Littelfuse Startco SE-325 Manual Download Page 17

 

Startco Engineering Ltd. 

Page 13 

 

SE-325 Neutral-Grounding-Resistor Monitor

 

Rev. 1 

 
 

Pub. SE-325-M, May 6, 2008. 

Resistor-Fault Circuit: 

 Neutral-To-Ground 

  Trip Voltage (V

N

) .................20 to 2,000 Vac Adjustable 

  NGR Trip Resistance, V

= 0 

   

ER-600VC or ER-5KV

.....2 k

Ω

 

   

ER-15KV or ER-25KV

....6 k

Ω

    

50 

k

Ω

 with Option S 

 Neutral-To-Ground 

 DC-Voltage 

Rejection: 

    ER-600VC or ER-5KV ..1.2 V 

    ER-15KV or ER-25KV ..0.7 V, 4 V with Option S 

  Trip-Resistance Accuracy ....+5, -2% of Sensing  

  

 

Resistor 

Resistance 

  Trip Time ..............................5 ± 0.5 s, 

   

 

20 ± 3 s with Option S 

 Operating 

Mode....................Latching, 

  

Non-latching 

with 

  

Option 

 
Output Relay: 
  CSA/ULContact Rating........1 mA to 4 A Resistive, 
   

 

240 Vac or 28 Vdc 

  Supplemental Contact Ratings: 
    Make/carry 0.2 s..............10 A 
    Carry continuous.............4 A 
   Break: 
   

dc................................20 W resistive, 

   

 

10 W inductive 

   

 

(L/R = 0.04 s) 

   

ac................................960 VA resistive, 

   

 

700 VA inductive 

   

 

(PF = 0.4) 

    Subject to maximums of 4 A and 240 V (ac or dc) 
  Contact Configuration ..........N.O. (Form A) 
  Fuse Rating (F1) ...................4.0 A, 250 Vac, 
  

 

Time 

Delay 

  Fuse Part Number .................Bussman MSL-4 or 
  

 

Littelfuse 

313.004 

  Operating Mode ...................UV (Fail-Safe) or 
  

 

SH 

(Non-Fail-Safe) 

 
Remote Indication: 
 +.............................................12 

Vdc 

 GI/RI .....................................Current 

Sink, 

  

560 

Ω

 Internal 

 
Optional RK-13 Module: 

  Contact Ratings ..................100 mA, 120 Vac 

  Contact Configuration ........N.O. (Form A) 

  Reset Input .........................24 to 120 V (ac or dc), 

   

Isolated 

 
PWB Conformal Coating......... MIL-1-46058 qualified, 

UL QMJU2 recognized 

4.2  S

ENSING 

R

ESISTORS 

 

ER-600VC: 

  Maximum Voltage .......... 600 Vac 
  Maximum Current........... 30 mA 
 Resistance ....................... 20 

k

Ω

 

 Thermal: 
     420 Vac ...........................Continuous 
     600 Vac ...........................6 minutes on, 
   

60 minutes off 

  Shipping Weight ................300 g (0.7 lb) 
 
ER-5KV: 
  Maximum Voltage .......... 2,500 Vac 
  Maximum Current........... 125 mA 
 Resistance ....................... 20 

k

Ω

 

 Thermal ..............................Continuous 
  Shipping Weight ................5.0 kg (11 lbs) 
 
ER-15KV: 
  Maximum Voltage .......... 8,400 Vac 
  Maximum Current........... 84 mA 
 Resistance ....................... 100 

k

Ω

 

  Thermal ..............................1 minute on, 
   

120 minutes off 

  Shipping Weight ................5.0 kg (11 lbs) 
 
ER-25KV: 
  Maximum Voltage .......... 14,400 Vac 
  Maximum Current........... 144 mA 
 Resistance ....................... 100 

k

Ω

 

  Thermal ..............................1 minute on, 
   

120 minutes off 

  Shipping Weight ................20 kg (44 lbs) 
 

4.3  C

URRENT 

T

RANSORMER 

 

CT200: 

  Current Ratio................... 200:5 A 

 Insulation ........................ 600-V 

Class 

  Window Diameter........... 56 mm (2.2”) 

  Shipping Weight ............. 1 kg (2.2 lbs) 

 

Certification ........................ CSA, Canada and USA 

     

LR 53428

US

C

R

 

   

Australia 

 

 

 

 

   

Commonwealth 

of 

Pennsylvania 

   

 SE-325........ BOTE 

 

1767-99 

 

SE-325P...... BOTE  1797-00 

 

Summary of Contents for SE-325

Page 1: ...s RESI STOR FAULT RES TRIP LEVEL VAC CT1 CT2 A B RI GI SW L1 R L2 G STARTCO E N G I N E E R I N G L T D NGR MONITOR SE 325 MODE RES GF 20 400 200 0 1 2 0 1 0 4 0 A 2 0 A 0 5 A SH UV 20K Copyright 200...

Page 2: ...This page intentionally left blank...

