Pipe and Drain pipes Connection
Liquid pipe
Tighten rope
Shelf
Vapor pipe
Angle hole
※
Select suitable position to make according to the location of indoor and outdoor units.
Position of the pipes
※
Take the pipes out of the accessory case.
※
Pull the pipes and cables from the holes and turn away the block things in the pipe.
※
Turn away the stopper in the connection pipes of the indoor unit.
※
Oiling bell-bottom of the pipe connection and the inner of sealing.
※
Align the pipes, connected with the screw with a torsion wrench. The torque list in the
table below.
※
Wrap the connected position of thermal insulation pipes.
Torque
(N . m )
Φ6 . 35
Φ1 9 .05
7 5~8 0
73~7 8
Φ1 5 .88
Pipe connection
The size
of pipe
(m m )
Φ9 . 52
15~2 5
3 5~4 0
Φ1 2 . 7
4 5~6 0
※
The drain should be downwards.
※
Tighten the interface.
※
Wrapping from 10cm to the plug of indoor unit
with plastic belt.
※
Make the pipe, cable to power and cable to signals
in order. Make sure of the streching direction and
the smoothly surface of the drain.
Side wind tube downward
Tighten tie-in
Attach
:
Wind pipe connection for ZV series
※
※
Through-flow
fan leaves
fresh air tube
Interface
Drain hose
(
in the accessory case
)
Thermal insulation drain pipe
Drain pipes connection
- 12 -
Indoor Unit
Summary of Contents for LT48N
Page 2: ...product...
Page 6: ...3 Controlling panel Mid...
Page 20: ...TWELVE...
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......