Auto-Programmable Controllers
Auto-programmable controllers, 1510000236 /
697096, 700156, or 1510000276 / 366703
(Winnebago), which connect to a rocker switch, have the ability to detect and display several faults. When a
fault is detected, the slide-out
room movement may stop and two different LEDs on the controller will flash
in a pattern.
NOTE:
Not all rocker switches contain fault indicator LEDs. For best results when reading fault codes, refer
to the controller's Fault Code LED scheme and Auto-Programmable Controllers Fault Codes table.
1.
The Fault Code LED on the rocker switch (Fig. 12A) will flash RED a number of times corresponding to
the number of red flashes on the controller (Fig. 13A).
NOTE:
Refer to the Fault Code Table - Auto-Programmable Controllers to best determine what caused the fault.
2.
The Motor LED (Fig. 13B) on the controller will flash GREEN a number of times corresponding to which
motor had the associated fault. For example, two GREEN flashes and four RED flashes means there is a
motor fault on Motor 2.
NOTE:
For major faults, the controller will automatically enter "Emergency Jog" mode when motor
movement is not detected by the controller in either direction during slide-out room activation.
When in "Emergency Jog" mode, the controller will jog both motors in the direction the rocker
switch is pressed (IN or OUT). The rocker switch may need to be pressed multiple times to fully
retract or extend the slide-out room. Take the unit to an OEM-authorized dealer for service.
The controller will return to normal operation mode after five minutes of inactivity or by cycling the power
to the controller.