Page 26
SE-330HV Neutral-Grounding-Resistor Monitor
Rev. 5-M-101817
NOTES:
(1)
L = long pause, S = short flash.
(2)
When LED is on, corresponding indication relay is energized when in the non-fail-safe mode or de-energized when in the
fail-safe mode.
P
ROBLEM
D
IAGNOSTIC
LED
F
LASH
C
ODE
(1)
S
OLUTION
USB Error
Diagnostic LED Flash Code
1 L – 10 S – 1 L
A USB algorithm timeout has been detected. Remove and reconnect
the USB cable and cycle supply voltage. If the problem persists
contact Littelfuse Startco.
Non-critical diagnostic code.
GF LED
(2)
: No Change, RF LED
(2)
: No Change, K1:No Change
DIAGNOSTIC LED = Solid Red
SE-330HV processor failed to start. Cycle supply. If problem
persists, consult Littelfuse Startco. K1: De-energized.
Pressing RESET does not clear trips.
Trip condition is still present. Locate and correct.
The RESET button is disabled if remote-reset terminals 15 and 16
are connected. Replace shorted remote-reset switch or issue Reset
command from the communications network.
UNIT HEALTHY relay K4 momentarily
changes state.
Occurs when processor is reset.
No analog-output current.
The output at terminals 19 and 20 requires a voltage source. See
Fig. 2 for analog-output connections. See Section 9.3 for the
analog-output tests.