4

LCN-SHS

       Installation guide 

Local Control Network  -  building controls in perfection

P-connection:

Here  you  can  connect  for  example,  the  4-way  binary  sensor  (LCN-BT4H/-BU4L),  the   
current  sensor  (LCN-BS4)  and  the  relay  blocks  (LCN-R8H/-R4M2H/-R2H.  The  LCN-
BT4H/BU4L  and  LCN-BS4  will  be  detected  automatically.  The  LCN-R8H  has  to  be 
activated first with the  LCN-P or LCN-PRO .

Notes about the sensor technology:

The module monitors overloads and short circuits  (T-, I-, P-port) on its sensor technology. 
Should the module be short circuited on its periphery, due to wiring errors, it will switch off 
the power supply from the sensor for 4 seconds by itself. If 2 further tests show the same 
error, it will switch off for 8s + 30s and a status message will be sent to the bus:

 “

module reports overload/short circuit periphery.

”,

apart from that the red LED will flash cyclic, as long as the sensor technology is 
switched off.

In this case check the connected sensor technology and the wiring. 
The LCN-SHS module stays accessible and operational even after these errors!

®

Summary of Contents for LCN-BT4H

Page 1: ...has 3 electronic outputs see illustration which are seperately controlled Amongst other things the push button converters LCN BT4H LCN BU4L the relay contacts LCN R8H LCN R2H LCN R4M2H and also the b...

Page 2: ...ange data wire blue neutral wire L L black phase live The power connections are voltage fixed up to max 4kV L N according to VDE additio nal measures against overvoltage in operational conditions are...

Page 3: ...itional switchings if necessary as actuator The functions can be programmed with the setup programme LCN Por LCN PRO T connection Over a LCN T8 or push button converter LCN BT4H BU4L max 8 conventiona...

Page 4: ...erloads and short circuits T I P port on its sensor technology Should the module be short circuited on its periphery due to wiring errors it will switch off the power supply from the sensor for 4 seco...

Page 5: ...and the LCN PRO received telegram data was faulty IR telegram received from unauthorised sender received illegal command will be ignored error in the structure of a received command parameter of a co...

Page 6: ...controlled over the bus the module may be installed before being setting up In this case the serial number of the unprogrammed module should be noted in the building plan for better identification Des...

Page 7: ...ut blocking 2x1 clock 1 relay 2 module ID 5 254 group nr 5 254 segment nr 5 124 12 fixed plus 10 dynamic A B C D with each 2 8 targets each 3 commands and 32 targets at 3 commands double operation dep...

Page 8: ...al access control transponder Properties of the built in control progamme 8 10 or 12 bit value correction hum sound suppression remote query two continuous controllers input sizes can be calculated as...

Page 9: ...ion Connection power supply power consumption terminals wire type load side connection sensor side Technical data 230VAC 15 50 60Hz 110VAC version available 0 4W screwless solid max 2 5mm oder fine wi...

Page 10: ...rel non condensing use as stationary installation according to VDE632 VDE637 IP20 38mm 2HP x 92mm x 66 5mm DIN rail 35 mm DIN50022 Installation operating temperature air humitidy environmental condit...

Reviews: