![Littelfuse Startco SE-330HV Manual Download Page 32](http://html1.mh-extra.com/html/littelfuse-startco/se-330hv/se-330hv_manual_1928668032.webp)
Page 28
SE-330HV Neutral-Grounding-Resistor Monitor
Rev. 5-M-101817
Subject to maximums of 8 A at 250 Vac, 8 A resistive
at 30 Vdc, and 0.4 A resistive at 150 Vdc.
Unit Healthy Output K4 (Option 0):
Configuration ........................ N.O. (Form A)
Operating Mode .................... Closed when Healthy
Ratings ................................... 100 mA, 250 V (ac or dc)
Closed Resistance ................. 30 to 50
W
Unit Healthy Output K4 (Option 1):
Configuration ........................ N.C. (Form B)
Operating Mode .................... Open when Healthy
Ratings ................................... 100 mA, 250 V (ac or dc)
Closed Resistance ................. 25 to 50
W
maximum
Auto-reset time ............................ 2.8 s maximum
4-20-mA Analog Output:
Type ....................................... Self Powered and
Loop Powered
Range ..................................... 4 to 22 mA
Loop Voltage ......................... 8 to 36 Vdc
Load ....................................... 500
W
(maximum with
24-Vdc supply)
Isolation ................................. 120 Vac
Parameter ............................... NGR Current, 20 mA =
CT Primary Current
USB Communications:
Baud Rate .............................. 12 Mbit/s
Protocol .................................. USB Device
Connector .............................. Mini B
SD Memory Card:
Type ....................................... Standard Grade
Form Factor ........................... microSD™
(3)
and
microSDHC™
(3)
Format .................................... FAT32
Capacity:
SE-330HV Hardware
Revision 16 and higher ...... 512 MB to 32 GB
SE-330HV Hardware
Revision 15 and lower ....... 512 MB to 4 GB
Operating Temperature:
Standard Grade
(Included) ........................... -25 to 85°C (-13 to 140°F)
Industrial Grade .................. -40 to 85°C (-40 to 140°F)
PWB Conformal Coating ............ MIL-1-46058 qualified,
UL QMJU2 recognized
Mounting Configurations ............ Panel Mount and Optional
Surface Mount
Dimensions:
Height .................................... 213 mm (8.4”)
Width ..................................... 99 mm (3.9”)
Depth ..................................... 132 mm (5.2”)
Shipping Weight ......................... 2.0 kg (4.4 lb)
Environment:
Operating Temperature ......... -40 to 60°C (-40 to 140°F)
Storage Temperature ............. -55 to 80°C (-67 to 176°F)
Humidity ................................ 85% Non-Condensing
IP Rating ................................ IP30
Surge Withstand .......................... ANSI/IEEE C37.90.1-1989
(Oscillatory and Fast
Transient)
EMC Tests:
Verification tested in accordance with IEC 60255-26:2013.
Radiated and Conducted
Emissions ............................
CISPR 11:2009,
CISPR 22:2008,
EN 55022:2010
Class A
Current Harmonics and
Voltage Fluctuations ........... IEC 61000-3-2
and IEC 61000-3-3
Class A
Electrostatic Discharge ........ IEC 61000-4-2
± 6 kV contact discharge
(direct and indirect)
± 8 kV air discharge
Radiated RF Immunity ........ IEC 61000-4-3
10 V/m, 80-1,000 MHz,
80% AM (1 kHz)
10 V/m, 1.0 to 2.7 GHz,
80% AM (1 kHz)
Fast Transient ...................... IEC 61000-4-4
Zone B
± 2 kV (power supply
port), ± 1 kV (all other
ports)
Surge Immunity ................... IEC 61000-4-5
Zone B
± 1 kV differential mode
± 2 kV common mode
Conducted RF Immunity ..... IEC 61000-4-6
10 V, 0.15-80 MHz,
80% AM (1 kHz)