Page 3: ...ty 14 7 Test Procedures 15 7 1 Ground Fault Performance Test 15 7 2 Resistor Fault Tests 16 7 2 1 Open Test 16 7 2 2 Voltage Test 16 7 3 Sensing Resistor Test 16 LIST OF FIGURES FIGURE PAGE 1 Typical...

Page 4: ...Startco Engineering Ltd Page ii SE 325 Neutral Grounding Resistor Monitor Rev 0 Pub SE 325 M May 6 2008 This page intentionally left blank...

Page 5: ...otection inoperative Transformer inrush current up to twelve times rated current can cause a ground fault voltage larger than expected A parallel transformer winding makes it difficult to monitor NGR...

Page 6: ...lue of the ground fault circuit Typical values for 5 15 and 25 A tripping systems are shown in Table 1 For others systems refer to the NGR Monitor Set Point Assistant at www startco ca 2 2 INDICATION...

Page 7: ...GROUND FAULT INDICATOR RESET SWITCH REMOTE INDICATION AND RESET RED RED F1 RESET POWER GROUND FAULT GF TRIP TIME s RESI STOR FAULT RES TRIP LEVEL VAC CT1 CT2 A B RI GI SW L1 R L2 G STARTCO E N G I N...

Page 8: ...AL BLOCK COVER REMOVED MINIMUM CLEARANCE FOR FUSE REMOVAL 109 0 4 29 3 50 5 50 5 90 88 9 139 7 150 0 4 8 0 19 DIA 100 0 3 93 3 06 77 8 F1 RESET POWER GROUND FAULT GF TRIP TIME s RESI STOR FAULT RES TR...

Page 9: ...nection to the SE 325 is not polarity sensitive Ground one side of the CT secondary For electrically noisy environments or lead lengths in excess of 10 m 30 ft use shielded twisted pair cable D A E B...

Page 10: ...resistor connection is not a neutral conductor as defined in Canadian Electrical Code Section 10 1108 and National Electrical Code Section 250 36 B It is not required to be 8 AWG or larger Since curre...

Page 11: ...ON MAY BE REMOVED FOR DIELECTRIC STRENGTH TESTING ENSURE THAT THE JUMPER IS INSTALLED AFTER TESTING ON REV 0 1 UNITS SCREW IS NOT PRESENT AND BASE IS ELECTRICALLY CONNECTED TO TERMINAL G 316 0 G R 188...

Page 12: ...0 0 90 0 5 67 8 46 3 53 11 00 3 94 3 53 FRONT MOUNTING DETAIL SIDE NOTES TOP 444 0 17 50 14 37 1 56 1 56 365 0 39 5 39 5 MINIMUM DISTANCE TO ADJACENT OBJECTS NOTE 3 1 DIMENSIONS IN MILLIMETRES INCHES...

Page 13: ...ENTRY NOTE 3 MINIMUM DISTANCE TO ADJACENT OBJECTS 320 12 6 FRONT SIDE N STARTCO E N G I N E E R I N G L T D MADE IN SASKATOON CANADA VOLTAGE AT TERMINAL N RISES TO LINE TO NEUTRAL VOLTAGE WHEN A GROUN...

Page 14: ...IGHTS 36 6 1 44 17 3 0 68 29 9 1 17 43 5 1 71 PUSH BUTTON 36 6 1 44 14 9 0 59 29 9 1 17 43 5 1 71 FIGURE 8 RK 302 Remote Indication and Reset NOTES 1 DIMENSIONS IN MILLIMETRES INCHES 2 NEMA 1 FRONT VI...

Page 15: ...2 5 I 3 0 0 1 1 8 25 0 0 98 CI RI GI OUTLINE NOTES 1 DIMENSIONS IN MILLIMETRES INCHES 2 NEMA 1 FIGURE 10 RK 325I Remote Indication Assembly 60 2 31 0 47 5 21 0 2 37 1 22 1 87 0 83 R S 1 R S 2 C G I G...

Page 16: ...he RK 302 RK 325 and RK 325I See Figs 1 and 11 Contact K1 closes when the Ground Fault LED is on and contact K2 closes when the Resistor Fault LED is on 3 7 GROUND FAULT TESTING Use CT primary current...

Page 17: ...004 Operating Mode UV Fail Safe or SH Non Fail Safe Remote Indication 12 Vdc GI RI Current Sink 560 Internal Optional RK 13 Module Contact Ratings 100 mA 120 Vac Contact Configuration N O Form A Reset...

Page 18: ...ation and Reset Assembly RK 325I Indication Assembly RK 13 Relay Interface Module 6 WARRANTY The SE 325 Neutral Grounding Resistor Monitor is warranted to be free from defects in material and workmans...

Page 19: ...bridges can be used to determine the existence of alternate ground paths d Verify proper reaction of the circuit interrupting device in response to a simulated or controlled ground fault current To si...

Page 20: ...LED should be off 7 2 2 VOLTAGE TEST Test Equipment 0 to 120 Vac voltage source and multimeter NOTE Applying the test voltage to the R and G terminals will damage the SE 325 and the ER sensing resist...