Assembly instructions | LK Heater 350

Installation of more than two heating circuits

In cases where more than two heating circuits are to 

be connected, the LK Heater 350 can be screwed to-

gether with the LK Mini Manifold. 

Note, however, that the maximum floor heating 

surface for the LK Heater is 12 m

2

. The floor hea-

ting circuits that are not being supplied by the 

heater are turned off via the inflow valves on the  

LK Mini Manifold. For more information on perfor-

mance please contact LK Technical Support. 

Troubleshooting

The floor is not warm.

• Start the control unit by pressing the 

Turn-on 

button and setting the water temperature.

• Check that there is current, the red light on the 

Turn-on

 button should be constantly lit. 

• If the red light next to 

Turn-on

 button flashes, 

this may indicate a defective electric cartridge 

or a triggered overheating protection. Triggered 

overheating protection is restored by removing 

the current to the control box for at least 10 sec. 

Note that the reason for failure should always 

be investigated before restarting the system. 

• Check that the pump is on. 
• Check that the minishunt return valve is open 

and in the case of an inflow divider that its 

circuit valves are open. 

• Increase the temperature until the floor heating 

temperature feels comfortable. 

Note! To cut power to the control unit the 

cable must be unplugged.

Technical data

Article no. 241 91 18

LK Heater 1-12

Article no. 241 91 19

LK Heater 1-16

Article no. 241 91 20

LK Heater 2-12

Article no. 241 91 21

LK Heater 2-16

Power controller

360W (of which electric cartridge 350W)

Voltage

230 V AC

Frequency

50 Hz

Temperature setup

22-35 ºC

Frost protection setting

10 ºC

Temperature sensor

NTC

Enclosure class control unit 

IP 44

Enclosure class cartridge

IP 54 

Max. operating pressure

0,20 MPa

Opening pressure Safety valve 0,25 MPa

Operation

The system should be filled and deaerated, see 

related instructions for the LK Minishunt. The 

pump should be deployed.

Note! The pump should always be on to en-

sure the cooling of electric cartridge which 

could otherwise become overheated.

 

Note! Ensure that the bleeding is done and 

that the manifold with an electric cartridge 

is mounted horizontally. Otherwise, electric 

cartridge may become overheated.

Connect the control unit’s power cable to a groun-

ded outlet (in the case of a blackout, the set tem-

perature is stored in the controller’s memory). Set 

the desired water temperature. Turn down the 

minishunt thermostat to the bottom so that the 

valve closes ”properly” in relation to the rest of 

the heating system. 

Note! The Control Unit´s power cable shall 

be connected to a grounded socket power 

outlet.