Littelfuse Startco SE-325 Manual Download Page 7

 

Startco Engineering Ltd.  

Page 3 

 

SE-325 Neutral-Grounding-Resistor Monitor 

Rev. 9 

 
 

Pub. SE-325-M, May 6, 2008. 

3.  I

NSTALLATION

 

3.1  SE-325

 

  SE-325 outline and mounting details are shown in 
Fig. 2.  Typical connections are shown in Fig. 1.  Connect 
supply voltage to L1 and L2.  For a 120-Vac supply, 
connect supply neutral to L2.  For a direct-current supply, 
connect supply negative to L2.  Connect chassis-bonding 
terminal 

 

to ground. 

  Connect contact terminals A and B as required. 

 
 
  Face-plate LED's are driven in series with remote-
indication LED's.  When remote-indication LED’s are not 
used, terminals GI, +, and RI must be connected for the 
face-plate LED’s to operate.  These jumpers are installed 
at the factory. 
  Install the upper terminal-block cover to prevent 
inadvertent contact with line terminals. 
 

N

R

G

ER-600VC

SENSING RESISTOR

20 K

600 VAC MAX

W

STARTCO

E N G I N E E R I N G L T D .

MADE IN SASKATOON, CANADA

600 V

4160 V

SUPPLY

NEUTRAL
GROUNDING
RESISTOR

CT200

GROUND-FAULT CT

UV

120 VAC

L

N

LOAD

RESISTOR-FAULT
INDICATOR

GROUND-FAULT
INDICATOR

RESET SWITCH

REMOTE INDICATION AND RESET

RED

RED

F 1

R E S E T

P O W E R

G R O U N D

F A U L T

GF TRIP

TIME (s)

R E S I STO R

F A U L T

RES TRIP

LEVEL (VAC)

CT1 CT2 A

B

R I

G I

S W

L 1

R

L 2

G

STARTCO

E N G I N E E R I N G L T D .

NGR MONITOR

SE-325

MODE R E S

G F

2 0

4 0 0

2 0 0

0 . 1

2 . 0

1 . 0

4.0 A

2.0 A

0.5 A

S H

U V 2 0 K

R I

G I

S W

R

G

STARTCO

E N G I N E E R I N G L T D .

NGR MONITOR

SE-325

ER

R
S
1

R
S
2

C
G
I

G
R
I

+

S
W

K1

K2

SW

CI/GI

+

GI/RI

TB1

RESISTOR-FAULT
INDICATOR

GROUND-FAULT
INDICATOR

RESET SWITCH

RED

RED

RK-13 CONNECTION WITH REMOTE INDICATION AND RESET

ALTERNATE
RESET CIRCUIT

24-120 Vac/Vdc

RK-13 CONNECTION WITHOUT REMOTE INDICATION OR RESET

K1

K2

RI

+

GI

SW

R I

G I

S W

R

G

STARTCO

E N G I N E E R I N G L T D .

NGR MONITOR

SE-325

RI

GI

SW

ER

R
S
1

R
S
2

C
G
I

G
R
I

+

S
W

K1

K2

SW

CI/GI

+

GI/RI

TB1

K1

K2

R I

G I

S W

R

G

STARTCO

E N G I N E E R I N G L T D .

NGR MONITOR

SE-325

ER

NOTES:

1. ALTERNATE SENSING-RESISTOR TERMINAL-N CONNECTION,

THE NEUTRAL CONNECTION IS NOT MONITORED.

2. K1 CLOSES ON GROUND-FAULT TRIP.

3. K2 CLOSES ON RESISTOR-FAULT TRIP.

4. VOLTAGE BETWEEN ER TERMINALS R AND G

LIMITED TO 100 V BY INTERNAL CLAMP.

CAUTION: DO NOT USE K1 OR K2 IN A TRIP CIRCUIT.

NOTE 1

NOTES 2 & 3

NOTE 4

FIGURE 1.  Typical Application. 

Summary of Contents for SE-325

Page 1: ...s RESI STOR FAULT RES TRIP LEVEL VAC CT1 CT2 A B RI GI SW L1 R L2 G STARTCO E N G I N E E R I N G L T D NGR MONITOR SE 325 MODE RES GF 20 400 200 0 1 2 0 1 0 4 0 A 2 0 A 0 5 A SH UV 20K Copyright 200...

Page 2: ...This page intentionally left blank...

Page 3: ...ty 14 7 Test Procedures 15 7 1 Ground Fault Performance Test 15 7 2 Resistor Fault Tests 16 7 2 1 Open Test 16 7 2 2 Voltage Test 16 7 3 Sensing Resistor Test 16 LIST OF FIGURES FIGURE PAGE 1 Typical...

Page 4: ...Startco Engineering Ltd Page ii SE 325 Neutral Grounding Resistor Monitor Rev 0 Pub SE 325 M May 6 2008 This page intentionally left blank...

Page 5: ...otection inoperative Transformer inrush current up to twelve times rated current can cause a ground fault voltage larger than expected A parallel transformer winding makes it difficult to monitor NGR...

Page 6: ...lue of the ground fault circuit Typical values for 5 15 and 25 A tripping systems are shown in Table 1 For others systems refer to the NGR Monitor Set Point Assistant at www startco ca 2 2 INDICATION...

Page 7: ...GROUND FAULT INDICATOR RESET SWITCH REMOTE INDICATION AND RESET RED RED F1 RESET POWER GROUND FAULT GF TRIP TIME s RESI STOR FAULT RES TRIP LEVEL VAC CT1 CT2 A B RI GI SW L1 R L2 G STARTCO E N G I N...

Page 8: ...AL BLOCK COVER REMOVED MINIMUM CLEARANCE FOR FUSE REMOVAL 109 0 4 29 3 50 5 50 5 90 88 9 139 7 150 0 4 8 0 19 DIA 100 0 3 93 3 06 77 8 F1 RESET POWER GROUND FAULT GF TRIP TIME s RESI STOR FAULT RES TR...

Page 9: ...nection to the SE 325 is not polarity sensitive Ground one side of the CT secondary For electrically noisy environments or lead lengths in excess of 10 m 30 ft use shielded twisted pair cable D A E B...

Page 10: ...resistor connection is not a neutral conductor as defined in Canadian Electrical Code Section 10 1108 and National Electrical Code Section 250 36 B It is not required to be 8 AWG or larger Since curre...

Page 11: ...ON MAY BE REMOVED FOR DIELECTRIC STRENGTH TESTING ENSURE THAT THE JUMPER IS INSTALLED AFTER TESTING ON REV 0 1 UNITS SCREW IS NOT PRESENT AND BASE IS ELECTRICALLY CONNECTED TO TERMINAL G 316 0 G R 188...

Page 12: ...0 0 90 0 5 67 8 46 3 53 11 00 3 94 3 53 FRONT MOUNTING DETAIL SIDE NOTES TOP 444 0 17 50 14 37 1 56 1 56 365 0 39 5 39 5 MINIMUM DISTANCE TO ADJACENT OBJECTS NOTE 3 1 DIMENSIONS IN MILLIMETRES INCHES...

Page 13: ...ENTRY NOTE 3 MINIMUM DISTANCE TO ADJACENT OBJECTS 320 12 6 FRONT SIDE N STARTCO E N G I N E E R I N G L T D MADE IN SASKATOON CANADA VOLTAGE AT TERMINAL N RISES TO LINE TO NEUTRAL VOLTAGE WHEN A GROUN...

Page 14: ...IGHTS 36 6 1 44 17 3 0 68 29 9 1 17 43 5 1 71 PUSH BUTTON 36 6 1 44 14 9 0 59 29 9 1 17 43 5 1 71 FIGURE 8 RK 302 Remote Indication and Reset NOTES 1 DIMENSIONS IN MILLIMETRES INCHES 2 NEMA 1 FRONT VI...

Page 15: ...2 5 I 3 0 0 1 1 8 25 0 0 98 CI RI GI OUTLINE NOTES 1 DIMENSIONS IN MILLIMETRES INCHES 2 NEMA 1 FIGURE 10 RK 325I Remote Indication Assembly 60 2 31 0 47 5 21 0 2 37 1 22 1 87 0 83 R S 1 R S 2 C G I G...

Page 16: ...he RK 302 RK 325 and RK 325I See Figs 1 and 11 Contact K1 closes when the Ground Fault LED is on and contact K2 closes when the Resistor Fault LED is on 3 7 GROUND FAULT TESTING Use CT primary current...

Page 17: ...004 Operating Mode UV Fail Safe or SH Non Fail Safe Remote Indication 12 Vdc GI RI Current Sink 560 Internal Optional RK 13 Module Contact Ratings 100 mA 120 Vac Contact Configuration N O Form A Reset...

Page 18: ...ation and Reset Assembly RK 325I Indication Assembly RK 13 Relay Interface Module 6 WARRANTY The SE 325 Neutral Grounding Resistor Monitor is warranted to be free from defects in material and workmans...

Page 19: ...bridges can be used to determine the existence of alternate ground paths d Verify proper reaction of the circuit interrupting device in response to a simulated or controlled ground fault current To si...

Page 20: ...LED should be off 7 2 2 VOLTAGE TEST Test Equipment 0 to 120 Vac voltage source and multimeter NOTE Applying the test voltage to the R and G terminals will damage the SE 325 and the ER sensing resist...

Reviews: