Replace ignition/flame sense electrode, making sure 

gasket is in good condition and correctly positioned.

Check ignition ground wiring

1.  Inspect water heater ground wire from the heat exchanger 

access cover to ground terminal strip.

2.  Verify all wiring is in good condition and securely 

attached.

3.  Check ground continuity of wiring using continuity 

meter.

4.  Replace ground wires if ground continuity is not 

satisfactory.

Check all water heater wiring

1.  Inspect all water heater wiring, making sure wires are in 

good condition and securely attached.

Check control settings

1.  Go to the Setup Screen and check all settings.  See Section 

1 of this manual.  Adjust settings if necessary.  See Section 
1 of this manual for adjustment procedures.

2.  Check settings of external limit controls (if any) and 

adjust if necessary.

Perform start-up and checks

1.  Start water heater and perform checks and tests specified 

in Section 9 - Start-up of the Armor X2 Installation and 
Operation Manual.

Check burner flame

1.  Inspect flame through observation window.

2.  If the flame is unsatisfactory at either high fire or low 

fire, turn off water heater and allow water heater to cool 
down.  Remove the burner and clean it thoroughly using a 
vacuum cleaner or compressed air.  Do not use compressed 
air to clean burner if performed inside a building.

3.  Remove the burner, reference FIG. 2-2.

4.  When replacing the burner, ensure gasket is in good 

condition and positioned correctly (FIG. 2-2).

BURNER

AIR/GAS GASKET

FLAPPER VALVE

BURNER DOOR

BURNER DOOR

HEX NUT (6)

IGNITER

FLAME SENSE

IGNITER GASKET

FLAME SENSE

GASKET

FLAME SENSE

SCREW (2X)

IGNITER SCREW (2X)

DOOR FIBER

FLAPPER VALVE

SCREW (5X)

Figure 2-2 Burner Assembly

2  

Maintenance 

(continued)

35

        

                             Service Manual

Check flame signal

1.  At high fire the flame signal shown on the display should be 

at least 10 microamps.

2.  A lower flame signal may indicate a fouled or damaged 

flame sense electrode.  If cleaning the flame sense electrode 
does not improve, ground wiring is in good condition, and 
ground continuity is satisfactory, replace the flame sense 
electrode.

3.  See Section 3 - Troubleshooting in this manual for other 

procedures to deal with low flame signal.

Review with owner

1.  Review the Armor X2 Installation and Operation Manual 

with the owner.

2.  Emphasize the need to perform the maintenance schedule 

specified in the Armor X2 Installation and Operation 
Manual (and in this manual as well).

3.  Remind the owner of the need to call a licensed contractor 

should the heater or system exhibit any unusual behavior.

Summary of Contents for ArmorX2 1.0

Page 1: ...echnician Read all instructions including this manual and the Armor X2 Installation and Operation Manual before installing Perform steps in the order given Failure to comply could result in severe per...

Page 2: ...er Table 10 11 Viewable and Changeable Control Parameters 12 31 2 MAINTENANCE Maintenance and Annual Startup 32 36 3 TROUBLESHOOTING Alarm Screen 37 Before Troubleshooting 38 Check Control Module Fuse...

Page 3: ...ing the ceramic materials it is advisable that the installer follow these safety guidelines Avoid breathing dust and contact with skin and eyes Use NIOSH certified dust respirator N95 This type of res...

Page 4: ...led information Armor X2 water heater operation Setup Service Setup Setpoint Night Setback Cascade Pumps BMS Maintenance Service and maintenance schedules Address reported problems Inspect water heate...

Page 5: ...1 Service The Armor X2 display 5 Service Manual...

Page 6: ...SENSOR PRIMARY SECONDARY FLAME SENSOR BLOCKED DRAIN SWITCH TOUCH PANEL INTERFACE PC INTERFACE SECONDARY SMART CONTROL MODULE PRIMARY SMART CONTROL MODULE HW TANK SENSOR ENABLE TOUCH DISPLAY MODBUS CO...

Page 7: ...IME CONTACTS SEQUENCER BUILDING MANAGEMENT SYSTEM HEAT EXCHANGER 1 HEAT EXCHANGER 2 HW PUMP IGNITOR BLOWER GAS VALVE PC INTERFACE SECONDARY SMART TOUCH CONTROL MODULE TOUCH PANEL INTERFACE TOUCH DISPL...

Page 8: ...t of gas to flow Sequence of operation Table 1A shows control module normal sequences of operation for each individual control module Additionally the control modules are programmed to synchronize the...

Page 9: ...ol does not detect flame current the control will try again If no flame current is detected on the second try the control will lockout indefinitely until the RESET button on the touch screen LCD is pr...

Page 10: ...No Serv Not Time 18 No No Yes Yes Serv Not Run H 18 No No Yes Yes Serv Not Cycl 18 No No Yes Yes Max Serv T 19 Yes No Yes No Temp Unit 19 No No Yes Yes User Passwd 19 No No Yes Yes LCD Backlight 19 N...

Page 11: ...Yes Max Outl temp 22 No No Yes Yes CASCADE 1 Service continued SETBACK BMS Type 23 No No Yes Yes ModBus Timeout 23 No No Yes Yes BMS Setp min V 23 No No Yes Yes BMS Setp max V 23 No No Yes Yes BMS V...

Page 12: ...ater call Standby The water heater has not received a hot water call HW Storage The water heater has received a hot water call HW Pump Delay The water heater has satisfied a hot water call and the hot...

Page 13: ...e time is displayed in the upper right hand corner of the display It is displayed in a 24 hour format Reference the Night Setback parameters on page 21 for information regarding adjusting the date and...

Page 14: ...w Switch Low Water Cutoff Is ON when the low water cutoff contacts are closed or if an optional flow switch is used and it is closed as well Is OFF when the low water cutoff contacts are open or if an...

Page 15: ...he control has dropped below 80 VAC Reference page 47 for more information regarding this fault message Connect Tank Sensor Tank sensor is not detected by Control Module 1 For proper operation of the...

Page 16: ...hows the operating and fault history of the two 2 control modules Service Mode Allows the installer to control the fan speed of the individual control modules for the purposes of combustion analysis S...

Page 17: ...eter and adjustment buttons To adjust the parameter press the or buttons to change the value being displayed Once the parameter has been adjusted to the desired setting press the APPLY button to chang...

Page 18: ...us BMS Voltage based on a 0 10V dc signal is provided to the water heater to control either set point or modulation An equivalent 0 10V dc signal is provided by writing to the holding registers on the...

Page 19: ...ler to a code of their choosing The default code is 0704 LCD Backlight Sets the length of time the LCD Screen will stay on after a button has been pressed This parameter can be changed by the user or...

Page 20: ...point Ifthetemperaturedropsbelowthe temperature parameter the control will abort anti cycling andallowthewaterheatertofire Thisparametercanonlybe changed by the installer The temperature range of this...

Page 21: ...han 32 F the night setback feature becomes active This will require on and off times to be programmed for the days that reduced temperatures are required Each day of the week Monday through Sunday wil...

Page 22: ...ler The temperature range of this parameter is 0 to 72 F The default value is 10 F Cascade Off On Differential Sets how many degrees below the turn off temperature set point Cascade Off Differential t...

Page 23: ...his parameter can only be changed by the installer The temperature range of this parameter is 70 to 190 F The default value is 179 F BMS Voltage at Minimum Set Point Determines the voltage at which th...

Page 24: ...modulation rate power Below this voltage the modulation rate power will be at the setting of the BMS Modulation at Minimum Voltage parameter This parameter is only active when the BMS Type is set to...

Page 25: ...in the cascade Demand Shows the status of the cascade Displayed items are No Demand the Cascade leader has not received a call for heat HotWaterDemand theCascadeleaderhasreceiveda call for heat Set P...

Page 26: ...03 of the Modbus communication board by the Building Automation System The value is displayed as the effective setpoint in degrees F or C Note The water heater can be configured to operate off the wat...

Page 27: ...The temperature is the tank set point for a Hot Water call Tank Sensor Temperature sensed in the tank by the tank sensor Time The time is displayed in the upper right hand corner of the display It is...

Page 28: ...ol module RPM s Each blower will display the rpm that the control module is requiring of the blower Flame Signal The flame signal for each control module will be displayed in dc microamps Time The tim...

Page 29: ...ay bar with their Min and Max ranges listed below them Press the BACK button to return to the Parameter Selection Screen Time The time is displayed in the upper right hand corner of the display It is...

Page 30: ...nitions Shows the total number of times the control has attempted to ignite Last 10 Faults Shows the last 10 faults of the control module by date and time Time The time is displayed in the upper right...

Page 31: ...dicator A blower is depicted on the display with a power level indicator beside it The level will increase and decrease indicating the approximate power level of the blower The display box underneath...

Page 32: ...and performance verification per Section 9 in the Armor X2 Installation and Operation Manual Flame inspection stable uniform Flame signal at least 10 microamps at high fire Clean the heat exchanger i...

Page 33: ...vicinity they must be removed If they cannot be removed reinstall the air and vent lines per this manual and the Armor X2 Installation and Operation Manual Inspect water heater interior 1 Remove the f...

Page 34: ...inspection agency to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally Certai...

Page 35: ...e through observation window 2 If the flame is unsatisfactory at either high fire or low fire turn off water heater and allow water heater to cool down Remove the burner and clean it thoroughly using...

Page 36: ...the heat exchanger while dry using a nylon bristle brush Caution DO NOT use a metal brush Re vacuum the heat exchanger 8 Finish cleaning using a clean cloth dampened with warm water Rinse out debris w...

Page 37: ...does not have a fault No Alarm Present will be in the text It is possible for one control module to be in alarm while the other continues to function However it will not be possible to view any other...

Page 38: ...c If one of these fuses is blown it can prevent the control module or other components from operating 1 Turn OFF the power to the water heater at the external line switch 2 Remove the front access cov...

Page 39: ...ain control board Blown fuse Replace fuse F3 on the main control board see page 38 of this manual No Burner Operation Main control board temperature set point satisfied Review temperature setting Remo...

Page 40: ...tance 68 14 773 176 1 707 86 9 804 194 1 266 104 6 652 212 952 122 4 607 230 726 140 3 252 248 560 158 2 337 Checking temperature sensors The water heater temperature sensors inlet water outlet water...

Page 41: ...procedure Clean or replace the burner as necessary Low water flow through the heat exchanger Refer to Section 6 System Piping of the Armor X2 Installation and Operation Manual for minimum flow rates...

Page 42: ...heck the flame rod and make sure it is clean Check the internal wiring for bad connections Replace main control board Gas Valve Connection will require a manual reset once the condition has been corre...

Page 43: ...ect flame sensor and associated wiring Reference page 35 of this manual for removal and cleaning procedures Replace if necessary Inspect the burner Reference page 35 of this manual for removal and cle...

Page 44: ...alve is not opening Replace the gas valve Inspect flame sensor and associated wiring Reference page 35 of this manual for removal and cleaning procedures Replace if necessary Inspect the burner Refere...

Page 45: ...le 3B on page 40 of this manual Replace sensor if necessary Replace outlet sensor HEX Temp SW Check continuity across two contacts Wires should be connected at both poles of normally closed switch Ins...

Page 46: ...ay to reset Either the inlet water or outlet water temperature sensor has been shorted Check the sensors and their associated wiring Repair or replace the sensor or wiring if damaged Measure the resis...

Page 47: ...s manual for removal and cleaning procedures Replace if necessary Faulty air pressure switch Replace switch Flap valve contacts are in an open position Check the wiring connections to the flap valve s...

Page 48: ...l of water and that all air has been properly purged from the system Verify that the heater is piped properly into the heating system Refer to Section 6 System Piping of the Armor X2 Installation and...

Page 49: ...een from the Status Screen by pressing the MAIN button and then the SERVICE MODE button 5 On the Service Screen place Heat Exchanger 1 into operation by selecting Heat Exchanger 1 with the SELECT butt...

Page 50: ...combustion is still not within the specified range revisit the possible causes in Table 3F on page 49 or replace the gas valve CAUTION Under normal operating conditions this valve should not need adju...

Page 51: ...Notes 51...

Page 52: ...Revision Notes Revision A ECO C09645 initial release AWX2 SER Rev A 1 12...

Reviews: