14
9. Appendix 1
Interface protocol USB and RS485 (not Modbus)
Byte 0…3
Sensor type
Byte 4…11 IEEE address
Byte 12
…13 PAN-ID
Byte 14…22 4xdata à 2Byte
Byte 23
Hop (number of intermediate stations)
Byte 24
Battery status
Byte 25
RSSI (field intensity)
Interface protocol for Modbus
For further information, please refer to the Modbus manual.
Register No.
Assignment
Example
Remarks
xxxx1
Device type transmitter 1
H
0x0000
xxxx2
Device type transmitter 1
L
0x1202
LKM75xFT
xxxx3
IEEE address H1
0x0015
xxxx4
IEEE address L1
0x8d00
xxxx5
IEEE address H0
0x0008
xxxx6
IEEE address L0
0x23CD
xxxx7
PAN ID
0xBAFF
xxxx8
Temperature
0x00EA
23.4°C
xxxx9
Analogue 2
0x0230
In general, the moisture value in the
case of transmitters with SHTxx,
here 56.0% r.h.
xxx10
Analogue 3
0x0000
In general 0, available only in the
case of special transmittes
xxx11
Analogue 4
0x0000
In general 0, available only in the
case of special transmitters
xxx12
Battery/Lost-Connect/ LQI
0x00FF
Battery OK (H) LQI = 255 (L)
xxx13
Reserve
0x0000
xxx14
Reserve
0x0000
xxx15
Reserve
0x0000