
Convection Grills
LTR50001038, Rev. E
Gas and P
ow
er Requir
ements
www.calflamebbq.com
10
Electrical Supply Requirements
You will need a dedicated 120V 10 amp grounded
electrical service. The power supplied to your grill
enclosure must be on a dedicated circuit with no other
appliances or lights sharing the power.
You do not need to hire a contractor to install your
electrical service, but you must ensure you have
all required permits and the installation complies
with State and local code. We recommend you hire
a certified contractor if you do not wish to do the
installation yourself.
If your dealer is not a certified contractor, you will need
to hire a contractor for installation of your electrical
service.
When installed in the United States, the electrical
wiring must meet the requirements of National Electric
Code, ANSI/NFPA 70-1999 and any applicable state
or local codes. The electrical circuit must be installed
by an electrical contractor and approved by a local
building / electrical inspector.
To determine the current, voltage, and wire size
required for the island configuration to be connected,
refer to the following:
Wire size is determined by length of run from
•
breaker box to the barbecue island and maximum
current draw.
We recommend copper wire with THHN
•
insulation.
All wiring must be copper to ensure adequate
•
connections. Do not use aluminum wire.
When NEC requires the use of wires larger than #6
•
(10mm²), install a junction box near the barbecue
island and use #6 (10mm²) wire between the
junction box and the grill enclosure.
Summary of Contents for Cal Flame BBQ08874CP
Page 1: ...LTR50001038 Rev E 1 1 16...