ROC-50 RATE OF CHANGE LOAD CONTROL

INSTALLATION, SET UP AND ADJUSTMENT

The Model ROC-50 monitors the true power going to a motor.
By sensing power (volts x amps x power factor) rather than just
amps, there is much greater sensitivity. It has two adjustable set
points.

Rate - Limits sudden increases in load regardless of total load.
Max - Limits the total load.

MOUNTING

Wiring is done to un-pluggable terminal strips on the rear of the unit.
Three ways to mount:

O n door or raceway - use cutout template

Panel Mount - use te optional Bezel Kit (No Charge)

O n wall - on standard outdoor junction box + optional

  O utlet Box Adapter (No Charge)

VOLTAGE

120 volts AC is taken from two of the phases. If the motor

starter already has a 120-volt control transformer with 10VA

of free capacity, it can be used. O therwise, install a separate

transformer. It is okay if the secondary is grounded.

BE SURE TO  NO TE WHICH TWO  PHASES SUPPLY THE

TRANSFO RMER.

In 120/ 208V three-phase system, the 120V MUST come from a

transformer connected to two of the phases. The 120V phase to

ground voltage cannot be used.

CURRENT

The current signal is taken from the REMAINING phase.
This current sample passes through the Range Finder Toroid.

It is VERY IMPO RTANT that the current signal comes from the phase
that IS NO T supplying the 120V control transformer. Be extra careful
when the machine has reversing starters or multi-speed windings. If a
wrong phase is used the control will either:

Work backwards

Have reduced sensitivity

If you are using a variable frequency drive, use a different control.
Call LOAD CO NTRO LS, INC. for help.

LOAD CONTROLS

INCORPORATED

Call LOAD CONTROLS, INC for help.

ROC-50 RATE OF CHANGE

 LOAD CONTROL

INSTALLATION, SET UP AND ADJUSTMENT

MOUNTING

VOLTAGE

CURRENT

Summary of Contents for ROC-50

Page 1: ...ity it can be used Otherwise install a separate transformer It is okay if the secondary is grounded BE SURE TO NOTE WHICH TWO PHASES SUPPL YTHE TRANSFORMER In 120 208V three phase system the 120V MUST come from a transformer connected to two of the phases The 120V phase to ground voltage cannot be used CURRENT The current signal is taken from the REMAINING phase This current sample passes through ...

Page 2: ...0 55 0 183 6 ON 1 40 55 0 138 6 ON 1 50 55 0 110 6 ON 1 60 84 0 140 1 ON 1 100 5 75 84 0 112 1 ON 1 100 5 100 130 130 1 ON 1 150 5 125 130 104 1 ON 1 150 5 150 173 115 1 ON 1 200 5 200 216 108 1 ON 1 250 5 250 260 104 1 ON 1 300 5 300 346 115 1 ON 1 400 5 MUL TIPLIERS For nominal voltages other than 460 volts multiply 460V full scale by 208V 45 230V 5 380V 83 415V 9 575V 1 25 For Kilowatts multipl...

Page 3: ...nt Gold flashed contacts Reed Relays Mercury Switches 4 20 MILLIAMP ANAL OG OUTPUT The Analog Output is directly proportional to Full Scale capacity It is always active 500 ohm maximum con nected impedance Terminal 2 4 20mA Positive Terminal 3 4 20mA Negative Use twisted pair or in noisy environments use shielded cable Ground shield at other end Use the Full Scale capacity from the chart to scale ...

Page 4: ...rip until the time is exceeded If t he trip condition goes away before the time is up the timer resets to zero ï Start with minimum Dela y If you are getting trips where you donít want them increase the Delay Time Adjusting R ate Set P oint The Rate Set Point limits sudden load changes 1 Fastest most sensitive 40 Slo west least sensitive Start at about 15 Go slo wer if you get nuisance trips Go fa...

Reviews: