Assembly instructions | LK Electric Boiler - 4,5

Troubleshooting

Intervention in the boiler which requires the use of tools should be carried out by an authorized electrician. 

Begin all troubleshooting tasks by looking at the status indicators, see the 

Control panel

 section.

Error

Possible cause

Measures

On/off indication 

is off, there is no 

heat in the heating 

system.

The electric boiler is currentless.

Check the fuses.

Circuits switched off.

Check that the main and control switches are on.

The electric boiler is blocked externally.

Check if the boiler is blocked by external switching/room ther-

mostat.

Alarm light is on.

Overheating (maximum safe temperature) 

protection is triggered.

If the overheating (maximum safe temperature) protection goes 

off, the function should be controlled at the circulation pump and 

valves. During resetting the button on the overheating (maxi-

mum safe temperature) protection is pushed in when the boiler 

temperature falls below 65°C (push the button hard for reset).

No or insufficient 

heat.

Thermostatic valves on the heating system or 

boiler thermostat set at too low temperature.

Inspect and adjust.

Faulty adjustment of bypass valve.

Inspect and adjust.

Group fuses for 

boiler are triggered.

The electric cartridge is broken.

Inspect the electric cartridge by testing it in isolation. Measure 

between the outward side on the contacts, and earth. 

Inform the installer!

Intervention in the boiler, which requires the use of tools, must only be carried out under the supervision 

of an authorized installer!

Drawings

9

14

10

6

5

7

1

11

8

12

3

2

4

2

13

1.  Cable bushes 
2.  Automatic bleeding valve 
3.  Expansion vessel 
4.  Sensor clip, thermometer bulb 
5.  Boiler vessel of stainless 

steel with electric cartridge, 

insulated 

6.  Circulation pump 
7.  Electric-shock protection over 

electric cartridge cable con-

nections 

8.  Bypass with shut-off valves 
9.  Flow pipe, ¾” male thread 
10.  Return connection, ¾” male 

thread 

11.  Collection vessel, waster 

water from safety valve 

12.  Safety valve 
13.  Electric-shock protection 
14.  Knockouts for cables, where 

these come from the wall

Summary of Contents for Electric Boiler-4.5

Page 1: ...wall mounted elec tric boiler intended primarily for low temperature heating systems e g under floor heating LK Electric Boiler 4 5 kW is delivered as a complete unit The boiler is ready for use once the water and electricity are connected The boiler includes Thermostat Overheating maximum safe temperature protection Indication power on and triggered overhea ting maximum safe temperature protectio...

Page 2: ...stment valve should be open by at least half a revolution 1 2 1 Isolation valve supply and return 2 By pass valve accessible after the protective plug has been unscrewed Installation system outline Below is a system outline Units should always be installed according to regulations and standards 4 1 2 3 1 LK Electric Boiler 4 5 2 Filling valve Drain valve 3 Manifolds under floor heating 4 Under flo...

Page 3: ...de any one of 10 curves can be selected by turning the button When the button has been released for 10 sec the pump returns to operat ing mode the LEDs stop flashing and the selected curve becomes active A lit red LED indicates an alarm or warning Indication Fault Status Measure Red fourth yellow Motor blocked Pump tries to restart at 1 5 sec intervals Release motor impeller or wait Red third yel ...

Page 4: ...ied out under the supervision of an authorized installer Electric installation Electric installation should be carried out in accor dance with the applicable regulations under the supervision of an authorized electrician The boiler must not be connected to the electrical supply before it is filled with water The boiler should be preceded by all pole circuit switches The ambient temperature must no...

Page 5: ...capacitor 5 Circulation pump 6 Overheating maximum safe temperature protection 7 Thermostat 8 Electric cartridge 9 Control switches 10 Alarm indication overheating maximum safe temperature protection triggered 11 On off indicating light goes on when vol tage is supplied to the boiler 12 Contacts External switching room thermostat The boiler can be blocked by external equipment e g room thermostat ...

Page 6: ...perature protection triggered Inspect together with installer after the instal lation that the unit is in a satisfactory condition Have the installer demonstrate how the unit works and should be handled The boiler and the heating system must be filled with water before the circuit switch is set to on The boiler cover should be assembled during ope ration Note Monitor the amount of water in the ves...

Page 7: ...ox 35 40 C and for wooden joists approx 40 45 C The desired temperature varies according to the time of year Safety valve The safety valve should be exercised regularly to maintain the safety function Overheating maximum safe temperature protection The overheating maximum safe temperature pro tection on the boiler is triggered when the boiler temperature exceeds 80 The protection is restored on th...

Page 8: ... the boiler temperature falls below 65 C push the button hard for reset No or insufficient heat Thermostatic valves on the heating system or boiler thermostat set at too low temperature Inspect and adjust Faulty adjustment of bypass valve Inspect and adjust Group fuses for boiler are triggered The electric cartridge is broken Inspect the electric cartridge by testing it in isolation Measure betwee...

Page 9: ...iler no Cogeneration space heater no Combination heater no Rated heat output Prated 5 kW Useful heat output at rated heat output P4 4 5 kW Energy class D Seasonal space heating energy efficiency boiler boiler with UTK ηs ηs 36 38 Useful efficiency η4 39 7 Auxiliary electricity consumption in stand by mode PSB 0 019 kW Standby heat loss Pstby 0 037 kW Material recycling After dismantling the boiler...

Reviews: