SE-325 Neutral-Grounding-Resistor Monitor 

Rev. 8 

 
 

Pub. SE-325-M, May 6, 2008. 

2.1.3  M

ODE

 

  In the shunt-trip mode (SH), the output relay energizes 
and its contact closes if a resistor-fault or ground-fault trip 
occurs.  The shunt-trip mode is not fail-safe because shunt-
trip devices do not operate if supply voltage fails. 
  In the undervoltage mode (UV), the output relay 
energizes and its contact closes if the resistor-fault and 
ground-fault circuits are not tripped.  The undervoltage 
mode is referred to as fail-safe because undervoltage devices 
release if supply voltage fails. 
 

2.1.4  RES

 

  This switch setting must correspond to the resistance of 
the external sensing resistor.  For the ER-600VC and 
ER-5KV, select 20K.  For the ER-15KV and ER-25KV, 
select 100K. 
 

2.1.5  RES T

RIP

 L

EVEL

 

  Neutral-to-ground trip voltage is adjustable from 20 to 
400 Vac with a 20-k

Ω

 sensing resistor, and 100 to 

2,000 Vac with a 100-k

Ω

 sensing resistor.  To prevent false 

resistor-fault trips, the RES TRIP LEVEL should be set 
higher than the voltage across the neutral-grounding resistor 
when neutral-to-ground current is equal to the operating 
value of the ground-fault circuit.  Typical values for 5-, 15-, 
and 25-A tripping systems are shown in Table 1.  For others 
systems, refer to the NGR Monitor Set-Point Assistant at 
www.startco.ca. 

 

2.2  I

NDICATION

 

AND

 R

ESET

 

  The green POWER LED indicates that the internal power 
supply is on.  Red LED's indicate ground-fault and resistor-
fault trips.  When a trip occurs, the SE-325 remains latched 
until the reset switch is pressed or supply voltage is cycled.  
Terminals are provided for remote indication and reset as 
shown in Fig. 1. 
  For the non-latching option, the SE-325 resets when the 
fault clears. 

 
2.3  F

USING

 

  The output contact is protected by fuse F1 (4.0 A, time 
delay). 
 

 

 
 

TABLE 1.  S

ETTINGS

 

FOR 

T

YPICAL

 S

YSTEMS 

System 

Voltage

 

Neutral-Grounding 

Resistor

 

Sensing 

Resistor

 

Ground-Fault 

Trip Level

 

ResTrip Level 

 

(Volts)

 

Let Through 

(Amperes)

 

Resistance 

(Ohms)

 

Model Resistance 

(Ohms) 

 

(Amperes)

 

 

(Volts)

 

480 
600 

2,400 
4,160 

480 
600 

2,400 
4,160 
7,200 

14,400 

7,200 

14,400 
25,000 




15 
15 
15 
15 
15 
15 
25 
25 
25 

55 
69 

277 
480 

18 
23 
92 

160 
277 
554 
166 
332 
577 

ER-600VC 
ER-600VC 
ER-5KV 
ER-5KV 
ER-600VC 
ER-600VC 
ER-5KV 
ER-5KV 
ER-15KV 
ER-15KV 
ER-15KV 
ER-15KV 
ER-25KV 

20,000 
20,000 
20,000 
20,000 
20,000 
20,000 
20,000 
20,000 

100,000 
100,000 
100,000 
100,000 
100,000 

0.5 
0.5 
0.5 
0.5 
2.0 
2.0 
2.0 
2.0 
2.0 
2.0 
4.0 
4.0 
4.0 

30 
40 

140 
240 

40 
50 

190 
320 
600 

1,100 

700 

1,400 
2,000 

 
 

Summary of Contents for SE-325

Page 1: ...s RESI STOR FAULT RES TRIP LEVEL VAC CT1 CT2 A B RI GI SW L1 R L2 G STARTCO E N G I N E E R I N G L T D NGR MONITOR SE 325 MODE RES GF 20 400 200 0 1 2 0 1 0 4 0 A 2 0 A 0 5 A SH UV 20K Copyright 200...

Page 2: ...This page intentionally left blank...

Page 3: ...ty 14 7 Test Procedures 15 7 1 Ground Fault Performance Test 15 7 2 Resistor Fault Tests 16 7 2 1 Open Test 16 7 2 2 Voltage Test 16 7 3 Sensing Resistor Test 16 LIST OF FIGURES FIGURE PAGE 1 Typical...

Page 4: ...Startco Engineering Ltd Page ii SE 325 Neutral Grounding Resistor Monitor Rev 0 Pub SE 325 M May 6 2008 This page intentionally left blank...

Page 5: ...otection inoperative Transformer inrush current up to twelve times rated current can cause a ground fault voltage larger than expected A parallel transformer winding makes it difficult to monitor NGR...

Page 6: ...lue of the ground fault circuit Typical values for 5 15 and 25 A tripping systems are shown in Table 1 For others systems refer to the NGR Monitor Set Point Assistant at www startco ca 2 2 INDICATION...

Page 7: ...GROUND FAULT INDICATOR RESET SWITCH REMOTE INDICATION AND RESET RED RED F1 RESET POWER GROUND FAULT GF TRIP TIME s RESI STOR FAULT RES TRIP LEVEL VAC CT1 CT2 A B RI GI SW L1 R L2 G STARTCO E N G I N...

Page 8: ...AL BLOCK COVER REMOVED MINIMUM CLEARANCE FOR FUSE REMOVAL 109 0 4 29 3 50 5 50 5 90 88 9 139 7 150 0 4 8 0 19 DIA 100 0 3 93 3 06 77 8 F1 RESET POWER GROUND FAULT GF TRIP TIME s RESI STOR FAULT RES TR...

Page 9: ...nection to the SE 325 is not polarity sensitive Ground one side of the CT secondary For electrically noisy environments or lead lengths in excess of 10 m 30 ft use shielded twisted pair cable D A E B...

Page 10: ...resistor connection is not a neutral conductor as defined in Canadian Electrical Code Section 10 1108 and National Electrical Code Section 250 36 B It is not required to be 8 AWG or larger Since curre...

Page 11: ...ON MAY BE REMOVED FOR DIELECTRIC STRENGTH TESTING ENSURE THAT THE JUMPER IS INSTALLED AFTER TESTING ON REV 0 1 UNITS SCREW IS NOT PRESENT AND BASE IS ELECTRICALLY CONNECTED TO TERMINAL G 316 0 G R 188...

Page 12: ...0 0 90 0 5 67 8 46 3 53 11 00 3 94 3 53 FRONT MOUNTING DETAIL SIDE NOTES TOP 444 0 17 50 14 37 1 56 1 56 365 0 39 5 39 5 MINIMUM DISTANCE TO ADJACENT OBJECTS NOTE 3 1 DIMENSIONS IN MILLIMETRES INCHES...

Page 13: ...ENTRY NOTE 3 MINIMUM DISTANCE TO ADJACENT OBJECTS 320 12 6 FRONT SIDE N STARTCO E N G I N E E R I N G L T D MADE IN SASKATOON CANADA VOLTAGE AT TERMINAL N RISES TO LINE TO NEUTRAL VOLTAGE WHEN A GROUN...

Page 14: ...IGHTS 36 6 1 44 17 3 0 68 29 9 1 17 43 5 1 71 PUSH BUTTON 36 6 1 44 14 9 0 59 29 9 1 17 43 5 1 71 FIGURE 8 RK 302 Remote Indication and Reset NOTES 1 DIMENSIONS IN MILLIMETRES INCHES 2 NEMA 1 FRONT VI...

Page 15: ...2 5 I 3 0 0 1 1 8 25 0 0 98 CI RI GI OUTLINE NOTES 1 DIMENSIONS IN MILLIMETRES INCHES 2 NEMA 1 FIGURE 10 RK 325I Remote Indication Assembly 60 2 31 0 47 5 21 0 2 37 1 22 1 87 0 83 R S 1 R S 2 C G I G...

Page 16: ...he RK 302 RK 325 and RK 325I See Figs 1 and 11 Contact K1 closes when the Ground Fault LED is on and contact K2 closes when the Resistor Fault LED is on 3 7 GROUND FAULT TESTING Use CT primary current...

Page 17: ...004 Operating Mode UV Fail Safe or SH Non Fail Safe Remote Indication 12 Vdc GI RI Current Sink 560 Internal Optional RK 13 Module Contact Ratings 100 mA 120 Vac Contact Configuration N O Form A Reset...

Page 18: ...ation and Reset Assembly RK 325I Indication Assembly RK 13 Relay Interface Module 6 WARRANTY The SE 325 Neutral Grounding Resistor Monitor is warranted to be free from defects in material and workmans...

Page 19: ...bridges can be used to determine the existence of alternate ground paths d Verify proper reaction of the circuit interrupting device in response to a simulated or controlled ground fault current To si...

Page 20: ...LED should be off 7 2 2 VOLTAGE TEST Test Equipment 0 to 120 Vac voltage source and multimeter NOTE Applying the test voltage to the R and G terminals will damage the SE 325 and the ER sensing resist...

Reviews: