Littelfuse Startco SE-330HV Manual Download Page 8

 

 

Page 4 

 

SE-330HV Neutral-Grounding-Resistor Monitor

 

Rev. 5-M-101817 

 
 

 

2.1.4.5  F

REQUENCY

 

(S6)

 

  Set switch S6 to 50 or 60 Hz to tune the digital filter to 
the line frequency of the monitored system. 
 

2.1.4.6  U

PGRADE

 M

ODE

 

(S8)

 

  The  microSD™  card  is  used  for  firmware  upgrades.  
See Section 4.1.2 for upgrade instructions. 
 

N

OTE

:  An  upgrade  causes  an  SE-330HV  restart  and  this 

may cycle the output relays.   
 

2.1.5  R

ESISTOR-

F

AULT 

T

RIP 

T

IME

 

  The  resistor-fault  trip  time  can  be  adjusted  from  12 
(default) to 60 seconds using the SE-MON330 software or 
via network communications. 
 

2.1.6  R

ESISTOR-

F

AULT 

T

RIP 

L

EVEL

 

  The  resistor-fault  trip  level  can  be  adjusted  using  the 
SE-MON330  software  or  via  network  communications.  
See Section 6.1. 

 
2.1.7  G

EO-

M

AGNETIC 

F

ILTER

 

  A  low-frequency  ground  current  can  be  caused  by  the 
Earth’s  magnetic  field  and  from  charged  clouds  passing 
overhead during a thunderstorm.  In some rare conditions, 
this can cause a false resistor-fault trip.  Enabling the geo-
magnetic  filter  and  increasing  the  resistor-fault  trip  time 
can help counteract these effects. 
  A  trip  time  of  30  seconds  is  recommended  when  the 
geo-magnetic filter is enabled. 
  The  geo-magnetic  filter  is  disabled  by  default,  but  can 
be enabled using the SE-MON330 software or via network 
communications. 

 
2.2  C

ALIBRATION

 

  The  SE-330HV  measures  the  resistance  change  of  the 
NGR  relative  to  the  NGR-resistance  value  determined  at 
the  time  of  calibration.    When  the  resistance  change  is 
greater  than  a  threshold  amount  (2,500 

  for  100-k

 

systems, 5,000 

 for 200-k

 systems), a resistor-fault trip 

occurs.    Calibrate  the  SE-330HV  on  new  installations,  if 
the NGR is changed, or if the sensing resistor is changed. 
 

N

OTE

:

  If the SE-330HV is not calibrated and is supplied 

from  the  load  side  of  the  breaker  (non-fail-safe  mode), 
calibrate  within  the  resistor-fault  trip  time  after  power-up 
or it may trip and interrupt its supply.  See Section 2.1.5. 
 
  The  CALIBRATION  button  is  located  behind  the 
access  cover  on  the  front  panel,  and  it  is  recessed  to 
prevent inadvertent activation. 
 

N

OTE

:

    Calibration  must  be  performed  with  the  

SE-330HV  connected  to  the  sensing  resistor  and  NGR  of 
the installed system. 
 

  To calibrate, press and hold the CALIBRATION button 
until the green CALIBRATED LED turns off and returns 
to on  (if the LED is already off, press and hold until the 
LED  turns  on).    Calibration  takes  approximately  two 
seconds.    If  calibration  is  not  successful,  a  resistor-fault 
trip occurs, the RESISTOR FAULT TRIP LED will be on, 
the  CALIBRATED  LED  will  be  off,  and  the 
DIAGNOSTIC  LED  will  flash  the  calibration-error  code.  
See Section 2.7. 
  The  SE-330HV  may  be  calibrated  remotely  using  
the  SE-MON330  software  with  the  USB  interface  or  the 
communications options. 
  If  latching  resistor  fault  (switch  S4)  is  selected,  the 
calibration-error code flashes until RESET is pressed even 
if the CALIBRATED LED is on. 
  The calibration value is stored in non-volatile memory. 
 

2.3  T

RIP

 I

NDICATION

 

AND

 R

ESET

 

  Red LED's and indication relays indicate ground-fault and 
resistor-fault  trips.    The  indication  relays  K2  (GF)  and  K3 
(RF) operate in fail-safe or non-fail-safe mode.  The default 
is non-fail-safe mode.  In this mode, the relays are energized 
when a fault occurs.  The relay mode setting is stored in non-
volatile 

memory 

and 

can 

be 

set 

using 

the  

SE-MON330 software or network communications. 
  When  a  trip  occurs  with  latching  operation  selected,  the 
SE-330HV  remains  tripped  until  reset  with  the  front  panel 
button  or  the  remote-reset  input.    See  Sections  2.1.4.3  and 
2.1.4.4.  Terminals 15 and 16 are provided for remote reset 
as  shown  in  Fig. 3.    The  reset  circuit  responds  only  to  a 
momentary closure so that a jammed or shorted button does 
not  prevent  a  trip.    The  front-panel  RESET  button  is 
inoperative when terminal 15 is connected to terminal 16.  If 
non-latching  operation  is  selected,  trips  and  corresponding 
indication  automatically  reset  when  the  fault  clears  and 
power-up trip memory is defeated even when configuration 
switch S2 is set to fail-safe.  The maximum automatic reset 
time is 2.8 s. 
  The  red  DIAGNOSTIC  LED  annunciates  latched 
calibration-error and remote trips.  See Section 2.7. 
  When  supply  voltage  is  applied  with  switch  S2  set  to 
FAIL-SAFE,  the  SE-330HV  returns  to  its  state  prior  to 
loss  of  supply  voltage.    When  supply  voltage  is  applied 
with switch S2 set to NON-FAIL-SAFE, SE-330HV trips 
are reset.  When a local, remote, or network reset is issued, 
both trip LED's will flash if they are off. 
  Resistor-fault-trip  reset  can  take  up  to  one  second.  
Resistor-fault trip-memory can take up to three seconds after 
SE-330HV power up. 
 

2.4  R

EMOTE 

O

PERATION

 

  Relays  K2  and  K3  can  be  used  for  remote  indication, 
and  terminals  15  and  16  are  provided  for  remote  reset.  
RK-332  Remote  Indication  and  Reset  components  are 
shown in Fig. 18.  Connect them as shown in Fig. 3.  RK-
332 components are not polarity sensitive. 
  Indication relays can be set to fail-safe or non-fail-safe 
operation  using  the  SE-MON330  software  or  network 

Summary of Contents for SE-330HV

Page 1: ...l techline littelfuse com www littelfuse com SE 330HV SE 330HV MANUAL NEUTRAL GROUNDING RESISTOR MONITOR REVISION 5 M 101817 Copyright 2017 Littelfuse Startco All rights reserved Document Number PM 12...

Page 2: ...Page i SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 This page intentionally left blank...

Page 3: ...libration and Open Test 32 9 1 2 Voltage Test 32 9 2 Sensing Resistor Test 32 9 3 Analog Output Test 32 9 4 Ground Fault Performance Test 33 Appendix A SE 330HV Revision History 34 LIST OF FIGURES FIG...

Page 4: ...Page iii SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 This page intentionally left blank...

Page 5: ...nt can cause a ground fault voltage larger than expected A parallel transformer winding makes it difficult to monitor NGR continuity A transformer can provide the inductance necessary to cause ferrore...

Page 6: ...ernet ports are available with support for fiber optic and RJ45 interfaces The IEC 61850 protocol has been added TABLE 1 TYPICAL VALUES FOR TRIPPING SYSTEMS SYSTEM VOLTAGE LINE LINE NEUTRAL GROUNDING...

Page 7: ...VEL setting for an interval greater than the GF TRIP TIME setting the ground fault circuit will also trip The VN TRIP LEVEL range is 100 to 10 000 V with switch S5 in the 100 kW Vx1 position and the r...

Page 8: ...bration is not successful a resistor fault trip occurs the RESISTOR FAULT TRIP LED will be on the CALIBRATED LED will be off and the DIAGNOSTIC LED will flash the calibration error code See Section 2...

Page 9: ...dication The number of short LED pulses between pauses indicates the cause of the trip By default both critical and non critical diagnostic flash codes are shown Non critical diagnostic codes include...

Page 10: ...and ER 72KV sensing resistors are shown in Figs 8 9 10 11 and 12 Install the NGR and the sensing resistor near the transformer or generator When installed outdoors a sensing resistor must be installed...

Page 11: ...Page 7 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 3 SE 330HV Connection Diagram...

Page 12: ...Page 8 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 4 SE 330HV Outline and Panel Mounting Details...

Page 13: ...Page 9 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 5 SE 330HV Outline and Surface Mounting Details...

Page 14: ...Page 10 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 6 SE IP65CVR G Weatherproof Cover Outline...

Page 15: ...Page 11 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 7 SE IP65CVR G Weatherproof Cover Installation...

Page 16: ...Page 12 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 8 ER 15KV Sensing Resistor...

Page 17: ...Page 13 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 9 ER 25KV Sensing Resistor...

Page 18: ...Page 14 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 10 ER 35KV Sensing Resistor...

Page 19: ...Page 15 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 11 ER 72KV Sensing Resistor Outline...

Page 20: ...Page 16 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 12 ER 72KV Sensing Resistor Mounting Details...

Page 21: ...Page 17 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 13 ER 1000HV Sensing Resistor...

Page 22: ...s of protection will result if the ground fault CT monitors the NGR connection to ground rather than its connection to neutral A minimal loss of protection will also result if the sensing resistor to...

Page 23: ...Page 19 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 15 EFCT 1 Ground Fault Current Sensor...

Page 24: ...Page 20 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 16 SE CS30 70 Ground Fault Current Sensor...

Page 25: ...Page 21 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 17 EFCT 26 and SE CS30 26 Ground Fault Current Sensors...

Page 26: ...Page 22 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 FIGURE 18 RK 332 Remote Indication and Reset FIGURE 19 PGA 0520 Analog Percent Current Meter...

Page 27: ...tion ground and precautions must be taken with the power supply and the trip contacts See Technical Note RG 1 NGR Monitoring with Isolated Ground Beds at www littelfuse com relayscontrols An alternate...

Page 28: ...firmware upgrade process The red DIAGNOSTIC LED blinks rapidly while the firmware upgrade is running and the SE 330HV may reset multiple times during the upgrade process Do not remove the SD card or p...

Page 29: ...p SD Card DIAGNOSTIC LED flash code 1 L 5 S 1 L SD Card is full or a write error occurred Delete files or use a different microSD card Non critical diagnostic code GF LED 2 No Change RF LED 2 No Chang...

Page 30: ...ostic code GF LED 2 No Change RF LED 2 No Change K1 No Change DIAGNOSTIC LED Solid Red SE 330HV processor failed to start Cycle supply If problem persists consult Littelfuse Startco K1 De energized Pr...

Page 31: ...y Rating or 2 to 100 using MEM parameter Trip Time 0 1 0 2 0 3 0 4 0 5 0 7 1 0 2 0 3 0 5 0 10 0 s Trip Level Accuracy Maximum of 1 of CT Primary Rating or 3 of Setting 2 Trip Time Accuracy 10 of Setti...

Page 32: ...ing Temperature Standard Grade Included 25 to 85 C 13 to 140 F Industrial Grade 40 to 85 C 40 to 140 F PWB Conformal Coating MIL 1 46058 qualified UL QMJU2 recognized Mounting Configurations Panel Mou...

Page 33: ...ccuracy included for EFCT x and SE CS30 x current sensors only 3 microSD and microSDHC are trademarks of SD 3C LLC 4 Remote reset wiring is limited to 10 m 32 5 This value can only be modified using S...

Page 34: ...Trip Level Accuracy 1 A 1 of CT Primary Rating 1 A 3 of CT Primary Rating EFCT 26 Current Ratio 5 0 05 A Insulation 600 V Class Window Diameter 26 mm 1 0 Shipping Weight 0 45 kg 1 0 lb Certifications...

Page 35: ...window SE CS30 70 Current Sensor 30 A primary rating 70 mm 2 7 window CT200 Current Sensor 200 A primary rating 56 mm 2 2 window 5SHT 101 E Current Sensor 100 A primary rating 40 mm 1 6 window 5SHT 1...

Page 36: ...econd 9 1 2 VOLTAGE TEST Test Equipment 0 to 250 Vac voltage source multimeter and ER sensing resistor NOTE Use an isolation transformer if the test voltage source does not provide dc continuity for t...

Page 37: ...ate ground paths do not exist that bypass the current sensor High voltage testers and resistance bridges can be used to determine the existence of alternate ground paths d Verify proper reaction of th...

Page 38: ...D 041414 13 2 20 January 9 2014 5 C 010914 12 11 November 29 2013 5 B 112913 10A 2 10 October 8 2013 5 A 100813 10A 2 08 MANUAL REVISION HISTORY REVISION 5 M 101817 SECTION 2 New features described i...

Page 39: ...ded CE C Tick and FCC information REVISION 5 D 041414 APPENDIX A Hardware revision updated REVISION 5 C 010914 SECTION 6 Extended operating temperatures added to the ER 15KV ER 25KV and ER 35KV sensin...

Page 40: ...oSD interfaces programmable trip level MEM feature and ability to add future options Real time clock added Added dual cable and fiber Ethernet ports Update to RTC circuit FIRMWARE REVISION HISTORY FIR...

Page 41: ...FIRMWARE REVISION 2 20 Added support for EtherNet IP protocol IED name now reported correctly through IEC 61850 interface EtherNet IP and Modbus communications card LED status updated Hardware versio...

Page 42: ...Page 38 SE 330HV Neutral Grounding Resistor Monitor Rev 5 M 101817 This page intentionally left blank...

Page 43: ...ronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information Littelfuse 5SHT 101 E 7SHT 401 E ER 1000HV 5SHT 500 E 7SHT 601 E 5SHT 151 E 7SHT 301 E 8SHT 151 E 8SHT 601...

Reviews: